kVA Tools logokVATools.io ❯ CT Cabinet


CT Cabinet

Technical Documentation and Calculation Methodology

1. Introduction

The CT Cabinet selects and verifies current transformers for metering and protection applications. Given the load current, fault duty, connected burden, and lead run, it recommends a standard ratio, verifies the connected burden against standard burden ratings, checks saturation performance including the DC-offset transient factor, and produces the specification string (ratio, class, burden, rating factor) to hand to a manufacturer. Calculations follow IEEE C57.13-2016, the application guidance of IEEE C37.110, and IEC 61869-2:2012.

The tool covers conventional iron-core CTs with 5 A or 1 A secondaries, including window, bar, bushing, split-core, and wound-primary constructions, plus a qualitative path for Rogowski coils. For IEC class P and PR cores it accepts the relay manufacturer's transient dimensioning factor Ktd, but it does not perform duty-cycle dimensioning of class TPX/TPY/TPZ cores; where that is needed it lists the parameters to give the manufacturer. It does not verify a specific manufacturer's excitation curve, and it does not size voltage transformers.

2. Current Transformer Fundamentals

A current transformer reproduces its primary current at a reduced magnitude, scaled by the turns ratio. The reproduction is imperfect because a portion of the primary ampere-turns must magnetize the core. This exciting current is the entire error budget of the CT: at low flux it is small and the CT is accurate; as the required secondary voltage rises, the core approaches saturation, the exciting current grows rapidly, and the secondary current collapses relative to ratio.

The secondary voltage the core must develop is set by Ohm's law around the secondary loop:

Vs = Is × (Rct + Rleads + Zburden)

Every term the user controls appears here: a higher ratio reduces Is; shorter or larger leads reduce Rleads; modern low-burden relays reduce Zburden. CT selection is the exercise of keeping Vs, under the worst credible fault, below the voltage the core can deliver.

3. Definitions

Rated Current Ratio (CTR)

The ratio of rated primary to rated secondary current, for example 600:5 (CTR = 120). Standard primary values are listed in C57.13 Table 9 for ANSI and in 61869-2 §5.201 for IEC (10, 12.5, 15, 20, 25, 30, 40, 50, 60, 75 A and decimal multiples). Standard secondaries are 5 A and 1 A.

Burden

The impedance connected across the secondary, expressed in ohms or in volt-amperes at rated current (VA = Isr² × Z). ANSI standard metering burdens are B-0.1 through B-1.8 at 0.9 power factor plus the electronic burdens E0.04 and E0.2 at unity power factor (Table 10); relaying burdens are B-0.1 through B-8.0 (Table 13). IEC standard rated outputs are 2.5, 5, 10, 15, and 30 VA (§5.5.201).

Relay Accuracy Class (ANSI)

A C-class CT delivers its class voltage (C100 = 100 V) at the secondary terminals at 20 times rated current into the corresponding standard burden without exceeding 10% ratio error (C57.13 §6.4.1.3). The C-number is a terminal voltage and is defined on a 5 A basis; for other secondaries the equivalent burden is V / (Isr × 20) per Table 13 note a. T-class CTs have significant leakage flux and require the manufacturer's overcurrent ratio curves. X-class CTs are user-specified by knee point, exciting current, and winding resistance (§6.4.1.4).

Accuracy Limit Factor (ALF, IEC)

The multiple of rated primary current up to which a protection CT holds its composite error limit at rated burden. Class 5P20 means 5% composite error at 20 times rated current. Standard ALF values are 5, 10, 15, 20, and 30 (§5.6.202.2.1). The effective ALF at a connected burden differing from rated scales as (Rct + Rb,rated) / (Rct + Rb,connected).

Knee Point

The onset of saturation on the excitation curve. ANSI defines it graphically as the point where the tangent to the log-log excitation curve is at 45°, for nongapped cores (C57.13 §6.10.2). IEC defines the knee point e.m.f. as the voltage which, when increased by 10%, causes the exciting current to increase by 50% (61869-2 §3.4.216). For class PX and PXR the rated knee point e.m.f. may be computed as Ek = Kx × (Rct + Rb) × Isr.

