kVA Tools


NEC Cable Sizing Calculator

Technical Documentation and Calculation Methodology

1. Introduction

The NEC Cable Sizing Calculator implements conductor sizing per NEC (National Electrical Code) Article 310, using ampacity tables (Table 310.16), temperature correction factors, adjustment factors for multiple conductors, and the 125% continuous load requirement. The calculator is designed for low-voltage conductors (600V and below) in accordance with NFPA 70 (NEC 2023 edition).

The calculator focuses on ampacity-based sizing, temperature and bundling effects, continuous load rules, OCPD coordination, voltage drop checks, and equipment grounding conductor (EGC) sizing. It makes explicit several aspects that are critical to NEC-compliant installations:

  • AWG/kcmil conductor sizing system with complete Table 310.16 values
  • Temperature correction per Table 310.15(B)(1) with interpolation
  • Adjustment factors for conductor bundling per Table 310.15(C)(1)
  • 125% continuous load requirement (NEC 210.19, 215.2)
  • Next-size-up rule for Overcurrent Protective Devices (OCPD) (NEC 240.4(B))
  • Equipment grounding conductor sizing per Table 250.122
  • Voltage drop as informational check (not mandatory per NEC)
  • Neutral sizing for harmonic loads (>50% third harmonic threshold)
This calculator uses NEC 2023 tables and requirements. Always verify against the current NEC edition applicable in your jurisdiction and check for local amendments. For final designs, consult a licensed professional.
2. Fundamental Definitions
2.1 Conductor Sizes & Terminology

AWG/kcmil System

The NEC uses the American Wire Gauge (AWG) system for smaller conductors (14 AWG through 4/0 AWG) and circular mils (kcmil) for larger conductors (250 kcmil through 2000 kcmil). The AWG system is inverse - smaller numbers indicate larger conductors (e.g., 10 AWG is larger than 14 AWG).

Ampacity

Per NEC Article 100, ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. The base ampacity values are found in Table 310.16 for conductors rated 0-2000 volts.

2.2 Load Classifications

Continuous Load

NEC Article 100 defines a continuous load as one where the maximum current is expected to continue for 3 hours or more. Examples include HVAC systems, lighting in commercial buildings, and continuously operating motors.

125% Sizing Requirement

NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders require that conductors be sized such that the ampacity (after applying correction factors) is not less than the noncontinuous load plus 125% of the continuous load. This can be expressed as:

Required Ampacity = Non-continuous Load + (1.25 × Continuous Load)

Alternatively, the protective device can be rated at 125% of the continuous load, with conductors sized to match the protective device rating.

2.3 Temperature Ratings

Conductor Temperature Ratings

Conductors are rated based on the maximum operating temperature of their insulation. Common NEC temperature ratings are:

  • 60°C (140°F): Types TW, UF - older installations, limited applications
  • 75°C (167°F): Types THW, THWN, XHHW - common for general use
  • 90°C (194°F): Types THHN, THWN-2, XHHW-2, RHW-2 - modern installations

Note: While 90°C conductors have higher ampacity, NEC 110.14(C) requires that terminations be evaluated. For circuits 100A or less, or conductors 14 through 1 AWG, use 60°C column. For circuits over 100A with conductors 1/0 and larger, 75°C column can be used if terminations are rated 75°C or higher. This calculator uses the selected temperature rating for sizing but users should verify termination compatibility.

3. Calculation Workflow

The calculator follows the NEC Article 310 workflow for conductor selection. The algorithm executes the following steps:

