kVA Tools logokVATools.io ❯ PV Project


PV Project

Technical Documentation and Calculation Methodology

1. Introduction

The PV Project tool sizes the photovoltaic array for a stand-alone PV system per IEEE Std 1562-2021. It is the companion to the Battery Sizer (PV) tool — IEEE 1562 takes the battery sizing output from IEEE 1013 (specifically Worksheet 1 lines 5c, 8d, and 12) and uses it to determine the number and configuration of PV modules required to maintain the battery's state of charge under expected load and solar resource conditions.

The tool computes both controller-type paths in parallel:

  • Shunt / series / PWM — modules cannot adjust array voltage, so the array must be configured to match the battery's nominal voltage. The series count is driven by Vmax and Vmp,new; the parallel count is driven by daily Ah requirement.
  • MPPT — the controller decouples array voltage from battery voltage, allowing the array to operate at its maximum power point. Sizing is energy-based (Wh/day), and the result is typically fewer modules.

Both totals are presented side by side, replicating the comparison the standard's Annex D worked examples explicitly draw.

2. Inputs

2.1 From Battery Sizer (PV) — IEEE 1013

The IEEE 1013 sizing run produces three values needed here:

  • Total daily load (Ah/day) — Worksheet 1 line 5c
  • Maximum battery voltage Vmax (Vdc) — Worksheet 1 line 8d. This is the highest battery charging voltage used (typically the absorption or finish-charge setpoint), which sets a lower bound on Vmp,new.
  • Battery capacity (Ah at the specified hour rate) — Worksheet 1 line 12

Days of autonomy and nominal system voltage are also carried over from the IEEE 1013 sizing.

2.2 Solar resource and array-to-load ratio

Peak sun hours (Sh) is the daily-energy-equivalent of solar irradiation on the plane of the array, expressed in kWh/m² (numerically equal to hours at 1 kW/m² standard irradiance). For non-constant monthly loads, IEEE 1562-2021 §8 recommends sizing using the worst-case-month combination of Sh and A:L.

The array-to-load ratio (A:L) is the ratio of average daily PV ampere-hours to average daily load ampere-hours. Per IEEE 1562-2021 §9.1:

  • 1.1–1.2 for non-critical loads with high, consistent solar irradiance
  • 1.3–1.4 or higher for critical loads or low-irradiance sites

The tool flags A:L values that fall outside the appropriate window for the selected load criticality.

2.3 Losses

System losses are entered as percentages per IEEE 1562-2021 Worksheet 1, item 7. The reference column shows the typical max/min window the standard recommends for each loss source. Each loss is converted to a multiplier of (1 − pct/100), and the total loss is calculated as:

σL,total = 1 − ∏(1 − pcti/100) × 100%

The complement, (1 − σL), appears as the loss factor in the per-module energy and current calculations. Typical combined values fall in the 10–35% range; values outside this window trigger an advisory.

Voltage losses, Vlosses (Vdc), is the total voltage drop between the modules and the battery — wire (round trip), charge controller, blocking diode, shunts and switches (IEEE 1562-2021 §9.6.1 and Annex A). It enters Equation (2) and so sets the number of modules in series; it is a voltage, not a percentage, and does not belong in the system-losses table, so it sits in its own field below the table. Worksheet 1 line 16 leaves the term out, which is the same as Vlosses = 0; the default of 0 V reproduces the Annex D examples.

2.4 PV module datasheet

The tool accepts the standard module-datasheet parameters: Imp, Isc, Vnominal, Voc, Vmp, Pmax, and three temperature coefficients (KT-V for Voc, KT-P for Pmax, KT-I for Isc). Each coefficient has a per-input unit selector for %/°C, V/W/A/°C, or ppm/°C — the conversions to V/°C, W/°C, and A/°C are applied automatically before being used in Equation (1). Maximum ambient temperature and NOCT (nominal operating cell temperature) are used to compute the module operating temperature.

2.5 Charge controller

The MPPT efficiency is entered as a percentage. Per IEEE 1562-2021 footnote 19, the datasheet peak/optimal efficiency derated by 1–2% usually yields a more accurate true efficiency. The shunt/series/PWM path does not use this value — those controller types cannot adjust array voltage, so the parallel-string count is driven by the module's temperature-corrected current, Imp,new (Worksheet 1 line 13).

