kVA Tools logokVA ToolsBETA Standby Planner


Input — Running Load

# Description Load Type Power Rating Power Factor Efficiency (%) Demand Factor Quantity NL Derate (%) kVAr kVA

Populating the Load Type field activates Efficiency and Non-linear (NL) Derate fields.

Input — System & Generator Configuration

Nominal (V)
Configuration
Nameplate Power Factor
Engine type
Turbo derate threshold
Altitude above sea level
Ambient Temperature
Applied to running load (%)

Input — Largest Motor Starting

Largest motor to start (HP) no motor loads in table
Motor starting method
LR kVA multiplier
Locked-rotor kVA/HP
Transient reactance (p.u.)
Allowable bus dip (%)

Voltage dip is estimated using the snapshot method per IEEE 446-1995 §4.2.11: generator modelled as a constant voltage source behind X'd. For full motor acceleration studies, use dedicated power-system software.

Input — Step Load Acceptance

Largest single-step load
Max single-step kW (% of rated)

Default 30% per NFPA 110 for standard generator sets. High-performance prime-power units with fast electronic governors may accept up to 100% in a single step — confirm with manufacturer data.

Output — Sizing Analysis

Parameter Value Units
Running Load
Total running kW kW
Total running kVAr kVAr
Total running kVA kVA
Running kVA (with margin) kVA
Req. Running nameplate kVA kVA
Step Load Acceptance
Step load min. kVA (at nameplate) kVA
Motor Starting
LR kVA — Terminals kVA
LR kVA after starting method reduction kVA
Estimated voltage dip %
Min. generator kVA for dip limit kVA
Governing Result
Min. required nameplate kW kW
Min. required nameplate kVAr kVAr
Min. required nameplate kVA kVA
Governing constraint
Recommended Size
Next standard nameplate kW kW
Equivalent nameplate kVA kVA
Headroom above required

Recommended size is selected from an industry-typical ladder of nameplate kW ratings offered by major OEMs. These rungs are not IEEE or NEMA standardised; confirm the exact rating with the chosen manufacturer's catalogue.

Output — Parameter Status

Parameter Value Units
Site Derating
Altitude derating factor falt p.u.
Temperature derating factor ftemp p.u.
Combined derating factor fcombined p.u.
Check Status
Load inventory
Altitude derating
Temperature derating
Motor starting voltage dip
Step load acceptance
Generator X'd range (0.10–0.50)