  1. Determine the load current and classify as continuous or non-continuous.
  2. Calculate required ampacity:
    • Continuous load: Required ampacity = Load × 1.25
    • Non-continuous load: Required ampacity = Load × 1.0
  3. Select conductor material (copper or aluminum) and temperature rating (60°C, 75°C, or 90°C).
  4. Look up base ampacity from Table 310.16 for selected material and temperature rating.
  5. Apply temperature correction factor if ambient temperature differs from 30°C (86°F):
    • Obtain correction factor from Table 310.15(B)(1) based on actual ambient temperature
  6. Apply adjustment factor if more than three current-carrying conductors are in raceway/cable:
    • Obtain adjustment factor from Table 310.15(C)(1) based on conductor count
  7. Calculate corrected ampacity:
    Corrected Ampacity = Base Ampacity × Temperature Factor × Adjustment Factor
  8. Verify: Corrected Ampacity ≥ Required Ampacity
  9. Select overcurrent protective device (OCPD) from standard ratings in Table 240.6(A).
    • NEC 240.4(B): If corrected ampacity doesn't match a standard OCPD size, next size up is permitted (if ≤ 800A and not for specific small circuits)
  10. Size equipment grounding conductor (EGC) from Table 250.122 based on OCPD rating.
  11. Check voltage drop (informational - not mandatory by NEC):
    • NEC 210.19(A) Informational Note No. 4: Branch circuits - 3% recommended
    • NEC 215.2(A)(1) Informational Note No. 2: Feeders - 3% recommended
    • Combined branch circuit and feeder: 5% total recommended
  12. Size neutral conductor considering harmonic content per NEC 310.15(C)(1) Exception.
Per the NEC, voltage drop limits are recommendations, not requirements. However, excessive voltage drop can cause equipment malfunction and should be evaluated for all circuits.
4. User Interface Inputs

The calculator organizes inputs into logical groups matching the NEC sizing workflow. This section describes each input field, its valid range, and how it affects the calculation.

4.1 Load & System Parameters
Control/Field Options/Range Effect on Calculation NEC Reference
Load Current (A) 0.1 to 10,000 A Starting point for all sizing. This is the actual load current the conductor must carry. 210.19, 215.2
Load Type Continuous / Non-continuous Continuous loads (≥3 hours) require 125% sizing factor. Required ampacity = Load × 1.25 for continuous, Load × 1.0 for non-continuous. 210.19(A)(1), Article 100
System Type Single-phase / Three-phase Affects voltage drop formula. Single-phase uses 2×I×Z×L, three-phase uses √3×I×Z×L.
System Voltage (V) 120 / 208 / 240 / 277 / 480 / 600 Used for voltage drop calculation. Higher voltage = lower percentage drop for same power level.
Power Factor 0.1 to 1.0 Affects voltage drop through R cos φ + X sin φ term. Lower PF increases voltage drop due to reactive component.
Harmonic Content (%) 0 to 100% If >50% third harmonic, neutral counts as current-carrying conductor per NEC 310.15(C)(1) Exception. Affects neutral sizing. 310.15(C)(1) Exception
4.2 Conductor Selection
Control/Field Options/Range Effect on Calculation NEC Reference
Material Copper / Aluminum Selects column in Table 310.16. Copper has higher ampacity and lower resistance than aluminum for same size. Table 310.16
Temperature Rating 60°C / 75°C / 90°C Selects row in Table 310.16. Higher ratings allow higher ampacity. Also affects temperature correction factor range. Note: Verify termination ratings per 110.14(C). Table 310.16, 110.14(C)
Current-Carrying Conductors 1 to 50 Number of conductors in raceway/cable carrying current. Triggers adjustment factor per Table 310.15(C)(1). ≤3 = no adjustment. >3 = reduced ampacity. Table 310.15(C)(1)
4.3 Environmental Conditions
Control/Field Options/Range Effect on Calculation NEC Reference
Ambient Temperature 10-80°C (50-176°F) Reference is 30°C (86°F). Temperatures above reduce ampacity (hot environment). Temperatures below increase ampacity (cold environment). Applied via Table 310.15(B)(1). Table 310.15(B)(1)
Temperature Unit °C / °F Display preference. Calculator converts internally to Celsius for table lookups. NEC uses Celsius primarily.
Conduit Type PVC / Aluminum / Steel-EMT Affects conductor reactance (X) used in voltage drop. Steel conduit has slightly higher reactance than PVC due to magnetic effects. Chapter 9, Table 9
4.4 Voltage Drop Parameters
Control/Field Options/Range Effect on Calculation NEC Reference
Circuit Length (feet) 1 to 10,000 feet One-way circuit length. Voltage drop is proportional to length: ΔV = I × Z × L. Longer circuits require larger conductors to meet voltage drop limits. 210.19(A) Note 4
Voltage Drop Limit (%) 0.1 to 10% Acceptance criterion. NEC recommends 3% for branch circuits, 3% for feeders (5% combined). This is informational only - not a code requirement. 210.19(A) Note 4, 215.2(A) Note 2
5. Output Parameters