Every input used in the calculation is required. A blank temperature coefficient, MPPT efficiency or module nominal voltage is not given a default — assuming no temperature derating or a 100 % efficient controller would undersize the array without any warning. A message names any field that is missing or out of range, and the results stay blank until it is corrected.

3. Calculation Methodology

3.1 Module operating conditions (Equation 1)

The module operating temperature is calculated as:

Tmodule = Tambient,max + (NOCT − 25 °C)

The temperature-corrected operating values are then computed via the IEEE 1562-2021 Equation (1) translation:

Vmp,new = Vmp + KT-V × (Tnew − 25 °C)

Pmax,new = Pmax + KT-P × (Tnew − 25 °C)

Imp,new = Imp + KT-I × (Tnew − 25 °C)

Per IEEE 1562-2021 §9.5, Tnew should be the highest anticipated operating temperature so that the resulting Vmp is the lowest expected — this conservatively ensures the module voltage is sufficient to charge the battery in hot conditions. If the temperature coefficient is given in %/°C or ppm/°C, it is converted to V/°C (or W/°C, A/°C) before substitution.

Reference value for the voltage coefficient. IEEE 1562-2021 is not consistent about which voltage a %/°C coefficient is multiplied by. The §9.5 worked example and the Annex A example convert it with Vmp (−0.5 %/°C × 17.0 V = −0.085 V/°C). Worksheet 1 line 10h, and both Annex D examples, use Voc (line 10d × 10g ÷ 100). The tool follows the worksheet:

KT-V (V/°C) = KT-V (%/°C) × Voc ÷ 100

Because Voc is larger than Vmp, this gives the larger voltage drop and is the more conservative choice; it is also the only reading that reproduces Annex D. For the D.2 module it gives Vmp,new = 16.50 V, against 16.79 V with Vmp as the reference; for D.3, 14.74 V against 15.41 V. Where a datasheet gives the coefficient of Vmp itself, enter it in V/°C to use it directly. Pmax and Isc coefficients are referenced to Pmax and Isc (lines 10j and 10l); the Isc coefficient is applied to Imp, as line 10r does.

3.2 Daily array Ah requirement (line 11)

Ah/dayarray = Loaddaily × A:L

This is the array's daily ampere-hour throughput, which incorporates the recharge multiplier needed to replace coulombic and other losses at the desired availability.

3.3 Shunt / series / PWM sizing (Equations 2 and 3)

Modules in series per string is determined by the maximum battery voltage:

ns = ⌈ Vmax / (Vmp,new − Vlosses) ⌉   (Eq. 2)

Vlosses is entered directly (§2.3). Worksheet 1 line 16 divides Vmax by Vmp,new alone, which is Equation (2) with Vlosses = 0. Voltage drops cannot be accounted for through the system-losses table instead: σL is a percentage of the load Ah and only affects Np and the MPPT production in line 20, never ns.

The series count is sensitive to Vlosses when Vmax / Vmp,new is close to a whole number. In the Annex D.3 example (Vmax 58 V, Vmp,new 14.74 V) the ratio is 3.93, so 4 modules in series give 58.98 V. With 0.5 V of losses ns becomes ⌈58 / 14.24⌉ = 5, one more module in every string.

The number of parallel strings is determined by the daily Ah requirement:

Np = ⌈ (LDA × A:L) / [(1 − σL) × Imp,new × Sh] ⌉   (Eq. 3)

The total module count is Np × ns.

3.4 MPPT sizing

The MPPT path sizes by daily energy. The daily load in Wh is:

Wh/dayload = Ah/dayarray × Vnominal,system   (line 19)

Per-module daily production accounts for system losses, sun hours, temperature-derated power, and MPPT converter efficiency:

Wh/daymodule = (1 − σL) × Sh × Pmax,new × ηMPPT   (line 20)

The minimum number of modules and final string configuration are:

Nmin = ⌈ Wh/dayload / Wh/daymodule ⌉   (line 22)

ns,MPPT = ⌈ Vnominal,system / Vnominal,module ⌉   (line 23)

Nstrings = ⌈ Nmin / ns,MPPT ⌉   (line 24)

Ntotal,MPPT = ns,MPPT × Nstrings   (line 25)

4. Worked Example — Vaccine-Storage Refrigerator

Reproduced from IEEE 1562-2021 Annex D.2. A remote vaccine-storage site near the equator, vented lead-acid batteries, six days of autonomy, calculated for both controller types.

