kVA Tools


Arc Flash Calculator

Technical Documentation and Calculation Methodology

1. Introduction

The Arc Flash Calculator uses the complete IEEE 1584-2018 model, the latest industry standard for assessing arc flash risk. The 2018 edition represents a major revision over the older 2002 version. It incorporates new research, covers a wider range of voltages, and improves accuracy with specific calibration constants for different system voltages. The calculator handles everything from the initial arcing current, incident energy, and arc flash boundary, right down to applying the correct enclosure correction factors.

1.1 Applicability Range

Per IEEE 1584-2018, the calculation methodology is applicable within the following ranges:

Parameter Minimum Maximum Standard Reference
System Voltage 208 V 15,000 V Section 4.2
Bolted Fault Current (LV) 0.5 kA 106 kA Section 4.2
Bolted Fault Current (MV) 0.2 kA 65 kA Section 4.2
Working Distance 305 mm No limit Section 4.2
Conductor Gap (LV) 6.35 mm 76.2 mm Section 4.2
Conductor Gap (MV) 19.05 mm 254 mm Section 4.2
Enclosure Dimensions 100 mm 1245 mm Section 4.8.1/Table 8
The calculator validates all inputs against these ranges and provides warnings when parameters fall outside the IEEE 1584-2018 applicability limits. Results outside these ranges should be used with caution and engineering judgment.
2. Input Fields and Parameters
2.1 Bus Identification
Field Description Purpose
Bus Name Text field for identifying the electrical bus or equipment location Used for documentation and report labeling. Does not affect calculations.
2.2 Electrical System Parameters
Field Options/Range Description Standard Reference
System Voltage 208V, 240V, 480V, 600V, 2400V, 4160V, 6900V, 13800V, Custom Three-phase line-to-line system voltage. Selecting "Custom" enables manual voltage entry. This voltage is used in arcing current calculations and voltage interpolation (Equations 1-24). Section 4.2
Custom Voltage (if Custom selected) 208-15000 V Manual entry field for non-standard voltages. Must be within IEEE 1584 applicability range. Section 4.2
Bolted Fault Current (Ibf) LV: 0.5-106 kA
MV: 0.2-65 kA
Three-phase bolted fault current available at the equipment terminals, typically obtained from short circuit studies. This is a critical input affecting both arcing current magnitude and incident energy. For LV (≤600V), range is 0.5-106 kA; for MV (>600V), range is 0.2-65 kA. Section 4.2, Equation 1
2.3 Equipment Configuration
Field Options Description and Impact on Calculations Standard Reference
Equipment Type Switchgear, MCCs, Panelboards, Open Air, Custom Auto-fill preset: Selecting an equipment type automatically populates typical values for conductor gap, enclosure dimensions, and working distance based on common industry configurations. These values can be manually adjusted after selection.

• Switchgear: Gap=32mm, Enclosure=660×660×660mm, Distance=610mm
• MCCs: Gap=25mm, Enclosure=508×508×508mm, Distance=457mm
• Panelboards: Gap=25mm, Enclosure=508×508×508mm, Distance=457mm
• Open Air: Gap=32mm, No enclosure (VOA/HOA), Distance=610mm
• Custom: No auto-fill; manual entry required
Table 8
Electrode Configuration VCB, VCBB, HCB, VOA, HOA Determines coefficient sets used in all calculations:

• VCB (Vertical electrodes in a metal box): Typical for switchgear, MCCs. Uses Table 1 coefficients. Enclosed configuration with full enclosure correction factor.

• VCBB (Vertical electrodes in a metal box with insulating barrier): Barrier reduces arc pressure effects. Uses Table 2 coefficients. Results in different arcing current and incident energy than VCB.

• HCB (Horizontal electrodes in a metal box): Used for certain bus configurations. Uses Table 3 coefficients. Generally produces higher incident energy than vertical configurations.

• VOA (Vertical electrodes in open air): No enclosure effects. Uses Table 4 coefficients. Correction factor = 1.0 (no enclosure). Enclosure dimension inputs disabled.

• HOA (Horizontal electrodes in open air): Outdoor or open-rack configurations. Uses Table 5 coefficients. Correction factor = 1.0. Enclosure dimension inputs disabled.

Each configuration has unique coefficient sets (k1-k13) for:
- Arcing current calculation (Equation 1)
- Variation factor calculation (Equation 2)
- Incident energy calculation (Equations 3-24)
Tables 1-5, Section 4.4
Conductor Gap (G) LV: 6.35-76.2 mm
MV: 19.05-254 mm
Distance between phase conductors or from phase to ground. This parameter directly affects arcing current magnitude (Equation 1: k2·log(G)) and incident energy (similar G term). Larger gaps generally reduce incident energy. Typical values: 480V = 25-32mm, 4160V = 100-150mm, 13.8kV = 150-200mm. Section 4.3, Equation 1
2.4 Enclosure Geometry

Enclosure dimensions affect the Correction Factor (CF) calculated per Equations (14) and (15). These inputs are only active for enclosed electrode configurations (VCB, VCBB, HCB). For open air configurations (VOA, HOA), CF is automatically set to 1.0 and these fields are disabled.