The calculator provides comprehensive output organized into sizing summary, correction factors, and verification checks. All outputs reference applicable NEC sections for traceability.

5.1 Results
Output Field Description How Determined
Selected Phase Conductor AWG or kcmil size for phase conductors Smallest conductor from Table 310.16 where corrected ampacity ≥ required ampacity and voltage drop ≤ limit
Selected Neutral AWG or kcmil size for neutral Same as phase for harmonic content >50%, may be reduced otherwise per NEC 220.61. Calculator keeps equal to phase for safety.
Equipment Ground (EGC) AWG or kcmil size for grounding From Table 250.122 based on OCPD rating. If phase conductors upsized for voltage drop, EGC must increase proportionally.
Load Current (A) Actual load current entered From user input. This is the current the circuit actually carries.
Required Ampacity (A) Minimum conductor ampacity needed Load × 1.25 if continuous, Load × 1.0 if non-continuous. This is what the corrected ampacity must meet or exceed.
Base Ampacity (A) Table 310.16 value for selected conductor Direct lookup from Table 310.16 based on size, material, and temperature rating. Before any corrections.
Corrected Ampacity (A) Ampacity after correction factors Base Ampacity × Temperature Factor × Adjustment Factor. This is the actual ampacity under installation conditions.
Selected OCPD Rating (A) Overcurrent device size Standard size from Table 240.6(A) that protects the conductor. Next-size-up rule applied if applicable per 240.4(B).
Voltage Drop (V) Voltage drop in volts Calculated from conductor impedance, current, and length using Chapter 9 Table 9 values for R and X.
Voltage Drop (%) Voltage drop as percentage of system voltage (Voltage Drop in V / System Voltage) × 100. Compared against limit (typically 3%).
5.2 Correction Factors
Factor Source Typical Range Effect
Temperature Factor Table 310.15(B)(1) 0.41 to 1.29 Corrects ampacity for ambient temperature. <1.0 if hot, >1.0 if cold. Reference: 30°C (86°F).
Adjustment Factor Table 310.15(C)(1) 0.35 to 1.0 Reduces ampacity for conductor bundling. 1.0 for ≤3 conductors, reduces for >3 due to heat buildup.
Total Factor Product of above 0.14 to 1.29 Combined effect of temperature and bundling. Corrected Ampacity = Base × Total Factor.
5.3 Notice

Ampacity Check: Verifies that Corrected Ampacity ≥ Required Ampacity. PASS means conductor can safely carry the load under installation conditions. FAIL means a larger conductor is needed.

Voltage Drop Check: Verifies that calculated voltage drop ≤ specified limit. Note that NEC voltage drop limits are informational recommendations, not mandatory requirements. However, excessive voltage drop can cause equipment malfunction and energy waste.

OCPD Coordination: Notes whether next-size-up rule was applied. Per NEC 240.4(B), if the conductor's corrected ampacity doesn't correspond to a standard OCPD rating, the next higher standard rating (not exceeding 800A) is permitted.

6. Worked Example: 100A Continuous Motor Load

This example demonstrates the complete NEC sizing workflow for a typical industrial motor feeder circuit.