4.1 Inputs

Parameter Value
Nominal system voltage 12 Vdc
Days of autonomy 6
Total daily load (line 5c, IEEE 1013) 51.4 Ah/day
Max battery voltage Vmax 14.7 Vdc
Battery capacity 440 Ah at 120-hour rate
Peak sun hours (Brasília, January) 4.4
A:L 1.2
Module: Brand XYZ, 50 W Imp 3.0 A, Vmp 18.3 V, Pmax 50 W
KT-V (Voc) −0.33 %/°C
KT-P (Pmax) −0.23 %/°C
KT-I (Isc) 0.04 %/°C
Tamb,max / NOCT 30 °C / 45 °C
System losses (parasitic, coulombic, wire, mismatch, aging, dust) 1, 17, 3, 0, 11, 1 %
MPPT efficiency 96 %
Voltage losses Vlosses 0 V (line 16 omits the term)

4.2 Module operating conditions

Tmodule = 30 + (45 − 25) = 50 °C, so ΔT = 25 °C.

KT-V = −0.33 %/°C × 21.8 V (Voc, line 10h) = −0.072 V/°C → Vmp,new = 18.3 + (−0.072) × 25 ≈ 16.5 Vdc.

KT-P = −0.23 %/°C × 50 W = −0.115 W/°C → Pmax,new ≈ 47 W.

KT-I = 0.04 %/°C × 3.2 A = 0.00128 A/°C → Imp,new ≈ 3.03 A.

4.3 Energy and losses

Total losses: 1 − (0.99 × 0.83 × 0.97 × 1.0 × 0.89 × 0.99) ≈ 30 %, so (1 − σL) ≈ 0.70.

Daily array Ah: 51.4 × 1.2 = 61.7 Ah/day.

4.4 Shunt / series / PWM result

Ah/day per module: 0.70 × 3.03 × 4.4 = 9.34 Ah/day.

Parallel strings raw: 61.7 / 9.34 = 6.61 → ⌈⌉ = 7 strings.

Series per string: ⌈14.7 / (16.5 − 0)⌉ = 1 module (Vlosses = 0, as in the standard).

Total: 7 modules.

4.5 MPPT result

Daily Wh load: 61.7 × 12 = 740 Wh/day.

Per-module Wh/day: 0.70 × 4.4 × 47 × 0.96 = 139 Wh/day.

Modules raw: 740 / 139 = 5.32 → ⌈⌉ = 6 minimum.

Modules per string: ⌈12 / 12⌉ = 1. Strings: ⌈6 / 1⌉ = 6.

Total: 6 modules.

4.6 Comparison

The MPPT path requires one fewer module than the shunt/series/PWM path — a 14% reduction. This is the central pedagogical point of the IEEE 1562-2021 Annex D worked examples: MPPT controllers can extract more usable energy from the same module, particularly at elevated cell temperatures where the array's maximum-power voltage diverges from the battery voltage.

5. Worked Example — Microwave Repeater

The standard's second worked example (Annex D.3) is a mountaintop telecommunications site near Phoenix, AZ — high reliability, VRLA batteries, MPPT controller, 25-year panel life. Key inputs: 48 Vdc system, 15 days autonomy, 17.8 Ah/day load, 58 Vmax, 660 Ah at 200-hour rate, 5.3 sun hours, A:L 1.3, Brand XYZ 120 W module (Imp 6.8 A, Vmp 18.1 V, Vnom 12), losses (1, 9, 3, 0, 17, 10) totaling 35%, Tamb,max 50 °C, NOCT 45 °C. The worked example yields:

  • Operating conditions: Tmodule = 70 °C, Vmp,new = 14.7 V, Pmax,new = 96.6 W, Imp,new = 7.02 A
  • Shunt/PWM: 23.1 Ah/day ÷ 24.2 Ah/day per module = 0.955 → 1 string; ⌈58 / 14.7⌉ = 4 in series; 4 modules
  • MPPT: 1110 Wh/day ÷ 319 Wh/day per module = 3.47 → 4 modules; 48 / 12 = 4 per string × 1 string = 4 modules

Both controller types need the same 4 modules. The 48 V battery needs four modules in series whichever controller is used, and four modules already supply more than the daily energy. The tool reproduces these results; it gives 96.8 W and 321 Wh/day where the standard rounds KT-P to −0.52 W/°C and (1 − σL) to 0.65, which does not change any module count.