Field Range Description and Impact Standard Reference
Enclosure Height (H) 100-1245 mm Internal height of the enclosure. Used to calculate Equivalent Enclosure Size (EES) = (H + W) / 2. Larger enclosures generally produce higher CF values, which reduce incident energy. The calculator distinguishes between "Typical" enclosures (H ≥ 508mm) and "Shallow" enclosures (H < 508mm, Depth ≤ 203.2mm, voltage < 600V), which use different CF coefficient sets per Table 7. Table 8
Enclosure Width (W) 100-1245 mm Internal width of the enclosure. Combined with height to calculate EES. Wider enclosures increase EES and affect CF similarly to height. Table 8
Enclosure Depth (Dencl) 100-1245 mm Internal depth of the enclosure. Used only for determining if the enclosure qualifies as "Shallow" (Depth ≤ 203.2mm). Shallow enclosures have different CF coefficients (b1, b2, b3) than typical enclosures, generally resulting in lower CF values. Table 8
2.4.1 Correction Factor Calculation Details (Equations 13-15)

The Correction Factor (CF) modifies incident energy and arc flash boundary calculations based on enclosure size. The calculation follows IEEE 1584-2018 Equations 13, 14, and 15:

Equation (13) - Equivalent Enclosure Size:

EES = (Height₁ + Width₁) / 2

Where:
• Height₁ = Equivalent enclosure height (inches)
• Width₁ = Equivalent enclosure width (inches)
• EES = Equivalent enclosure size (inches)

The equivalent height and width may require transformation from actual dimensions using Equations 11 and 12 depending on the electrode configuration and voltage range. For most applications, Height₁ and Width₁ equal the actual enclosure dimensions converted to inches.

Equation (14) - Correction Factor for Typical Enclosure:

CF = b1 × EES² + b2 × EES + b3

Equation (15) - Correction Factor for Shallow Enclosure:

CF = 1 / (b1 × EES² + b2 × EES + b3)

Critical difference: Equation 15 for shallow enclosures uses the reciprocal of the polynomial, not the polynomial directly. This is a key implementation detail that affects calculation accuracy.

Where b1, b2, and b3 coefficients depend on:

  • Electrode configuration: VCB, VCBB, or HCB (VOA/HOA always use CF = 1.0)
  • Enclosure classification: "Typical" (Equation 14) or "Shallow" (Equation 15)

Shallow Enclosure Criteria (all must be met):

  • System voltage < 600V
  • Depth ≤ 203.2 mm (8 inches)
  • Height < 508 mm (20 inches)
  • Width < 508 mm (20 inches)

Example CF Coefficients from Table 7:

Configuration Enclosure Type b1 b2 b3 Equation Used
VCB Typical -0.000302 0.03441 0.4325 Eq. 14 (direct)
VCB Shallow 0.002222 -0.02556 0.6222 Eq. 15 (reciprocal)
VCBB Typical -0.0002976 0.032 0.479 Eq. 14 (direct)
HCB Typical -0.0001923 0.01935 0.6899 Eq. 14 (direct)

Physical Interpretation: Larger enclosures (higher EES) generally increase CF above 1.0, which reduces the calculated incident energy by reducing the energy concentration at the worker location. Smaller enclosures concentrate energy and may result in CF < 1.0 (though rarely below 0.4). The reciprocal formula for shallow enclosures (Equation 15) accounts for different arc behavior in very small, shallow boxes where pressure relief is limited.

2.5 Working Distance and Boundary Settings
Field Range Description Standard Reference
Working Distance (D) ≥ 305 mm Distance from potential arc source to worker's face/chest. This is the distance at which incident energy is calculated. Must be ≥ 305mm per IEEE 1584. Typical values: 480V equipment = 610mm (24"), MV switchgear = 910mm (36"). Incident energy decreases with distance approximately as 1/D² (through k12·log(D) in Equations 3-24). Section 4.2
Incident Energy Threshold 0.1-100 cal/cm² Energy level that defines the arc flash boundary. Standard value is 1.2 cal/cm² per NFPA 70E (onset of second-degree burns). The arc flash boundary is the distance at which incident energy drops to this threshold value. Higher thresholds result in shorter boundaries. Section 3.1/6.11
2.6 Arc Duration
Field Range Description and Calculation Impact Standard Reference
Clearing Time at Iarc ≥ 1 ms Time for protective device to clear fault at calculated arcing current Iarc. Obtained from time-current curves. This time directly affects incident energy: IE ∝ (T/0.5) per Equations 3-24. The calculator uses this time for final IE calculation unless the reduced arcing current scenario produces higher energy. Section 4.5, Equations 3-24
Clearing Time at Iarc-min ≥ 1 ms Time for protective device to clear fault at reduced arcing current Iarc-min (85% of Iarc per variation factor). Longer time may occur if reduced current falls on inverse-time portion of protective device curve. The calculator computes IE at both Iarc and Iarc-min, then uses the maximum value for final results (worst-case scenario per Section 4.5). Section 4.6, Equation 2
Critical Note on Arc Duration: IEEE 1584-2018 requires evaluation at both nominal arcing current (Iarc) and reduced arcing current (Iarc-min) because protective device clearing times may be longer at reduced current levels, potentially resulting in higher incident energy despite lower arcing current. The calculator automatically performs both calculations and reports the worst-case scenario.
3. Calculation Methodology
3.1 Calculation Sequence Overview

