kVA Tools logokVATools.io ❯ CT Cabinet


Inputs — Application & System

Standard
Application Type
CT Construction
Rated Secondary
System Voltage
Phase Configuration
Frequency
Max Continuous Load
Load Basis
Max Symmetrical Fault
Fault Duration (s)
Lead-Length Fault Basis
X/R at Fault Point
Min Fault (optional)
Protection Type

Lead-Length Fault Basis sets the lead-loop resistance: a phase-to-ground fault returns through the neutral lead (2 × one-way run, per IEEE C37.110); a balanced 3Ø fault sums to zero in the neutral (1 × one-way run). Ø-G is the conservative default. Fault Duration is the total time the fault can flow; the 1 s thermal rating to specify is If × √t (C57.13 §6.6.2). Relay Ktd (IEC only) is the transient dimensioning factor from the relay manufacturer; blank sizes class P for symmetrical current, as 61869-2 defines it.

Inputs — Burden & Leads

Relay Technology
Relay Burden
Other Devices (VA)
Test Switch / Blocks (Ω)
Meter Burden
Conductor Size
One-way Run Length
Lead Material
Lead Temperature (°C)
Rct at 75 °C (Ω, optional)

Relay Technology prefills typical burdens (microprocessor ≈0.02 Ω, solid-state ≈0.10 Ω, electromechanical ≈1.0 Ω); override the value for the actual device. Leave Rct blank to use a typical-by-ratio estimate (≈2.5 mΩ per secondary turn for 5 A windings, ≈7.5 mΩ per turn for 1 A). Results using the estimate are labelled accordingly; use the test-report value when available.

Inputs — Environment & Class Targets

Average Ambient (°C)
Altitude (m)
Rating Factor (RF)
Metering Class
Protection Class
Multi-ratio (MR) CT

ANSI RF is rated at 30 °C average ambient per IEEE C57.13 §6.5; above 30 °C the effective factor is derated (Figure 1 basis). IEC has no RF concept and instead uses extended current ratings of 120/150/200% per 61869-2 §5.203.

Output — Recommended CT

—

Ratio Load Fault ×In Verdict Rationale
—

Output — Burden Analysis

Quantity Value Units
Lead Loop Resistance — Ω
Device Burden (Σ) — Ω
Total Connected Burden — Ω
Total Burden at Rated Current — VA
Required Standard Burden — —
Burden Verdict — —
Secondary Total Burden VA at Rated Lead Share
—

Output — Saturation & Accuracy

Quantity Value Units
Secondary Fault Current Is — A
Rct Used — Ω
Vs Required (symmetrical) — V
Vs Required × (1 + X/R) — V
Required Accuracy Class — —
Saturation Margin — %
Secondary Current at Load — A
Load Position — % rated
Specify Metering CT As — —
Accuracy Range Verdict — —

Output — Ratings & MR Taps

Quantity Value Units
Effective RF at Ambient — —
Continuous Capability — A
Specify Ith (1 s) ≥ — kA
Dynamic / Mechanical Rating — kA pk
Insulation Class / BIL — —