Continuous Thermal Current Rating Factor (RF)

The ANSI multiplier on rated primary current the CT can carry continuously at 30 °C average ambient while holding its accuracy class. Preferred values are 1.0, 1.33, 1.5, 2.0, 3.0, and 4.0 (C57.13 §6.5). IEC has no RF; instead a rated continuous thermal current may be specified at 120%, 150%, or 200% of rated primary (61869-2 §5.203), with accuracy retained up to the extended current for the ext-marked classes.

Instrument Security Factor (FS, IEC)

The multiple of rated current at which a metering core deliberately saturates to protect connected instruments during faults. Standard values are FS 5 and FS 10 (§5.6.201.6). A lower FS is safer for the meter. ANSI has no equivalent parameter.

Short-Time Ratings (Ith, Idyn)

Ith is the 1-second symmetrical thermal withstand with the secondary shorted. The dynamic (mechanical) rating is the first asymmetrical peak the CT withstands: 2.7 × Ith under ANSI (C57.13 §6.6.1) and 2.5 × Ith under IEC (61869-2 §5.204.2). For durations up to 5 s, Ith(t) = Ith(1 s) / √t.

Secondary Winding Resistance (Rct)

The DC resistance of the secondary winding corrected to 75 °C, as used in all saturation and knee-point arithmetic in both standards.

4. Ratio Selection Methodology

4.1 Metering Rule

Metering accuracy classes are verified down to 10% of rated current for ANSI 0.3, 0.6 and 1.2; 5% for 0.15, 0.15S and 0.3S (C57.13 Table 8); 5% for IEC 0.1–1, 1% for IEC 0.2S and 0.5S, and 50% for IEC classes 3 and 5 (61869-2 Tables 201–203). Below that point the candidate Fails. Above it, the tool treats the load as Pass from 50% to 100% of rated primary current, a design-practice band because errors grow toward the bottom of the range. For classes whose limits are constant over a wide range the band is the standard's own: 5–100% for ANSI 0.15S and 0.3S (Figure 4), 20–120% for IEC 0.2S and 0.5S (Table 202), 50–120% for IEC 3 and 5. Between the verification point and the band the candidate is Marginal.

4.2 Protection Rule

The C-class error limit is rated at 20 times rated current (C57.13 Table 12, §6.4.1.3), and ALF 20 is a common IEC choice. 20× is a rating point, not a saturation limit: a CT with a light burden can reproduce higher multiples. The tool therefore prefers:

Ifault / Ipr ≤ 20

Candidates between 16 and 20 times are flagged Marginal for thin margin; candidates above 20 times are Marginal and ranked below every candidate at or under 20×, and the saturation check (Section 6) decides whether they work. Among passing candidates the ranking prefers the smallest ratio, because relay sensitivity to minimum faults degrades as the ratio grows.

4.3 Continuous Capability

Every candidate must also satisfy Ipr × RFeff × Falt ≥ Iload, where RFeff is the ambient-corrected rating factor (Section 9) and Falt the altitude factor.

4.4 Dual Applications

When one location must serve revenue metering and protection, the constraints conflict: metering wants the smallest ratio that covers the load, protection wants headroom to 20 times fault. The tool sizes a ratio satisfying both, then advises a two-core CT so each core carries its proper class. Sharing one core between an energy meter and a relay is poor practice and defeats the FS protection concept.

5. Burden Analysis

5.1 Lead Loop Resistance

Lead resistance is computed from published Ω/km conductor data corrected to the operating temperature:

Rlead,1-way = R20 × L × [1 + α × (T − 20)]

with α = 0.00393/°C for copper and 0.00403/°C for aluminium (aluminium base resistance 1.64 × copper for equal size). The loop multiplier depends on the fault type used for verification, per IEEE C37.110: a phase-to-ground fault returns through the neutral lead, so the CT sees two times the one-way run; a balanced three-phase fault sums to zero in the neutral and the CT sees one times the run. The phase-to-ground basis is the conservative default and the single largest lever on marginal installations.