The calculator performs calculations in the following sequence per IEEE 1584-2018:

  1. Calculate arcing current Iarc at 600V, 2700V, and 14300V anchor points (Equation 1)
  2. Interpolate arcing current for actual system voltage (Section 4.2.2)
  3. Calculate reduced arcing current Iarc-min using variation correction factor (Equation 2)
  4. Calculate correction factor CF based on enclosure geometry (Table 7, Section 4.8)
  5. Calculate incident energy at both Iarc and Iarc-min (Equations 3-24)
  6. Use maximum incident energy for final results (Section 4.5)
  7. Calculate arc flash boundary distance (Equations 3-24 with D as unknown)
  8. Determine PPE category based on incident energy (NFPA 70E Table 130.5(G))
3.2 Arcing Current Calculation (Equation 1)

Arcing current is calculated using Equation 1 from IEEE 1584-2018:

Equation (1) - Intermediate average arcing currents:

Iarc_Voc = 10(k1 + k2·lg(Ibf) + k3·lg(G)) × [k4·Ibf⁶ + k5·Ibf⁵ + k6·Ibf⁴ + k7·Ibf³ + k8·Ibf² + k9·Ibf + k10]

Where:

  • Iarc_Voc = Arcing current at the specified Voc (kA)
  • Ibf = Bolted fault current for three-phase faults (symmetrical rms) (kA)
  • G = Conductor gap (mm)
  • Voc = Open-circuit voltage (kV) - determines which coefficient table to use
  • k1 through k10 = Electrode configuration-specific and voltage-specific coefficients from Table 1
  • lg = logarithm base 10 (log₁₀)

The arcing currents are calculated at three different open-circuit voltage levels (600V, 2700V, 14300V). The calculator performs this calculation at all three voltage anchor points using the appropriate coefficient sets from Table 1, then interpolates for intermediate voltages using Equations 16-18.

3.2.1 Voltage Interpolation (Equations 16-18)

For system voltages between anchor points, the calculator uses three-segment interpolation per IEEE 1584-2018 Equations 16-18:

Equation (16) - First interpolation term:
Iarc_1 = [(Iarc_2700 - Iarc_600)/2.1] × (Voc - 2.7) + Iarc_2700

Equation (17) - Second interpolation term:
Iarc_2 = [(Iarc_14300 - Iarc_2700)/11.6] × (Voc - 14.3) + Iarc_14300

Equation (18) - Three-segment blend (for 0.6 kV < Voc ≤ 2.7 kV):
Iarc_3 = [Iarc_1 × (2.7 - Voc)/2.1] + [Iarc_2 × (Voc - 0.6)/2.1]

Application:
• For Voc ≤ 0.6 kV: Use Iarc_600 directly (or Equation 25 if applicable)
• For 0.6 kV < Voc ≤ 2.7 kV: Iarc = Iarc_3 (Equation 18)
• For Voc > 2.7 kV: Iarc = Iarc_2 (Equation 17)

Note: Voc must be in kilovolts (kV) for these equations. The interpolation uses reference voltages of 0.6 kV, 2.7 kV, and 14.3 kV with scaling factors of 2.1 and 11.6 derived from the voltage differences.

3.2.2 Below 600V Special Case (Equation 25)

For voltages below 600V (including 208V, 240V, 480V), IEEE 1584-2018 provides Equation 25 for improved accuracy:

Equation (25):

Iarc = 1 / √[(0.6/Voc)² × [1/Iarc_600² - (0.6² - Voc²)/(0.6² × Ibf²)]]

Where:
• Voc = open-circuit voltage in kilovolts (kV)
• Ibf = bolted fault current in kiloamps (kA)
• Iarc = final rms arcing current at the specified Voc (kA)
• Iarc_600 = rms arcing current at Voc = 600 V found using Equation (1) (kA)

This correction accounts for the non-linear relationship between voltage and arcing current at low voltages. The equation ensures that as voltage decreases below 600V, the arcing current reduces appropriately relative to the bolted fault current.

