kVA Tools
NEC Cable Sizing Calculator
Technical Documentation and Calculation Methodology
The NEC Cable Sizing Calculator implements conductor sizing per NEC (National Electrical Code) Article 310, using ampacity tables (Table 310.16), temperature correction factors, adjustment factors for multiple conductors, and the 125% continuous load requirement. The calculator is designed for low-voltage conductors (600V and below) in accordance with NFPA 70 (NEC 2023 edition).
The calculator focuses on ampacity-based sizing, temperature and bundling effects, continuous load rules, OCPD coordination, voltage drop checks, and equipment grounding conductor (EGC) sizing. It makes explicit several aspects that are critical to NEC-compliant installations:
- AWG/kcmil conductor sizing system with complete Table 310.16 values
- Temperature correction per Table 310.15(B)(1) with interpolation
- Adjustment factors for conductor bundling per Table 310.15(C)(1)
- 125% continuous load requirement (NEC 210.19, 215.2)
- Next-size-up rule for Overcurrent Protective Devices (OCPD) (NEC 240.4(B))
- Equipment grounding conductor sizing per Table 250.122
- Voltage drop as informational check (not mandatory per NEC)
- Neutral sizing for harmonic loads (>50% third harmonic threshold)
AWG/kcmil System
The NEC uses the American Wire Gauge (AWG) system for smaller conductors (14 AWG through 4/0 AWG) and circular mils (kcmil) for larger conductors (250 kcmil through 2000 kcmil). The AWG system is inverse - smaller numbers indicate larger conductors (e.g., 10 AWG is larger than 14 AWG).
Ampacity
Per NEC Article 100, ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. The base ampacity values are found in Table 310.16 for conductors rated 0-2000 volts.
Continuous Load
NEC Article 100 defines a continuous load as one where the maximum current is expected to continue for 3 hours or more. Examples include HVAC systems, lighting in commercial buildings, and continuously operating motors.
125% Sizing Requirement
NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders require that conductors be sized such that the ampacity (after applying correction factors) is not less than the noncontinuous load plus 125% of the continuous load. This can be expressed as:
Alternatively, the protective device can be rated at 125% of the continuous load, with conductors sized to match the protective device rating.
Conductor Temperature Ratings
Conductors are rated based on the maximum operating temperature of their insulation. Common NEC temperature ratings are:
- 60°C (140°F): Types TW, UF - older installations, limited applications
- 75°C (167°F): Types THW, THWN, XHHW - common for general use
- 90°C (194°F): Types THHN, THWN-2, XHHW-2, RHW-2 - modern installations
Note: While 90°C conductors have higher ampacity, NEC 110.14(C) requires that terminations be evaluated. For circuits 100A or less, or conductors 14 through 1 AWG, use 60°C column. For circuits over 100A with conductors 1/0 and larger, 75°C column can be used if terminations are rated 75°C or higher. This calculator uses the selected temperature rating for sizing but users should verify termination compatibility.
The calculator follows the NEC Article 310 workflow for conductor selection. The algorithm executes the following steps:
- Determine the load current and classify as continuous or non-continuous.
-
Calculate required ampacity:
- Continuous load: Required ampacity = Load × 1.25
- Non-continuous load: Required ampacity = Load × 1.0
- Select conductor material (copper or aluminum) and temperature rating (60°C, 75°C, or 90°C).
- Look up base ampacity from Table 310.16 for selected material and temperature rating.
-
Apply temperature correction factor if ambient temperature differs from 30°C (86°F):
- Obtain correction factor from Table 310.15(B)(1) based on actual ambient temperature
-
Apply adjustment factor if more than three current-carrying conductors are in raceway/cable:
- Obtain adjustment factor from Table 310.15(C)(1) based on conductor count
-
Calculate corrected ampacity:
Corrected Ampacity = Base Ampacity × Temperature Factor × Adjustment Factor
- Verify: Corrected Ampacity ≥ Required Ampacity
-
Select overcurrent protective device (OCPD) from standard ratings in Table 240.6(A).
- NEC 240.4(B): If corrected ampacity doesn't match a standard OCPD size, next size up is permitted (if ≤ 800A and not for specific small circuits)
- Size equipment grounding conductor (EGC) from Table 250.122 based on OCPD rating.