6.1 Given Information
  • Application: Three-phase motor feeder
  • Load Current: 100 A (continuous operation)
  • System: 480V, three-phase
  • Power Factor: 0.90 (typical for motors)
  • Conductor Material: Copper
  • Insulation: THWN (75°C rated)
  • Installation: 3 current-carrying conductors in PVC conduit
  • Ambient Temperature: 40°C (104°F) - hot mechanical room
  • Circuit Length: 150 feet (one-way)
  • Voltage Drop Limit: 3% (NEC recommendation)
6.2 Step-by-Step Calculation

Step 1: Determine Required Ampacity

Motor load is continuous (runs >3 hours). Per NEC 210.19 and 215.2:

Required Ampacity = Load Current × 1.25
Required Ampacity = 100 A × 1.25 = 125 A

Step 2: Select Base Conductor Size

From Table 310.16, Copper, 75°C column, try 1 AWG:

Base Ampacity (1 AWG, Cu, 75°C) = 130 A

Step 3: Apply Temperature Correction

Ambient is 40°C. From Table 310.15(B)(1), 75°C column, 40°C ambient:

Temperature Correction Factor = 0.88

Step 4: Apply Adjustment Factor

Three current-carrying conductors. From Table 310.15(C)(1):

Adjustment Factor = 1.0 (no adjustment for ≤3 conductors)

Step 5: Calculate Corrected Ampacity

Corrected Ampacity = Base × Temp Factor × Adjust Factor
Corrected Ampacity = 130 A × 0.88 × 1.0 = 114.4 A

FAILS: 114.4 A < 125 A required. Need larger conductor.

Step 6: Try Next Size - 1/0 AWG

From Table 310.16, Copper, 75°C column:

Base Ampacity (1/0 AWG, Cu, 75°C) = 150 A
Corrected Ampacity = 150 A × 0.88 × 1.0 = 132 A

PASSES: 132 A ≥ 125 A required

Step 7: Select OCPD Rating

Required OCPD rating ≥ 125 A (for continuous load). From Table 240.6(A), standard sizes include: ..., 110A, 125A, 150A, ...

Selected OCPD = 125 A (matches requirement exactly)

Step 8: Size Equipment Grounding Conductor

From Table 250.122, for 125 A OCPD:

EGC Size (Copper) = 8 AWG

Step 9: Check Voltage Drop

From Chapter 9, Table 9, for 1/0 AWG copper in PVC conduit at 75°C:

  • Resistance (R) = 0.122 Ω per 1000 feet
  • Reactance (X) = 0.044 Ω per 1000 feet (PVC)

For three-phase circuit:

ΔV = √3 × I × (R cos φ + X sin φ) × L

Where:
I = 100 A (load current, not required ampacity)
cos φ = 0.90
sin φ = sin(arccos 0.90) = 0.436
L = 150 ft = 0.150 per 1000 ft

Impedance term:
Z_eff = R cos φ + X sin φ
Z_eff = 0.122 × 0.90 + 0.044 × 0.436
Z_eff = 0.1098 + 0.0192 = 0.129 Ω/1000 ft

Voltage drop:
ΔV = 1.732 × 100 × 0.129 × 0.150
ΔV = 3.35 volts

Percentage:
ΔV% = (3.35 / 480) × 100 = 0.70%

PASSES: 0.70% < 3% limit

6.3Worked Example - Result Summary
Component Size/Rating Notes
Phase Conductors 1/0 AWG Copper, THWN (75°C), 3 conductors in PVC conduit
Neutral Conductor 1/0 AWG Same as phase (motor load, balanced, low harmonics)
Equipment Ground 8 AWG Copper, per Table 250.122 for 125A OCPD
Overcurrent Device 125 A Circuit breaker or fuses rated 125A
Conduit TBD Size per NEC Chapter 9, Table 4 for (4) conductors
This solution provides proper conductor sizing with margin for voltage drop. The 1/0 AWG conductors have corrected ampacity of 132A (vs. 125A required), providing a 5.6% safety margin. Voltage drop of 0.70% is well within the 3% recommendation, leaving headroom for future load growth or longer circuit modifications.
7. NEC-Specific Rules and Requirements
7.1 Continuous Load Rule (NEC 210.19, 215.2)