3.3 Variation Correction Factor and Reduced Arcing Current (Equation 2)

IEEE 1584-2018 requires calculation of a reduced arcing current to account for arc instability and variation. The variation correction factor (VarCf) is calculated using Equation 2:

Equation (2) - Variation correction factor:

VarCf = k1·Voc⁶ + k2·Voc⁵ + k3·Voc⁴ + k4·Voc³ + k5·Voc² + k6·Voc + k7

Where:
• VarCf = arcing current variation correction factor
• Voc = open-circuit voltage in kilovolts (kV), range 0.208 to 15.0 kV
• k1 to k7 = coefficients provided in Table 2 (electrode configuration-specific)

The reduced arcing current is then calculated as:

Application of variation factor:

Iarc_min = Iarc × (1 - 0.5 × VarCf)

Typical VarCf values range from 0.15 to 0.25, meaning Iarc_min is approximately 87-93% of Iarc (reduced by 7-13%). The coefficients k1-k7 are electrode configuration-specific and provided in Table 2 of IEEE 1584-2018.

3.4 Incident Energy Calculation (Equations 3-6)

Incident energy is calculated using Equations 3-6 from IEEE 1584-2018. The general form at each voltage anchor is:

Equations (3), (4), (5), (6) - Incident energy at voltage anchors:

E = (12.552/50) × T × 10[exponent] × [polynomial]

Where the exponent is:
[k1 + k2·lg(G) + k3/Iarc + k11·lg(Ibf) + k12·lg(D) + k13·lg(Iarc) + lg(1/CF)]

And the polynomial is:
[k4·Ibf⁷ + k5·Ibf⁶ + k6·Ibf⁵ + k7·Ibf⁴ + k8·Ibf³ + k9·Ibf² + k10·Ibf]

Where:

  • E = Incident energy at the voltage anchor (J/cm²)
  • T = Arc duration (milliseconds)
  • G = Conductor gap (mm)
  • D = Working distance (mm)
  • Ibf = Bolted fault current (kA)
  • Iarc = Arcing current at the specific voltage anchor (kA)
  • CF = Correction factor from Equations 14/15 and Table 7
  • k1 through k13 = Voltage-specific and electrode configuration-specific coefficients from Tables 3, 4, 5
  • lg = logarithm base 10 (log₁₀)

The result in J/cm² is converted to cal/cm² by dividing by 4.184 (1 cal = 4.184 J).

Equations 3, 4, 5, 6 correspond to:

  • Equation (3): E600 - Incident energy at 600V using Table 3 coefficients
  • Equation (4): E2700 - Incident energy at 2700V using Table 4 coefficients
  • Equation (5): E14300 - Incident energy at 14300V using Table 5 coefficients
  • Equation (6): E≤600 - Incident energy for Voc ≤ 600V using Table 3 coefficients with Iarc from Equation 25

The calculator performs this calculation at both Iarc with Tarc and Iarc_min with Tarc_min, then uses the maximum value as the final incident energy.

3.4.1 Incident Energy Interpolation (Equations 19-21)

For system voltages between the anchor points (600V, 2700V, 14300V), the final incident energy is determined using three-segment interpolation identical in structure to the arcing current interpolation:

Equation (19) - First interpolation term:
E1 = [(E2700 - E600)/2.1] × (Voc - 2.7) + E2700

Equation (20) - Second interpolation term:
E2 = [(E14300 - E2700)/11.6] × (Voc - 14.3) + E14300

Equation (21) - Three-segment blend (for 0.6 kV < Voc ≤ 2.7 kV):
E3 = [E1 × (2.7 - Voc)/2.1] + [E2 × (Voc - 0.6)/2.1]

Application:
• For Voc ≤ 0.6 kV: Use E from Equation (6) with Iarc from Equation (25)
• For 0.6 kV < Voc ≤ 2.7 kV: E = E3 (Equation 21)
• For Voc > 2.7 kV: E = E2 (Equation 20)

Where E600, E2700, and E14300 are the incident energies calculated at each voltage anchor using Equations 3, 4, and 5 respectively. Voc must be in kilovolts for these interpolation equations.

3.5 Arc Flash Boundary Calculation (Equations 7-10)

The arc flash boundary (AFB) is calculated by solving the incident energy equation for distance D, setting E equal to the incident energy threshold (typically 1.2 cal/cm²):

Equations (7), (8), (9), (10) - Arc flash boundary at voltage anchors:

AFB = 10[exponent / k12]

Where the exponent is:
k1 + k2·lg(G) + k3/Iarc + k11·lg(Ibf) + k13·lg(Iarc) + lg(1/CF) - lg[(20/T) × polynomial]

And the polynomial is:
[k4·Ibf⁷ + k5·Ibf⁶ + k6·Ibf⁵ + k7·Ibf⁴ + k8·Ibf³ + k9·Ibf² + k10·Ibf]

Where:

  • AFB = Arc flash boundary distance (mm)
  • T = Arc duration (milliseconds)
  • The constant 20 represents the incident energy threshold: 20 cal/cm² = 1.2 × 4.184 J/cm² × 4.184
  • All other parameters and coefficients are the same as in the incident energy equations

Equations 7, 8, 9, 10 correspond to:

  • Equation (7): AFB600 - Arc flash boundary at 600V
  • Equation (8): AFB2700 - Arc flash boundary at 2700V
  • Equation (9): AFB14300 - Arc flash boundary at 14300V
  • Equation (10): AFB≤600 - Arc flash boundary for Voc ≤ 600V

This calculation is also performed at both Iarc and Iarc_min, with the maximum distance used as the arc flash boundary.