-
Check voltage drop (informational - not mandatory by NEC):
- NEC 210.19(A) Informational Note No. 4: Branch circuits - 3% recommended
- NEC 215.2(A)(1) Informational Note No. 2: Feeders - 3% recommended
- Combined branch circuit and feeder: 5% total recommended
- Size neutral conductor considering harmonic content per NEC 310.15(C)(1) Exception.
The calculator organizes inputs into logical groups matching the NEC sizing workflow. This section describes each input field, its valid range, and how it affects the calculation.
| Control/Field | Options/Range | Effect on Calculation | NEC Reference |
|---|---|---|---|
| Load Current (A) | 0.1 to 10,000 A | Starting point for all sizing. This is the actual load current the conductor must carry. | 210.19, 215.2 |
| Load Type | Continuous / Non-continuous | Continuous loads (≥3 hours) require 125% sizing factor. Required ampacity = Load × 1.25 for continuous, Load × 1.0 for non-continuous. | 210.19(A)(1), Article 100 |
| System Type | Single-phase / Three-phase | Affects voltage drop formula. Single-phase uses 2×I×Z×L, three-phase uses √3×I×Z×L. | — |
| System Voltage (V) | 120 / 208 / 240 / 277 / 480 / 600 | Used for voltage drop calculation. Higher voltage = lower percentage drop for same power level. | — |
| Power Factor | 0.1 to 1.0 | Affects voltage drop through R cos φ + X sin φ term. Lower PF increases voltage drop due to reactive component. | — |
| Harmonic Content (%) | 0 to 100% | If >50% third harmonic, neutral counts as current-carrying conductor per NEC 310.15(C)(1) Exception. Affects neutral sizing. | 310.15(C)(1) Exception |
| Control/Field | Options/Range | Effect on Calculation | NEC Reference |
|---|---|---|---|
| Material | Copper / Aluminum | Selects column in Table 310.16. Copper has higher ampacity and lower resistance than aluminum for same size. | Table 310.16 |
| Temperature Rating | 60°C / 75°C / 90°C | Selects row in Table 310.16. Higher ratings allow higher ampacity. Also affects temperature correction factor range. Note: Verify termination ratings per 110.14(C). | Table 310.16, 110.14(C) |
| Current-Carrying Conductors | 1 to 50 | Number of conductors in raceway/cable carrying current. Triggers adjustment factor per Table 310.15(C)(1). ≤3 = no adjustment. >3 = reduced ampacity. | Table 310.15(C)(1) |
| Control/Field | Options/Range | Effect on Calculation | NEC Reference |
|---|---|---|---|
| Ambient Temperature | 10-80°C (50-176°F) | Reference is 30°C (86°F). Temperatures above reduce ampacity (hot environment). Temperatures below increase ampacity (cold environment). Applied via Table 310.15(B)(1). | Table 310.15(B)(1) |
| Temperature Unit | °C / °F | Display preference. Calculator converts internally to Celsius for table lookups. NEC uses Celsius primarily. | — |
| Conduit Type | PVC / Aluminum / Steel-EMT | Affects conductor reactance (X) used in voltage drop. Steel conduit has slightly higher reactance than PVC due to magnetic effects. | Chapter 9, Table 9 |
| Control/Field | Options/Range | Effect on Calculation | NEC Reference |
|---|---|---|---|
| Circuit Length (feet) | 1 to 10,000 feet | One-way circuit length. Voltage drop is proportional to length: ΔV = I × Z × L. Longer circuits require larger conductors to meet voltage drop limits. | 210.19(A) Note 4 |
| Voltage Drop Limit (%) | 0.1 to 10% | Acceptance criterion. NEC recommends 3% for branch circuits, 3% for feeders (5% combined). This is informational only - not a code requirement. | 210.19(A) Note 4, 215.2(A) Note 2 |
The calculator provides comprehensive output organized into sizing summary, correction factors, and verification checks. All outputs reference applicable NEC sections for traceability.