5.2 Device Burdens and Unit Conversion

Devices entered in VA are converted to ohms at rated secondary current, Z = VA / Isr². Typical prefill values are 0.02 Ω for a microprocessor relay, 0.10 Ω solid-state, and 1.0 Ω electromechanical; the actual device datasheet value should be entered when known. Test switches and terminal blocks default to 0.05 Ω, which is small but decides borderline cases.

5.3 Standard Burden Matching

The total connected burden is matched upward to the next standard burden: ANSI Table 13 designations for protection or Table 10 (including the E-burdens) for metering, and the next standard rated output in VA for IEC. Two standard-specific cautions apply. First, an ANSI CT that meets class at a 0.9 power-factor B burden is not guaranteed to meet it at a unity power-factor electronic burden (C57.13 §6.3). Second, IEC accuracy is guaranteed only between 25% and 100% of rated output (50% to 100% for classes 3 and 5), so a 15 VA CT feeding a 0.5 VA electronic meter is outside its guaranteed band; the tool warns and suggests a lower VA rating or the extended burden range (1 VA to rated output at unity power factor, available only for rated outputs up to 15 VA, §5.6.201.4).

5.4 5 A versus 1 A Secondary

Lead burden in VA scales with the square of secondary current, so a 1 A secondary cuts the lead contribution by a factor of 25 for the same conductor. The tool tabulates both. Under IEC selection it auto-recommends 1 A when the lead loop dominates the 5 A burden or the 5 A total exceeds 30 VA; under ANSI it retains 5 A (the near-universal North American practice) and raises the 1 A option in the comparison note when leads dominate. At secondaries other than 5 A the ANSI burden tables are read as the standard directs: metering burdens keep the same impedance and designation, with VA = Z × Isr² (Table 10 note a, e.g. B-0.5 = 0.5 Ω = 0.5 VA at 1 A); relaying burdens become terminal V / (Isr × 20) (Table 13 note a, e.g. C100 at 1 A = 100 V / 20 A = 5 Ω, five times the 5 A value).

6. Saturation Verification

6.1 Required Secondary Voltage

The symmetrical requirement follows Section 2 with Is = Ifault / CTR. Real faults carry a decaying DC offset that drives core flux far beyond the symmetrical value. Each standard is checked on its own basis, with requirement and capability always compared like for like.

6.2 ANSI Class Selection

The C rating is the secondary terminal voltage the CT delivers to a standard burden at 20 times rated current (C57.13 §6.4.1.3); it excludes the drop across the CT's own winding. The requirement is therefore formed on the external burden only, with the (1 + X/R) offset factor of IEEE C37.110:

Vterminal = Is × (Rleads + Zburden) × (1 + X/R)

The resistive sum is used deliberately: reactive burden components do not contribute to DC-offset flux buildup, and treating the connected burden as resistive is conservative for modern low-burden devices. The required class is the smallest standard C voltage (10, 20, 50, 100, 200, 400, 800) at or above Vterminal. The saturation margin is reported as (Vclass − Vterminal) / Vterminal; margins below 25% are flagged Marginal. A requirement above C800 means the duty cannot be met by class selection alone: reduce burden, raise the ratio, or accept transient saturation with a relay proven stable for it. At 1 A the C-class voltage is unchanged; only the equivalent burden changes (Section 5.4).

6.3 IEC ALF Selection

IEC class P and PR are defined for symmetrical steady-state fault current (61869-2 Table 204), and the ALF is an e.m.f. criterion that includes Rct. The required rated ALF at the matched rated output, with the burden correction, is:

ALFreq = (Ifault / Ipr) × Ktd × (Rct + Rconnected) / (Rct + Rb,rated)

Ktd is the transient dimensioning factor. It defaults to 1 (symmetrical sizing, as the standard defines class P); enter the relay manufacturer's published value to cover the part of the DC offset the relay needs to see before it operates. A fully offset fault would need Ktd ≈ 1 + X/R. The next standard ALF (5, 10, 15, 20, 30) is reported as a 5P class at the matched VA, or in the family of the chosen target (10P, 5PR, 10PR) with a check that the target ALF is enough. Where the requirement exceeds ALF 30, the remedies are a higher ratio or a transient-performance core: the tool lists Kssc = Ifault / Ipr and Tp = (X/R) / 2πf for a class TPX or TPY specification (61869-2 §5.6.202.5), to which the rated resistive burden and duty cycle are added.