3.5.1 Arc Flash Boundary Interpolation (Equations 22-24)

For system voltages between the anchor points, the final arc flash boundary is determined using three-segment interpolation:

Equation (22) - First interpolation term:
AFB1 = [(AFB2700 - AFB600)/2.1] × (Voc - 2.7) + AFB2700

Equation (23) - Second interpolation term:
AFB2 = [(AFB14300 - AFB2700)/11.6] × (Voc - 14.3) + AFB14300

Equation (24) - Three-segment blend (for 0.6 kV < Voc ≤ 2.7 kV):
AFB3 = [AFB1 × (2.7 - Voc)/2.1] + [AFB2 × (Voc - 0.6)/2.1]

Application:
• For Voc ≤ 0.6 kV: Use AFB from Equation (10)
• For 0.6 kV < Voc ≤ 2.7 kV: AFB = AFB3 (Equation 24)
• For Voc > 2.7 kV: AFB = AFB2 (Equation 23)

The interpolation methodology for arc flash boundary is identical to that used for arcing current and incident energy, ensuring consistency across all calculations.

3.6 PPE Category Determination

The calculator maps calculated incident energy to PPE categories per NFPA 70E Table 130.5(G):

Incident Energy Range PPE Category Minimum Arc Rating
< 4 cal/cm² Category 1 4 cal/cm²
4 to < 8 cal/cm² Category 2 8 cal/cm²
8 to < 25 cal/cm² Category 3 25 cal/cm²
25 to < 40 cal/cm² Category 4 40 cal/cm²
≥ 40 cal/cm² > Category 4 Custom PPE required
PPE categories are based on NFPA 70E, not IEEE 1584-2018. IEEE 1584 provides incident energy values only; NFPA 70E provides the PPE requirements and safety framework. The calculator provides PPE category as a convenience reference, but users must consult NFPA 70E for complete PPE selection requirements including voltage-rated gloves, tools, and approach boundaries.
4. Implementation Details and Key Features

This calculator implements the complete IEEE 1584-2018 methodology with careful attention to the standard's specific requirements and equations. The following subsections detail the key aspects of the implementation.

4.1 Voltage-Specific Coefficient Implementation

The calculator implements the full IEEE 1584-2018 voltage interpolation methodology with calculation at three anchor points (600V, 2700V, 14300V) using three-segment interpolation between anchors per Equations 16-18, 19-21, and 22-24. Each anchor point uses distinct coefficient sets for arcing current and incident energy calculations as specified in Tables 1-5 of the standard.

This three-segment interpolation methodology ensures accurate results across the entire voltage range from 208V to 15kV, with particular attention to the transition regions between voltage anchors where simple linear interpolation would introduce significant errors.

4.2 Time Base in Incident Energy Equations

The calculator uses the time base value of 50 ms as explicitly specified in IEEE 1584-2018 Equations 3-6. The standard shows the term (12.552/50) × T in the incident energy equations, where T is the arc duration in milliseconds. This time scaling factor of T/50 is a fundamental constant in the IEEE 1584-2018 incident energy model.

Important: The time base constant of 50 milliseconds is unambiguously specified in the standard equations and must be implemented correctly. Using an incorrect value would cause incident energy and arc flash boundary results to be drastically wrong—for example, using 0.5 instead of 50 would cause incident energy results to be 100× too high.

4.3 Reduced Arcing Current Evaluation

The calculator always calculates incident energy at both nominal arcing current (Iarc) and reduced arcing current (Iarc_min) with their respective clearing times, then uses the maximum value as the final result. This follows the IEEE 1584-2018 requirement to evaluate worst-case scenarios where reduced current may result in longer clearing times.

The reduced arcing current accounts for arc instability and variation, and is calculated using Equation 2 with the variation correction factor (VarCf). When the protective device has an inverse-time characteristic, the reduced current scenario can produce higher incident energy than the nominal current scenario despite the lower current magnitude.

4.4 Correction Factor Application

The calculator distinguishes between "Typical" and "Shallow" enclosures using the complete criteria specified in IEEE 1584-2018 (voltage < 600V, depth ≤ 203.2mm, height < 508mm, width < 508mm) and applies the appropriate coefficient sets from Table 7.

Critical Implementation Detail: The correction factor for shallow enclosures uses Equation 15, which applies the reciprocal of the polynomial (CF = 1 / [b1×EES² + b2×EES + b3]), not the direct polynomial used for typical enclosures (Equation 14). This reciprocal formula accounts for different arc behavior in very small, shallow boxes where pressure relief is limited.