| Output Field | Description | How Determined |
|---|---|---|
| Selected Phase Conductor | AWG or kcmil size for phase conductors | Smallest conductor from Table 310.16 where corrected ampacity ≥ required ampacity and voltage drop ≤ limit |
| Selected Neutral | AWG or kcmil size for neutral | Same as phase for harmonic content >50%, may be reduced otherwise per NEC 220.61. Calculator keeps equal to phase for safety. |
| Equipment Ground (EGC) | AWG or kcmil size for grounding | From Table 250.122 based on OCPD rating. If phase conductors upsized for voltage drop, EGC must increase proportionally. |
| Load Current (A) | Actual load current entered | From user input. This is the current the circuit actually carries. |
| Required Ampacity (A) | Minimum conductor ampacity needed | Load × 1.25 if continuous, Load × 1.0 if non-continuous. This is what the corrected ampacity must meet or exceed. |
| Base Ampacity (A) | Table 310.16 value for selected conductor | Direct lookup from Table 310.16 based on size, material, and temperature rating. Before any corrections. |
| Corrected Ampacity (A) | Ampacity after correction factors | Base Ampacity × Temperature Factor × Adjustment Factor. This is the actual ampacity under installation conditions. |
| Selected OCPD Rating (A) | Overcurrent device size | Standard size from Table 240.6(A) that protects the conductor. Next-size-up rule applied if applicable per 240.4(B). |
| Voltage Drop (V) | Voltage drop in volts | Calculated from conductor impedance, current, and length using Chapter 9 Table 9 values for R and X. |
| Voltage Drop (%) | Voltage drop as percentage of system voltage | (Voltage Drop in V / System Voltage) × 100. Compared against limit (typically 3%). |
| Factor | Source | Typical Range | Effect |
|---|---|---|---|
| Temperature Factor | Table 310.15(B)(1) | 0.41 to 1.29 | Corrects ampacity for ambient temperature. <1.0 if hot, >1.0 if cold. Reference: 30°C (86°F). |
| Adjustment Factor | Table 310.15(C)(1) | 0.35 to 1.0 | Reduces ampacity for conductor bundling. 1.0 for ≤3 conductors, reduces for >3 due to heat buildup. |
| Total Factor | Product of above | 0.14 to 1.29 | Combined effect of temperature and bundling. Corrected Ampacity = Base × Total Factor. |
Ampacity Check: Verifies that Corrected Ampacity ≥ Required Ampacity. PASS means conductor can safely carry the load under installation conditions. FAIL means a larger conductor is needed.
Voltage Drop Check: Verifies that calculated voltage drop ≤ specified limit. Note that NEC voltage drop limits are informational recommendations, not mandatory requirements. However, excessive voltage drop can cause equipment malfunction and energy waste.
OCPD Coordination: Notes whether next-size-up rule was applied. Per NEC 240.4(B), if the conductor's corrected ampacity doesn't correspond to a standard OCPD rating, the next higher standard rating (not exceeding 800A) is permitted.
This example demonstrates the complete NEC sizing workflow for a typical industrial motor feeder circuit.
- Application: Three-phase motor feeder
- Load Current: 100 A (continuous operation)
- System: 480V, three-phase
- Power Factor: 0.90 (typical for motors)
- Conductor Material: Copper
- Insulation: THWN (75°C rated)
- Installation: 3 current-carrying conductors in PVC conduit
- Ambient Temperature: 40°C (104°F) - hot mechanical room
- Circuit Length: 150 feet (one-way)
- Voltage Drop Limit: 3% (NEC recommendation)
Step 1: Determine Required Ampacity
Motor load is continuous (runs >3 hours). Per NEC 210.19 and 215.2:
Required Ampacity = 100 A × 1.25 = 125 A
Step 2: Select Base Conductor Size
From Table 310.16, Copper, 75°C column, try 1 AWG:
Step 3: Apply Temperature Correction
Ambient is 40°C. From Table 310.15(B)(1), 75°C column, 40°C ambient:
Step 4: Apply Adjustment Factor
Three current-carrying conductors. From Table 310.15(C)(1):
Step 5: Calculate Corrected Ampacity
Corrected Ampacity = 130 A × 0.88 × 1.0 = 114.4 A
FAILS: 114.4 A < 125 A required. Need larger conductor.
Step 6: Try Next Size - 1/0 AWG
From Table 310.16, Copper, 75°C column:
Corrected Ampacity = 150 A × 0.88 × 1.0 = 132 A
PASSES: 132 A ≥ 125 A required
Step 7: Select OCPD Rating
Required OCPD rating ≥ 125 A (for continuous load). From Table 240.6(A), standard sizes include: ..., 110A, 125A, 150A, ...