7. High-Impedance Differential and Class X / PX

High-impedance differential and restricted earth fault schemes are stabilized by the knee-point voltage rather than a C-class or ALF. Selecting these schemes routes the tool to the knee-point requirement used in Class X (C57.13 §6.4.1.4) and PX/PXR (61869-2 §5.6.202.4) practice:

Vk ≥ 2 × Is,through × (Rct + Rleads)

where Is,through is the maximum external through-fault secondary current. The factor 2 is the customary relay-manufacturer stability margin, not a requirement of either standard; the standards define how the result is specified — Class X by Ek, Ik and Rct (C57.13 §6.4.1.4), class PX by Ek = Kx × (Rct + Rb) × Isr (61869-2 §5.6.202.4). All CTs in the scheme must share the same ratio, use the full winding, and the stabilizing resistor is set from the relay voltage setting during commissioning. PX limits turns ratio error to ±0.25%; PXR relaxes this to ±1% but caps the remanence factor at 10%.

8. Metering Performance

8.1 Accuracy Classes and Verification Points

Standard Classes Verification Points
ANSI (C57.13 Table 8) 0.15, 0.15S, 0.15N, 0.3S, 0.3, 0.6, 1.2 100% and 10% of rated (5% for 0.15 and S-classes); limits also apply at RF × rated current
IEC (61869-2 Tables 201–203) 0.1, 0.2, 0.2S, 0.5, 0.5S, 1, 3, 5 5/20/100/120% of rated (plus 1% for S-classes); classes 3 and 5 at 50/120% with no phase limit

The tool verifies the load position against these bands and assembles the ordering specification: for ANSI a class-at-burden string such as 0.3 @ B-0.5, and for IEC the rating-plate form of §6.13.202, for example 5 VA cl. 0.2S ext. 150% FS 5.

8.2 Instrument Security (IEC)

FS is defined at rated burden. At a lower connected burden the core saturates later and the meter sees more current (61869-2 §3.4.205 Note 1). From the secondary limiting e.m.f. EFS = FS × Isr × (Rct + Rb) (§3.4.206) the tool estimates:

FSeff = FS × (Rct + Rb,rated) / (Rct + Rb,connected)

When the fault multiple exceeds FSeff the meter sees no more than about FSeff × Isr; if FSeff is more than twice the nameplate FS the check is Marginal, because the meter's withstand must then be confirmed. If the fault multiple is below FSeff, the meter carries the full fault secondary current. Where no FS is specified and fault multiples are high, the tool recommends FS 5.

9. Thermal and Environmental Ratings

9.1 Ambient Correction of RF (ANSI)

C57.13 rates RF at 30 °C average ambient with 55 °C rise. Because winding rise is proportional to current squared, the Figure 1 loading curves reduce to:

RFeff = RF × √[(85 − θa) / 55]

for θa above 30 °C. At 55 °C ambient an RF 2.0 CT delivers approximately 150% of rated current, matching the worked example in C57.13 §4.4.2. Bushing CTs inside transformer tanks are a special case rated against 90 °C oil per Annex B and should be specified with the equipment manufacturer.

9.2 Altitude

Above 1000 m the continuous current capability is reduced by 0.3% for each 100 m of additional altitude (C57.13 §4.4.1), and the dielectric strength of external insulation falls by the Table 1 factor (0.80 at 3000 m, interpolated between rows; §4.2). The tool reports the sea-level BIL equivalent to specify, BIL / factor.

9.3 Short-Time and Insulation Ratings

The tool reports the minimum 1 s Ith to specify. For a fault duration t up to 5 s that is Ifault × √t, the inverse of the C57.13 §6.6.2 rule that a t-second rating is the 1 s rating divided by √t (a 3 s rating is 58% of the 1 s rating). It also reports the mechanical (ANSI, 2.7 × Ifault peak, §6.6.1) or dynamic (IEC, 2.5 ×, §5.204.2) rating, and the insulation class and BIL from C57.13 Table 2. Window, bushing and split-core CTs have no primary insulation of their own and no BIL requirement (Table 2 note e); the tool says so instead of quoting a BIL. Under IEC selection the Table 2 value is labelled as an ANSI reference; specify Um and the lightning impulse level per IEC 61869-1.