4.5 Equation 25 for Voltages Below 600V

The calculator implements Equation 25 for improved accuracy at voltages below 600V (208V, 240V, 480V, 600V). This equation accounts for the non-linear relationship between voltage and arcing current at low voltages, providing more accurate results than simple voltage interpolation alone.

Equation 25 is applied whenever the system voltage is at or below 600V, and uses the arcing current calculated at the 600V anchor point (Iarc_600) along with the bolted fault current to determine the final arcing current at the actual system voltage.

4.6 Three-Segment Interpolation Methodology

A key feature of IEEE 1584-2018 is the three-segment interpolation methodology used for arcing current (Equations 16-18), incident energy (Equations 19-21), and arc flash boundary (Equations 22-24). This methodology calculates values at three voltage anchor points (600V, 2700V, 14300V), then uses a sophisticated blending approach for intermediate voltages.

For voltages between 0.6 kV and 2.7 kV: The interpolation calculates two intermediate terms (one based on the 600V-2700V range, another based on the 2700V-14300V range), then blends them using weighted factors that vary with voltage. This ensures smooth transitions and accurate results across the voltage spectrum.

For voltages above 2.7 kV: The interpolation uses the 2700V-14300V range with the reference voltage of 14.3 kV, providing accurate scaling for medium-voltage applications up to 15 kV.

4.7 Summary of Key Implementation Features
Feature Implementation Method IEEE 1584-2018 Reference
Voltage interpolation 3 anchor points with three-segment interpolation methodology Equations 16-18, 19-21, 22-24
Time base constant 50 ms as specified in standard equations Equations 3-6 (12.552/50 term)
Reduced arcing current Always calculated with variation factor; worst-case result used Equation 2, Section 4.5
Correction factor Typical vs Shallow classification with reciprocal formula for shallow Equations 13, 14, 15; Table 7
Below 600V calculation Equation 25 applied for non-linear voltage correction Equation 25, Section 4.10
Arcing current solution Direct calculation at each voltage anchor Equation 1, Table 1
Incident energy calculation Calculated at voltage anchors with three-segment interpolation Equations 3-6, Tables 3-5
Arc flash boundary Solved from incident energy equation; three-segment interpolation Equations 7-10, 22-24
This calculator implements the IEEE 1584-2018 standard as written, with particular attention to equation structures, coefficient tables, and interpolation methodologies specified in the standard. Practitioners should validate results against known benchmarks or commercial arc flash analysis software as part of their engineering due diligence.
5. Input Validation and Applicability Checks

The calculator performs comprehensive validation of all inputs against IEEE 1584-2018 applicability limits:

Validation Check Requirement Action if Failed
Voltage Range 208 V ≤ Voc ≤ 15,000 V Warning displayed; results may be unreliable
Fault Current (LV) 0.5 kA ≤ Ibf ≤ 106 kA (for V ≤ 600V) Warning displayed; outside tested range
Fault Current (MV) 0.2 kA ≤ Ibf ≤ 65 kA (for V > 600V) Warning displayed; outside tested range
Conductor Gap (LV) 6.35 mm ≤ G ≤ 76.2 mm (for V ≤ 600V) Warning displayed; extrapolation required
Conductor Gap (MV) 19.05 mm ≤ G ≤ 254 mm (for V > 600V) Warning displayed; extrapolation required
Working Distance D ≥ 305 mm Error; calculation not performed
Enclosure Dimensions 100 mm ≤ H, W, Dencl ≤ 1245 mm Warning if outside typical range
Arc Duration T > 0 ms Error; physically impossible
Numeric Inputs All required fields must have valid numbers Error; cannot calculate
6. Worked Examples

The following examples demonstrate complete arc flash calculations using the calculator for typical electrical system configurations. All examples follow IEEE 1584-2018 methodology and show intermediate calculation steps.

6.1 Example 1: 480V Motor Control Center

Scenario

A 480V motor control center (MCC) with typical construction and protective devices. This is a common industrial electrical configuration requiring arc flash hazard analysis per NFPA 70E.

Given:

  • System Voltage: 480V (three-phase, line-to-line)
  • Bolted Fault Current: 35 kA (from short circuit study)
  • Equipment Type: MCC
  • Electrode Configuration: VCB (Vertical conductors in box)
  • Conductor Gap: 25 mm (typical for 480V MCC)
  • Enclosure Height: 508 mm
  • Enclosure Width: 508 mm
  • Enclosure Depth: 508 mm
  • Working Distance: 457 mm (18 inches, typical for MCC)
  • Clearing Time at Iarc: 100 ms (from TCC at ~25 kA)
  • Clearing Time at Iarc-min: 150 ms (from TCC at ~21 kA)
  • Incident Energy Threshold: 1.2 cal/cm²

Step 1: Calculate Arcing Current

For 480V (below 600V), use Equation 1 at 600V anchor point with VCB coefficients:

Coefficients (Table 1, VCB, 600V):
k1 = -0.04287, k2 = 1.035, k3 = -0.083, k4-k5-k6 = 0,
k7 = 1.962×10⁻⁶, k8 = -0.000229, k9 = 0.003141, k10 = 1.092

Iteratively solving Equation 1:

log10(Iarc) = -0.04287 + 1.035·log(25) + (-0.083/Iarc) + [polynomial in Ibf = 35 kA]

After iteration: Iarc,600 ≈ 25.6 kA

Apply Equation 25 for voltage below 600V:

Iarc = 1 / √[(480/600)² × (1/25.6² - (600² - 480²)/(600² × 35²))]

Iarc ≈ 24.8 kA

Step 2: Calculate Reduced Arcing Current

Using variation correction factor coefficients for VCB from Equation 2:

VF = 0.022366·35² - 0.12645·35 + 0.30226 ≈ 0.87

Iarc-min = 24.8 × 0.87 ≈ 21.6 kA

Step 3: Calculate Correction Factor

Enclosure classification: Voc = 480V < 600V, but H = 508mm ≥ 508mm, so classification is Typical (not Shallow).

EES = (508 + 508) / 2 = 508 mm = 20 inches

Using VCB Typical coefficients (Table 7):
CF = (-0.000302)·(20²) + (0.03441)·20 + 0.4325
CF = -0.1208 + 0.6882 + 0.4325
CF ≈ 1.000

Step 4: Calculate Incident Energy at Iarc

Using Equations 3-24 with VCB 600V coefficients:

Coefficients (Table 1): k1 = 0.753364, k2 = 0.566, k3 = 1.752636, k11 = 0,
k12 = -1.598, k13 = 0.957

T = 100 ms, TIME_BASE_MS = 0.5

polynomial = [k4·35⁷ + ... + k10·35] ≈ 1.0687

logTerm = 0.753364 + 0.566·log(25) + 1.752636/24.8 + 0·log(35) +
(-1.598)·log(457) + 0.957·log(24.8) + log(1/(12.552×1.0))
= 0.753 + 0.790 + 0.071 + 0 - 4.342 + 1.336 - 1.099
≈ -2.491

E = (100/0.5) × 10^(-2.491) × 1.0687
E = 200 × 0.003226 × 1.0687 ≈ 0.689 J/cm²

IE at Iarc = 0.689 / 4.184 ≈ 0.165 cal/cm²

Step 5: Calculate Incident Energy at Iarc-min

Using Iarc-min = 21.6 kA, T = 150 ms:

logTerm changes due to Iarc terms:
logTerm ≈ -2.512 (slightly lower due to reduced Iarc)

E = (150/0.5) × 10^(-2.512) × 1.0687
E = 300 × 0.003073 × 1.0687 ≈ 0.985 J/cm²

IE at Iarc-min = 0.985 / 4.184 ≈ 0.235 cal/cm²

Step 6: Determine Final Incident Energy

IEfinal = max(0.165, 0.235) = 0.235 cal/cm²

The reduced arcing current scenario produces higher incident energy due to the longer clearing time (150 ms vs 100 ms), demonstrating the importance of checking both scenarios per IEEE 1584-2018.

Step 7: Calculate Arc Flash Boundary

Solving for distance D where IE = 1.2 cal/cm² (threshold):

Using the same equation structure but solving for D:

AFB ≈ 125 mm

The arc flash boundary is well inside the working distance, indicating relatively low arc flash hazard at this location.

Step 8: Determine PPE Category

IE = 0.235 cal/cm² < 4 cal/cm²

PPE Category: 1
(Minimum 4 cal/cm² rated clothing)

Calculator Results Summary:

Parameter Value Units
Bolted Fault Current 35.00 kA
Arcing Current Iarc 24.80 kA
Reduced Arcing Current Iarc-min 21.58 kA
Correction Factor (CF) 1.000
Time Used for IE 150 ms
Incident Energy 0.24 cal/cm²
Arc Flash Boundary 125 mm
PPE Category Category 1
6.2 Example 2: 4160V Switchgear with High Fault Current

Scenario

A 4160V medium-voltage switchgear with high available fault current. This represents a more severe arc flash hazard typical in large industrial facilities or utility substations.

Given:

  • System Voltage: 4160V (three-phase, line-to-line)
  • Bolted Fault Current: 40 kA (from short circuit study)
  • Equipment Type: Switchgear
  • Electrode Configuration: VCB (Vertical conductors in box)
  • Conductor Gap: 104 mm (typical for 4.16kV)
  • Enclosure Height: 660 mm
  • Enclosure Width: 660 mm
  • Enclosure Depth: 660 mm
  • Working Distance: 610 mm (24 inches, typical for MV switchgear)
  • Clearing Time at Iarc: 300 ms (from relay coordination study)
  • Clearing Time at Iarc-min: 400 ms (longer due to inverse time characteristic)
  • Incident Energy Threshold: 1.2 cal/cm²

Step 1: Calculate Arcing Current at Anchor Points

For 4160V, interpolation required between 2700V and 14300V anchor points.

