kVA Tools logokVA ToolsBETA Conduit Filler


Input — Conduit

Input — Conductors

# Wire Type (NEC Table 5) Size Quantity Unit Area (in²) Unit Area (mm²) Unit Area (cm²) Row Total (in²)

Areas from NEC 2026, Table 5. Fill limits from Table 1: 53% (1 conductor), 31% (2 conductors), 40% (3+). Nipple exception: 60% fill for raceways ≤ 24″ in length.

Output — Fill Results

Parameter Value Units
Total Conductor Area in²
Conduit Internal Area in²
Allowable Fill Area in²
Fill Limit Applied
Fill Percentage %
Total Conductors
Result

Output — Advisories

Check Result
Minimum Passing Size / Auto-Size
Jam Ratio (advisory)
Future Fill Advisory

Jam ratio — informational only; not an NEC enforceable requirement (ref. NEC Annex C). Applies when exactly 3 identical conductors are pulled together. Ratio = conduit ID ÷ wire OD. Possible jam: 2.8–3.2. High risk: < 2.8.
Future fill: design practice is to limit actual fill to 40% to leave spare capacity.

NEC Reference

Conductors in Raceway Max Fill Source
1 conductor 53% NEC Ch. 9 Table 1
2 conductors 31% NEC Ch. 9 Table 1
3 or more conductors 40% NEC Ch. 9 Table 1
Nipple ≤ 24″ (any count) 60% NEC Ch. 9, Table 1 Notes

Conduit Application

Conduit Type Sizes Typical Environment Typical Use Key Traits
Electrical Metallic Tubing (EMT) ½″–4″ Dry indoor, exposed Branch circuits, lighting Light steel, easy bend, economical
Intermediate Metal Conduit (IMC) ½″–4″ Indoor/outdoor, damp Feeders, service runs Medium-wall steel, corrosion-resistant
Rigid Metal Conduit (RMC) ½″–6″ Harsh, hazardous Services, industrial feeders Thick-wall steel, max protection
PVC Schedule 40 / 80 ½″–6″ Underground, wet Buried feeders, duct banks Nonmetallic, corrosion-proof
High-Density Polyethylene (HDPE) ½″–4″ Underground duct Utility, telecom, fiber Flexible, smooth interior
Liquidtight Flexible Metal Conduit (LFMC) ⅜″–4″ Wet, vibrating Motors, HVAC, equipment Flexible, liquidtight jacket
Electrical Nonmetallic Tubing (ENT) ½″–2″ Concealed indoor Residential branch wiring Flexible plastic, fast install