Step 8: Size Equipment Grounding Conductor
From Table 250.122, for 125 A OCPD:
Step 9: Check Voltage Drop
From Chapter 9, Table 9, for 1/0 AWG copper in PVC conduit at 75°C:
- Resistance (R) = 0.122 Ω per 1000 feet
- Reactance (X) = 0.044 Ω per 1000 feet (PVC)
For three-phase circuit:
Where:
I = 100 A (load current, not required ampacity)
cos φ = 0.90
sin φ = sin(arccos 0.90) = 0.436
L = 150 ft = 0.150 per 1000 ft
Impedance term:
Z_eff = R cos φ + X sin φ
Z_eff = 0.122 × 0.90 + 0.044 × 0.436
Z_eff = 0.1098 + 0.0192 = 0.129 Ω/1000 ft
Voltage drop:
ΔV = 1.732 × 100 × 0.129 × 0.150
ΔV = 3.35 volts
Percentage:
ΔV% = (3.35 / 480) × 100 = 0.70%
PASSES: 0.70% < 3% limit
| Component | Size/Rating | Notes |
|---|---|---|
| Phase Conductors | 1/0 AWG | Copper, THWN (75°C), 3 conductors in PVC conduit |
| Neutral Conductor | 1/0 AWG | Same as phase (motor load, balanced, low harmonics) |
| Equipment Ground | 8 AWG | Copper, per Table 250.122 for 125A OCPD |
| Overcurrent Device | 125 A | Circuit breaker or fuses rated 125A |
| Conduit | TBD | Size per NEC Chapter 9, Table 4 for (4) conductors |
NEC Article 100 defines a continuous load as one where the maximum current is expected to continue for three hours or more. Common continuous loads include:
- HVAC systems (air conditioning, heating)
- Commercial lighting systems
- Continuously operating motors and pumps
- Process equipment in industrial facilities
- Data center and telecommunications equipment
Per NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders, conductors must be sized so that the ampacity (after applying correction factors) is not less than:
Alternatively, the overcurrent protective device (OCPD) can be rated at not less than 125% of the continuous load plus 100% of the noncontinuous load, with conductors sized to match or exceed the OCPD rating. Both approaches yield equivalent results.
NEC 240.4(B) allows the use of the next higher standard overcurrent device rating (above the conductor ampacity) if the conductor ampacity does not correspond to a standard OCPD rating from Table 240.6(A). This rule is subject to limitations:
- Applies only if the next size up does not exceed 800 amperes
- Does not apply to 120V 15A and 20A branch circuits (must use exact sizes)
- Conductor ampacity (after corrections) must still be adequate for the load
Example: A conductor with corrected ampacity of 118A can be protected by a 125A OCPD (next standard size up), but a conductor with corrected ampacity of 118A cannot be protected by a 150A OCPD.
When more than three current-carrying conductors are in a raceway or cable, the ampacity of each conductor must be reduced per Table 310.15(C)(1). The adjustment accounts for reduced heat dissipation when multiple conductors are bundled:
| Number of Current-Carrying Conductors | Adjustment Factor (%) |
|---|---|
| 1-3 | 100% (no adjustment) |
| 4-6 | 80% |
| 7-9 | 70% |
| 10-20 | 50% |
| 21-30 | 45% |
| 31-40 | 40% |
| 41 or more | 35% |
Exception: The neutral conductor of a 3-wire, single-phase circuit or 4-wire, three-phase wye circuit is not considered current-carrying UNLESS there is more than 50% third harmonic content. This exception is critical for nonlinear loads.
In circuits supplying nonlinear loads (electronic equipment, LED drivers, switching power supplies), third harmonic currents do not cancel in the neutral conductor. When third harmonic content exceeds 50%, the neutral must be counted as a current-carrying conductor and sized accordingly:
- If neutral current is expected to equal or exceed phase current, neutral must be same size as phase
- Neutral is included in conductor count for adjustment factor purposes
- In extreme cases, neutral may need to be larger than phase conductors
Common sources of high harmonic content: data centers, office buildings with LED lighting, facilities with many switching power supplies, variable frequency drives (VFDs).