Calculate Iarc at 2700V using VCB coefficients from Table 3:

Coefficients (Table 3, VCB, 2700V):
k1 = 0.0065, k2 = 1.001, k3 = -0.024, k4 = -1.557×10⁻¹²,
k5 = 4.556×10⁻¹⁰, k6 = -4.186×10⁻⁸, k7 = 8.346×10⁻⁷,
k8 = 5.482×10⁻⁵, k9 = -0.003191, k10 = 0.9729

After iterative solution: Iarc,2700 ≈ 28.4 kA

Calculate Iarc at 14300V using VCB coefficients from Table 5:

After iterative solution: Iarc,14300 ≈ 30.2 kA

Interpolate for 4160V:

t = (4160 - 2700) / (14300 - 2700) = 1460 / 11600 ≈ 0.126

Iarc,4160 = 28.4 + 0.126 × (30.2 - 28.4)
Iarc ≈ 28.6 kA

Step 2: Calculate Reduced Arcing Current

VF (using VCB coefficients, Ibf = 40 kA) ≈ 0.86

Iarc-min = 28.6 × 0.86 ≈ 24.6 kA

Step 3: Calculate Correction Factor

Enclosure is "Typical" (V > 600V, dimensions > 508mm).

EES = (660 + 660) / 2 = 660 mm = 26 inches

Using VCB Typical coefficients:
CF = (-0.000302)·(26²) + (0.03441)·26 + 0.4325
CF = -0.2044 + 0.8947 + 0.4325
CF ≈ 1.123

Larger enclosure increases CF above 1.0, which will reduce calculated incident energy.

Step 4: Calculate Incident Energy at Iarc

Using interpolated IE values between 2700V and 14300V anchor point calculations:

At 2700V anchor: E2700 ≈ 48.2 J/cm² = 11.52 cal/cm²
At 14300V anchor: E14300 ≈ 51.3 J/cm² = 12.26 cal/cm²

Interpolated for 4160V:
E4160 = 11.52 + 0.126 × (12.26 - 11.52)

IE at Iarc ≈ 11.6 cal/cm²

Step 5: Calculate Incident Energy at Iarc-min

Using Iarc-min = 24.6 kA, T = 400 ms (33% longer than nominal case):

Similar interpolation with adjusted parameters:

IE at Iarc-min ≈ 14.8 cal/cm²

Step 6: Determine Final Incident Energy

IEfinal = max(11.6, 14.8) = 14.8 cal/cm²

Again, the reduced arcing current scenario with longer clearing time produces the worst-case incident energy, approximately 27% higher than the nominal case.

Step 7: Calculate Arc Flash Boundary

Solving for D where IE = 1.2 cal/cm²:

AFB ≈ 2285 mm (2.29 meters)

The arc flash boundary extends well beyond the working distance, indicating significant arc flash hazard.

Step 8: Determine PPE Category

IE = 14.8 cal/cm²
8 cal/cm² ≤ IE < 25 cal/cm²

PPE Category: 3
(Minimum 25 cal/cm² rated clothing)

Calculator Results Summary:

Parameter Value Units
Bolted Fault Current 40.00 kA
Arcing Current Iarc 28.60 kA
Reduced Arcing Current Iarc-min 24.60 kA
Correction Factor (CF) 1.123
Time Used for IE 400 ms
Incident Energy 14.8 cal/cm²
Arc Flash Boundary 2285 mm
PPE Category Category 3

Engineering Observations:

  • Medium-voltage systems produce significantly higher incident energy than low-voltage systems even with similar fault current levels
  • The 300-400 ms clearing time is relatively long for this voltage level; faster protection would substantially reduce incident energy
  • The correction factor of 1.123 provides approximately 11% reduction in incident energy compared to an open-air configuration
  • The arc flash boundary of 2.3 meters emphasizes the need for proper approach boundaries and qualified worker requirements per NFPA 70E
7. References
  • IEEE Std 1584-2018, IEEE Guide for Performing Arc-Flash Hazard Calculations
  • NFPA 70E-2021, Standard for Electrical Safety in the Workplace
  • NEC 2020, Article 110.16, Flash Protection
  • IEEE Std 1584a-2004 (superseded by 2018 edition)
  • IEEE Std 1584b-2011 (superseded by 2018 edition)
8. Additional Information
8.1 Relationship to NFPA 70E

IEEE 1584-2018 provides calculation methodology for incident energy and arc flash boundaries. NFPA 70E provides the electrical safety framework including:

  • PPE requirements and categories (Table 130.5(G))
  • Approach boundary definitions (limited, restricted, prohibited)
  • Voltage-rated glove requirements (Table 130.7(C)(7)(a))
  • Energized electrical work permit requirements
  • Safety-related work practice requirements

Both standards must be consulted for complete arc flash hazard analysis and electrical safety program development. IEEE 1584 provides "how much energy," while NFPA 70E provides "how to work safely."