NEC Article 100 defines a continuous load as one where the maximum current is expected to continue for three hours or more. Common continuous loads include:

  • HVAC systems (air conditioning, heating)
  • Commercial lighting systems
  • Continuously operating motors and pumps
  • Process equipment in industrial facilities
  • Data center and telecommunications equipment

Per NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders, conductors must be sized so that the ampacity (after applying correction factors) is not less than:

Minimum Ampacity = Noncontinuous Load + (1.25 × Continuous Load)

Alternatively, the overcurrent protective device (OCPD) can be rated at not less than 125% of the continuous load plus 100% of the noncontinuous load, with conductors sized to match or exceed the OCPD rating. Both approaches yield equivalent results.

7.2 Next-Size-Up OCPD Rule (NEC 240.4(B))

NEC 240.4(B) allows the use of the next higher standard overcurrent device rating (above the conductor ampacity) if the conductor ampacity does not correspond to a standard OCPD rating from Table 240.6(A). This rule is subject to limitations:

  • Applies only if the next size up does not exceed 800 amperes
  • Does not apply to 120V 15A and 20A branch circuits (must use exact sizes)
  • Conductor ampacity (after corrections) must still be adequate for the load

Example: A conductor with corrected ampacity of 118A can be protected by a 125A OCPD (next standard size up), but a conductor with corrected ampacity of 118A cannot be protected by a 150A OCPD.

7.3 Adjustment Factors (NEC 310.15(C)(1))

When more than three current-carrying conductors are in a raceway or cable, the ampacity of each conductor must be reduced per Table 310.15(C)(1). The adjustment accounts for reduced heat dissipation when multiple conductors are bundled:

Number of Current-Carrying Conductors Adjustment Factor (%)
1-3100% (no adjustment)
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41 or more35%

Exception: The neutral conductor of a 3-wire, single-phase circuit or 4-wire, three-phase wye circuit is not considered current-carrying UNLESS there is more than 50% third harmonic content. This exception is critical for nonlinear loads.

7.4 Neutral Conductor Sizing for Harmonic Loads (NEC 310.15(C)(1) Exception)

In circuits supplying nonlinear loads (electronic equipment, LED drivers, switching power supplies), third harmonic currents do not cancel in the neutral conductor. When third harmonic content exceeds 50%, the neutral must be counted as a current-carrying conductor and sized accordingly:

  • If neutral current is expected to equal or exceed phase current, neutral must be same size as phase
  • Neutral is included in conductor count for adjustment factor purposes
  • In extreme cases, neutral may need to be larger than phase conductors

Common sources of high harmonic content: data centers, office buildings with LED lighting, facilities with many switching power supplies, variable frequency drives (VFDs).

7.5 Termination Temperature Limitations (NEC 110.14(C))

While conductors may be rated for 90°C operation, terminals on equipment are often rated for lower temperatures. NEC 110.14(C) requires consideration of termination temperature ratings:

  • For circuits rated 100A or less, or conductors 14 AWG through 1 AWG: Use the 60°C ampacity column unless the equipment is listed for 75°C
  • For circuits rated over 100A, or conductors 1/0 AWG and larger: Use the 75°C ampacity column unless the equipment is listed for higher temperatures

Practical Application: Even with 90°C rated THHN/THWN-2 conductors, you may need to use the 75°C ampacity for sizing. However, the 90°C rating is valuable for applying correction factors - you can use the 90°C column ampacity with corrections, then verify the resulting ampacity meets the 75°C termination requirement.