10. Multi-Ratio CTs

When the recommended ratio is an exact tap of a standard ANSI multi-ratio CT (600, 1200, 2000, 3000, 4000, or 5000:5 parents per C57.13 Table 11), the tool displays the parent's full tap table with the recommended tap highlighted, including the X-terminal pairs to strap. Two caveats are printed with the table: accuracy classes apply to the full winding only unless the nameplate states per-tap ratings (§6.3.1, §6.4.2). For relaying the tool also derates the class to the tap: the C rating belongs to the full winding and a tap delivers only its share of the turns, so the full winding must be rated at least Creq × (parent / tap). For example, 452 V required on the 400 tap of a 600:5 MR needs the full winding rated C800. IEC selectable-ratio arrangements are manufacturer specific (§5.6.203) and no standardized tap table applies.

11. Alternatives and Workarounds

11.1 Multi-Turn Primary

Passing the primary conductor N times through a window CT divides the effective ratio by N. It is worth considering when the recommended CT is under-ranged (load below 50% of rated), choosing a turn count that keeps the load at or below 100%. Manufacturers generally do not warrant metering accuracy with multi-turn primaries, window fill and the conductor's own ampacity govern feasibility. The continuous, thermal and mechanical limits belong to the secondary winding (C57.13 §6.6.3), so with N primary turns the primary-referred Ith, mechanical rating and RF capability all divide by N and must be rechecked.

11.2 Summation (Paralleled) CTs

Paralleling secondaries totalizes two separate circuits into one device; it does not multiply ratio. Two equal CTs on the same conductor with paralleled secondaries deliver the sum of their outputs, an effective ratio of CTR/2, and each CT sees the other's excitation branch as added burden. Specifying a paralleled pair to obtain a higher ratio is a common and consequential error.

11.3 Auxiliary CTs

An auxiliary CT can match a non-standard ratio to the connected device, but its burden reflects to the main CT by the auxiliary ratio squared; the burden analysis must be repeated with the reflected value.

11.4 Rogowski Coils

An air-cored Rogowski coil has no saturation limit and no meaningful burden constraint, which removes the entire Section 6 problem for very high currents, retrofit windows, or unbeatable transient duties. Its output is a low-level voltage proportional to di/dt, so the connected relay must accept Rogowski input directly or through an integrator per IEEE C37.235; conventional 1 A / 5 A inputs will not work. Selecting Rogowski construction in the tool bypasses the ratio, burden, and saturation blocks and prints this guidance.

12. Rct Estimation

When no test-report value is entered, the tool estimates the secondary winding resistance at 75 °C from the turns count:

Rct ≈ Ns × 2.5 mΩ (5 A) or Ns × 7.5 mΩ (1 A)

where Ns = Ipr / Isr. These per-turn values are typical of distribution-class cores; actual values vary with core diameter and wire gauge. Results computed from the estimate are labelled, and the nameplate or test value should replace it for any final specification, particularly on the knee-point path where Rct is a first-order term.

13. Worked Example

13.1 Feeder Protection CT (tool defaults)

A 480 V feeder carries 450 A maximum continuous load with 10 kA symmetrical fault duty at X/R = 10. The microprocessor relay presents 0.02 Ω, test blocks 0.05 Ω, and the leads are 30 m of copper AWG 10 at 75 °C, verified on the phase-to-ground basis.

Ratio. 600:5 places the fault at 16.7 × In, inside the limit but with thin margin; 750:5 gives 13.3 × In and 60% load position, and is recommended.

Leads. AWG 10 copper is 3.277 Ω/km at 20 °C. One way:

R = 3.277 × 0.030 × [1 + 0.00393 × (75 − 20)] = 0.120 Ω

Two-way loop: 0.239 Ω. Total connected burden with devices: 0.309 Ω = 7.7 VA at 5 A, matched to standard burden B-0.5.