While conductors may be rated for 90°C operation, terminals on equipment are often rated for lower temperatures. NEC 110.14(C) requires consideration of termination temperature ratings:
- For circuits rated 100A or less, or conductors 14 AWG through 1 AWG: Use the 60°C ampacity column unless the equipment is listed for 75°C
- For circuits rated over 100A, or conductors 1/0 AWG and larger: Use the 75°C ampacity column unless the equipment is listed for higher temperatures
Practical Application: Even with 90°C rated THHN/THWN-2 conductors, you may need to use the 75°C ampacity for sizing. However, the 90°C rating is valuable for applying correction factors - you can use the 90°C column ampacity with corrections, then verify the resulting ampacity meets the 75°C termination requirement.
The equipment grounding conductor (EGC) provides a low-impedance path for fault currents, enabling rapid operation of overcurrent devices. Key requirements:
- Size based on rating of overcurrent device ahead of equipment (Table 250.122)
- If phase conductors are increased in size for voltage drop, EGC must be increased proportionally
- Minimum size: 14 AWG copper for circuits ≤15A, 12 AWG copper for circuits ≤20A
- EGC may be solid or stranded conductor, or in the form of raceway, armor, or shield
NEC 210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2 recommend voltage drop limits but do not mandate them:
- Branch Circuits: 3% maximum recommended
- Feeders: 3% maximum recommended
- Combined (feeder + branch circuit): 5% maximum recommended
While not code requirements, these limits represent good engineering practice. Excessive voltage drop can cause:
- Motor overheating and reduced life
- Lamp dimming and reduced light output
- Electronic equipment malfunction
- Increased energy consumption
- Inability to start large motors
This calculator implements NEC 2023 (NFPA 70-2023) requirements. Always verify:
- Which NEC edition has been adopted in your jurisdiction
- Any state or local amendments to the NEC
- Special requirements for your specific industry or application
- More restrictive requirements from other applicable codes (building codes, fire codes)
The calculator uses standard values from NEC tables, which represent typical installation conditions. Actual conductor ampacities and properties may vary based on:
- Specific manufacturer and construction
- Cable configuration (flat vs. triplexed vs. separated)
- Installation method details
- Thermal characteristics of surrounding materials
For critical applications, verify conductor properties with manufacturer data sheets.
- Parallel Conductors: NEC 310.10(G) requirements for paralleling not automated
- Very Large Conductors: Sizes larger than 2000 kcmil require custom analysis
- Medium Voltage: Systems above 2000V use different tables (310.60 series)
- Special Cables: Mineral-insulated (MI), aerial, or submarine cables have different ratings
- Specific Installation Methods: Duct banks, direct burial in concrete, etc., may require detailed analysis
- High Altitude: May affect equipment but not conductor sizing per NEC
This calculator is intended for preliminary sizing and educational purposes. For final designs:
- Engage a licensed practitioner for plans requiring professional seal
- Perform detailed short-circuit and coordination studies
- Consider future load growth and system flexibility
- Verify all assumptions with field conditions
- Document all calculations and bases of design
- Consider using safety margins (10-25%) beyond minimum code requirements
- Evaluate alternative solutions and life-cycle costs
- Verify calculator results against manual calculations for critical circuits
- Compare results from multiple sizing methods
- Have calculations reviewed by a second qualified person
- Maintain documentation of all design decisions and assumptions
- Update designs if field conditions differ from assumptions
- NFPA 70-2023, National Electrical Code (NEC)
- Article 100: Definitions
- Article 210: Branch Circuits
- Article 215: Feeders
- Article 240: Overcurrent Protection
- Article 250: Grounding and Bonding
- Article 310: Conductors for General Wiring
- Chapter 9: Tables and Annexes
- NFPA 70E-2021, Standard for Electrical Safety in the Workplace
National Fire Protection Association (NFPA), Quincy, MA
For conductor-specific data and installation guidance, consult manufacturer technical literature:
- Southwire Company LLC - Wire and Cable Technical Reference
- General Cable - Product Engineering Handbooks
- Encore Wire Corporation - Technical Data Sheets
- Prysmian Group - Engineering Resources
- Nexans - Technical Documentation