7.6 Equipment Grounding Conductor (NEC 250.122)

The equipment grounding conductor (EGC) provides a low-impedance path for fault currents, enabling rapid operation of overcurrent devices. Key requirements:

  • Size based on rating of overcurrent device ahead of equipment (Table 250.122)
  • If phase conductors are increased in size for voltage drop, EGC must be increased proportionally
  • Minimum size: 14 AWG copper for circuits ≤15A, 12 AWG copper for circuits ≤20A
  • EGC may be solid or stranded conductor, or in the form of raceway, armor, or shield
7.7 Voltage Drop - Informational Recommendations (NEC 210.19(A) Note 4)

NEC 210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2 recommend voltage drop limits but do not mandate them:

  • Branch Circuits: 3% maximum recommended
  • Feeders: 3% maximum recommended
  • Combined (feeder + branch circuit): 5% maximum recommended

While not code requirements, these limits represent good engineering practice. Excessive voltage drop can cause:

  • Motor overheating and reduced life
  • Lamp dimming and reduced light output
  • Electronic equipment malfunction
  • Increased energy consumption
  • Inability to start large motors
8. Limitations and Good Practice
8.1 Code Edition and Jurisdiction

This calculator implements NEC 2023 (NFPA 70-2023) requirements. Always verify:

  • Which NEC edition has been adopted in your jurisdiction
  • Any state or local amendments to the NEC
  • Special requirements for your specific industry or application
  • More restrictive requirements from other applicable codes (building codes, fire codes)
8.2 Representative Values

The calculator uses standard values from NEC tables, which represent typical installation conditions. Actual conductor ampacities and properties may vary based on:

  • Specific manufacturer and construction
  • Cable configuration (flat vs. triplexed vs. separated)
  • Installation method details
  • Thermal characteristics of surrounding materials

For critical applications, verify conductor properties with manufacturer data sheets.

8.3 Special Conditions Not Explicitly Covered
  • Parallel Conductors: NEC 310.10(G) requirements for paralleling not automated
  • Very Large Conductors: Sizes larger than 2000 kcmil require custom analysis
  • Medium Voltage: Systems above 2000V use different tables (310.60 series)
  • Special Cables: Mineral-insulated (MI), aerial, or submarine cables have different ratings
  • Specific Installation Methods: Duct banks, direct burial in concrete, etc., may require detailed analysis
  • High Altitude: May affect equipment but not conductor sizing per NEC
8.4 Professional Engineering Practice

This calculator is intended for preliminary sizing and educational purposes. For final designs:

  • Engage a licensed practitioner for plans requiring professional seal
  • Perform detailed short-circuit and coordination studies
  • Consider future load growth and system flexibility
  • Verify all assumptions with field conditions
  • Document all calculations and bases of design
  • Consider using safety margins (10-25%) beyond minimum code requirements
  • Evaluate alternative solutions and life-cycle costs
  • Verify calculator results against manual calculations for critical circuits
  • Compare results from multiple sizing methods
  • Have calculations reviewed by a second qualified person
  • Maintain documentation of all design decisions and assumptions
  • Update designs if field conditions differ from assumptions
9. References
9.1 Primary Code References
  1. NFPA 70-2023, National Electrical Code (NEC)
    • Article 100: Definitions
    • Article 210: Branch Circuits
    • Article 215: Feeders
    • Article 240: Overcurrent Protection
    • Article 250: Grounding and Bonding
    • Article 310: Conductors for General Wiring
    • Chapter 9: Tables and Annexes
    National Fire Protection Association (NFPA), Quincy, MA
  2. NFPA 70E-2021, Standard for Electrical Safety in the Workplace
    National Fire Protection Association (NFPA), Quincy, MA
9.2 Manufacturer References

For conductor-specific data and installation guidance, consult manufacturer technical literature:

  • Southwire Company LLC - Wire and Cable Technical Reference
  • General Cable - Product Engineering Handbooks
  • Encore Wire Corporation - Technical Data Sheets
  • Prysmian Group - Engineering Resources
  • Nexans - Technical Documentation
This calculator provides guidance based on NEC 2023 requirements. It is intended for preliminary engineering calculations and educational purposes. Users are responsible for verifying applicability to their specific project, confirming compliance with locally adopted codes and amendments, and engaging appropriate licensed professionals for final design and approval. The developers assume no liability for designs based on calculator output.