Saturation. Is = 10 000 / 150 = 66.7 A. The C rating is a terminal voltage, so Rct is not added:

Vterminal = 66.7 × 0.309 = 20.6 V
Vterminal × (1 + 10) = 227 V → specify C400 (margin 76%)

Ratings. Specify Ith ≥ 10 kA (1 s, for a fault duration of 1 s or less); mechanical rating 27 kA peak (2.7 ×). A window CT has no primary insulation and no BIL requirement of its own. The resulting specification is a 750:5, C400, RF 1.0 CT. The X/R transient factor is what lifts it above C100; halving the lead run or the X/R materially reduces the requirement.

13.2 Reference Cases from IEEE C57.13

C57.13-2016 is a requirements standard and contains no complete CT sizing example. It does give the small numerical examples below, and each is provided as a project file that reproduces it.

Project fileClauseTool reproduces
C5713_Table13_NoteA_C100_1ATable 13 note aC100 at 1 A = 100 V / (1 A × 20) = 5 Ω: 500:1, 5 Ω burden, 10 A × 5 Ω × (1 + 1) = 100 V → C100
C5713_Table10_NoteA_B05_1ATable 10 note aB-0.5 keeps 0.5 Ω at 1 A (0.5 VA): 0.45 Ω connected → 0.3 @ B-0.5
C5713_442_RF2_at_55C§4.4.2RF 2.0 at 55 °C ≈ 150%: effective RF 1.48; 1000:5 carries 1450 A
C5713_662_3s_Thermal_Rating§6.6.23 s rating = 58% of 1 s: 20 kA for 3 s → specify Ith (1 s) ≥ 34.6 kA
C5713_441_Table1_Altitude_3000m§4.4.1, Table 13000 m: current ×0.94 (600:5 carries 564 A); dielectric ×0.80 (200 kV BIL → 250 kV sea-level equivalent)

14. Installation and Safety

The tool sizes the CT; these points govern how it is installed and commissioned.

  • Never open an energized CT secondary. Open-circuit voltages can exceed several kV peak and are lethal. Short the secondary before any work. C57.13 §6.7.1 requires a CT to survive an open secondary for only 1 minute, and only where the open-circuit voltage stays below 3500 V peak; above that, fit a voltage-limiting device (varistor or spark gap) across the secondary terminals.
  • Ground the secondary circuit at one point only, normally at the first point of application (NEC 250.170 through 250.178; IEEE C57.13.3).
  • Short and ground unused CT secondaries and unused multi-ratio taps, without creating a second ground on the circuit (NEC 110.23).
  • Verify polarity (H1/X1) before energizing; differential and directional schemes depend on it. Wire through a shorting-type test switch.
  • Multi-ratio CT accuracy classes apply to the full winding only, unless the nameplate states otherwise (C57.13 §6.3.1, §6.4.2).
  • Demagnetize after any DC resistance test or primary injection with DC content (C57.13 §9.2).
  • Label the CT ratio, connected tap, class and burden at the terminal block.

15. Limitations and Assumptions

The saturation check treats the connected burden as resistive. On the ANSI path it applies the full (1 + X/R) offset factor of C37.110, which is conservative; on the IEC path DC offset enters only through the Ktd entered. The tool does not model remanence, time-to-saturation, or reclosing duty cycles, for which IEC TP-class dimensioning applies. that the load position and burden fall inside the band where the specified class is guaranteed; they do not predict the actual RCF or phase angle of a particular CT, which requires the manufacturer's curves. The Rct estimate is typical, not guaranteed. Lead resistance assumes a single conductor pair; wye-connected CT sets sharing a common neutral, and delta-connected CTs, need scheme-specific lead treatment per IEEE C37.110. Standard ratings tables reflect C57.13-2016 and 61869-2:2012 as published.

16. References

  1. IEEE Std C57.13-2016, IEEE Standard Requirements for Instrument Transformers
  2. IEC 61869-2:2012, Instrument Transformers — Part 2: Additional Requirements for Current Transformers
  3. IEEE Std C37.110-2007, IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes
  4. IEEE Std C37.235-2007, IEEE Guide for the Application of Rogowski Coils Used for Protective Relaying Purposes
  5. IEEE Std C57.13.3-2014, IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases
  6. NFPA 70-2026, National Electrical Code (NEC), Articles 110.23 and 250.170–250.178