The four-module string reaches 58.98 V at 70 °C, under 1 V above Vmax, so the tool notes the small margin for both controller paths. Any real Vlosses of 0.5 V or more would add a fifth module to the shunt/PWM string (§3.3).

6. Validation Advisories

The tool issues advisory notes in the following cases:

  • A:L below recommended for critical loads — IEEE 1562-2021 §9.1 recommends A:L of 1.3–1.4 or higher for critical loads.
  • A:L outside typical 1.1–1.2 window for non-critical loads — informational, not blocking.
  • Missing or invalid input — the results stay blank and the message names each field that is blank or out of range (§2.5).
  • Vlosses ≥ Vmp,new — Equation (2) has no solution; the shunt/PWM series count is not reported.
  • Shunt/PWM: hot-day voltage forces extra modules in series — ns from Equation (2) is greater than Vnominal,system / Vnominal,module. This is how the IEEE 1562-2021 Annex A failure case appears: a crystalline-silicon module with Vmp 16.90 V and −0.43 %/°C drops to 15.40 V at 46 °C, which may be inadequate to charge a 12 V lead-acid battery, so a second module is needed in every string. Per §9.6.1 the designer either keeps the rounded-up count or selects a different module.
  • Shunt/PWM string within 1 V of Vmax — ns × Vmp,new − Vlosses is less than 1 V above Vmax; a small additional drop would add a module to every string. Informational.
  • MPPT string at or below Vmax — line 23 sets the MPPT string length from nominal voltages only. The tool checks the string's Vmp,new less Vlosses against Vmax and warns when a buck-type MPPT controller would have no headroom to reach Vmax on a hot day; under 1 V of margin is noted for a check against the controller datasheet.
  • MPPT efficiency outside 90–98 % — informational; the standard's typical range.
  • Total losses outside 10–35 % — informational; the standard's §9.4 typical range.
  • Monthly variation reminder — every calculation appends a reminder that non-constant loads should be re-run with worst-case-month sun hours and A:L per §8.

7. Limitations

  • Single-month sizing. The tool sizes for one set of sun-hour and A:L values. For non-constant monthly loads, the user must perform the iterative worst-case analysis described in §8 manually and enter the worst-case figures.
  • No shading model. IEEE 1562-2021 does not address shading; the array is assumed unshaded throughout the day.
  • No PV-hybrid or grid-connected systems. Per the standard's scope, this tool applies only to stand-alone PV systems where PV is the only charging source.
  • No battery-type variation in sizing. While IEEE 1562 mentions that the methodology can be used with battery types beyond lead-acid (per its footnote 3), the integration with IEEE 1013 implies lead-acid in the present companion-tool workflow.
  • No controller, inverter or wire sizing. Per IEEE 1562-2021 §1.1 and §4.1 these are outside the standard's scope. Vlosses is entered as a single total; it is not calculated from wire sizes or controller data.

8. References

8.1 Primary Standard

  1. IEEE Std 1562-2021, IEEE Recommended Practice for Sizing Stand-Alone Photovoltaic (PV) Systems

8.2 Related Standards

  1. IEEE Std 1013-2019, IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stand-Alone Photovoltaic (PV) Systems
    The companion battery-sizing standard whose Worksheet 1 outputs feed the inputs to this tool.
  2. IEEE Std 1361-2024, IEEE Guide for Selection, Charging, Test and Evaluation of Lead-Acid Batteries Used in Stand-Alone Photovoltaic (PV) Systems
    Charge controller technology and battery-charging guidance.
  3. IEEE Std 937-2023, IEEE Recommended Practice for Installation and Maintenance of Lead-Acid Batteries for Photovoltaic (PV) Systems
  4. NFPA 70 (NEC), National Electrical Code, Article 690 — PV system installation requirements; Table 690.7(A) provides sample voltage correction factors referenced in IEEE 1562-2021 §9.5.

8.3 Bibliographic References

  1. NREL/TP-463-5607: Marion, W., and Wilcox, S., "Solar Radiation Data Manual for Flat-plate and Concentrating Collectors," April 1994 — the "Red Book," referenced as the source for sun-hour data in IEEE 1562-2021 Annex D.3.
  2. IEEE Std 1635 / ASHRAE 21, Guide for the Ventilation and Thermal Management of Batteries for Stationary Applications — referenced for coulombic loss data.
  3. Sivertsen, J.C., and Søyland, P., Master's Thesis, "Design and Installation of a Grid-Connected PV System," University of Agder, 2014 — referenced for the Equation (1) translation.