kVA Tools logokVATools.io ❯ Arc Flash Calculator


Inputs

System Voltage
3Ø Fault Current
Equipment Type
Electrode Configuration
Conductor Gap
Enclosure Height
Enclosure Width
Enclosure Depth
Working Distance
IE Threshold (cal/cm²)
Protective Device Type
Relay Response at Iarc
Relay Response at Iarc-min

Equipment Type auto-fills typical Gap, Enclosure, and Working Distance values. Also, selecting the Protective Device Type adds the breaker opening time per IEEE 1584.1-2022 Table C.1 (fuses: 0 ms; LV MCCB: 25 ms; LV ICCB/PCB: 50 ms; MV CB: 80 ms) to the device response time from the TCC curve;

Output — Results

Quantity Value Units
Correction Factor (CF) — —
Clearing Time Used — s
Arcing Current Iarc — kA
Arcing Current Iarc-min — kA
Incident Energy — cal/cm²
— J/cm²
Incident Energymin — cal/cm²
— J/cm²
Arc-Flash Boundary — mm
— inches
Arc-Flash Boundarymin — mm
— inches
Recommended PPE Category — —
Recommended PPE Categorymin — —

Only Incident Energy values are derived from IEEE 1584-2018. Recommended PPE Category reflects the corresponding minimum protective equipment required per NFPA 70E-2024 Table 130.7(C)(15)(c).

Output — Parameter Status

Category Status
Required Inputs —
Voltage Range (208 V–15 kV) —
Fault Current Range —
Gap & Enclosure Limits —
Working Distance ≥ 305 mm —
Electrode Configuration —