kVA Tools logokVATools.io ❯ Coordination Dial


Coordination Dial

Technical Documentation and Calculation Methodology

1. Introduction

The Coordination Dial plots time-current curves (TCCs) for a series string of low-voltage protective devices, measures the vertical time separation between adjacent devices at the available fault current, and flags miscoordination, thin margins, and unprotected cable. It supports four device families — thermal-magnetic moulded-case circuit breakers (MCCBs), electronic trip units (LSIG), miniature circuit breakers (MCBs) to IEC 60898, and fuses — plus an optional conductor damage overlay.

The methodology follows the graphical coordination approach described in IEEE Std 242 (the Buff Book): overlay each device's operating characteristic on log-log axes of current versus time, and require that, for any current a downstream device could see, the downstream device operates faster than the device upstream of it by a defined margin. Where curves overlap or cross, coordination is lost and a downstream fault may trip an upstream device, widening the outage.

The device curves in this tool are generic parametric models, not manufacturer catalogue data. They are constructed from published standard shapes and trip-unit setpoints and are intended for planning, teaching, and first-pass screening. They cannot reproduce a specific breaker's tested let-through energy or a manufacturer's published selectivity (discrimination) table, particularly in the instantaneous region. Confirm every final coordination decision against manufacturer curves and selectivity tables.

2. Scope and Standards

2.1 What the tool does

The Coordination Dial draws each device's nominal operating curve (or tolerance band, where the standard defines one), marks the available fault current as a vertical reference line, computes the time separation between each adjacent pair of devices, and classifies the pair as coordinated, marginal, or miscoordinated. It also compares each device's clearing time against a conductor thermal-withstand curve to check that cable is protected.

2.2 What the tool does not do

It does not model arcing-fault current, dynamic impedance, motor contribution decay, or the current- limiting let-through of fuses and current-limiting breakers. It does not certify selectivity: two devices whose published curves appear separated may still fail to discriminate at high fault currents where instantaneous elements and dynamic let-through dominate. Series-rated combinations and zone-selective interlocking (ZSI) are outside its scope.

Relevant standards: IEEE Std 242 (Buff Book) coordination method; IEC 60898-1 (MCB instantaneous classes); IEC 60947-2 (LV circuit-breakers); UL 248 (LV fuses); NEC (NFPA 70) 240.87, 240.12, and 700.32 / 701.32 for selective coordination of emergency and legally required standby systems.

3. Definitions and Concepts

Time-Current Curve (TCC)

A plot of a protective device's operating time against the current passing through it, drawn on log-log axes. Higher current produces faster operation, so curves slope down to the right. Both axes are logarithmic because protective devices operate across several decades of current (overload to short-circuit) and time (milliseconds to hours).

Coordination and Selectivity

Two devices are coordinated when, for any fault the downstream device can see, it clears the fault before the upstream device begins to operate. Selectivity (or discrimination) is the same idea stated as an outcome: only the device nearest the fault opens, leaving the rest of the system energised.

Coordination Margin

The vertical time separation between two adjacent device curves at a given current. A positive margin means the upstream device is slower; a margin at or below the chosen threshold indicates the two devices operate too close together to guarantee selectivity once tolerances are considered. The margin is a band separation, not a fixed universal figure — the frequently quoted 0.3 s is a conservative default for electromechanical relays, not a law.

Minimum-Melt and Total-Clearing Time (fuses)

A fuse is described by two curves: the minimum-melting time (the shortest time at which the element begins to melt at a given current) and the total-clearing time (the longest time to fully interrupt, including arcing). The region between them is the fuse's operating band.

Pickup and Per-Unit Multiple

Pickup is the current at which a protective element starts to time out. Trip-unit settings are expressed as multiples of a base current — of the sensor rating In, or of the long-time setting Ir — so a setting travels correctly when the base rating changes.

4. Device Curve Models

Input convention: continuous trip-unit settings are entered as per-unit multiples (×In or ×Ir) with a live amperes helper, while physical ratings (breaker frames, MCB sizes, fuse ampere ratings) are chosen from discrete standard-size lists. Settings are continuous; hardware ratings are discrete.

4.1 Thermal-Magnetic MCCB

A thermal-magnetic breaker has an inverse thermal region (bimetal) and a fixed or adjustable magnetic instantaneous trip. The thermal region is modelled as a representative inverse characteristic and the instantaneous as a vertical drop at the pickup current:

t(I) = 350 / [ (I / In)² − 1 ]   (thermal)
I ≥ mi · In ⇒ t ≈ 0.02 s   (instantaneous)

where mi is the instantaneous pickup multiple. The constant 350 anchors the thermal curve to roughly 10 s at six times rating; it is representative, not a specific frame rating.

4.2 Electronic Trip Unit (LSIG)

An electronic trip unit is built from independent setpoints: Long-time (L), Short-time (S), Instantaneous (I), and Ground-fault (G). The long-time pickup sets the reference current Ir = mLT · In. The long-time band is an I²t characteristic anchored so that its delay is defined at six times Ir:

Ir = mLT · In
Long-time: t(I) = 36 · tLT / (I / Ir)²

The short-time element picks up at mST · Ir and is either a flat definite-time delay or an I²t ramp:

Ip,ST = mST · Ir
Short-time (flat): t = tST
Short-time (I²t in): t(I) = tST · (Ip,ST / I)²

The instantaneous element, when enabled, drops the curve to the floor above mI · In. The composite operating time at any current is the fastest active band:

t(I) = min( tLT(I), tST(I), tINST(I) )

The ground-fault element, if present, is drawn as an independent definite-time line at its own pickup and delay; it is not part of the phase-overcurrent composite.

4.3 Miniature Circuit Breaker (IEC 60898)

An MCB is defined by its instantaneous class. IEC 60898-1 fixes the magnetic trip band as a multiple of rated current, drawn here as a shaded vertical band; the thermal region is a representative inverse curve anchored to the standard's conventional tripping time (1.45 × In within one hour for In ≤ 63 A):

Thermal: t(I) = K / [ (I / In)² − 1 ],   K = 3600 · (1.45² − 1) ≈ 3969
Class Instantaneous band Typical application
B 3–5 × In Resistive loads, long cable runs
C 5–10 × In General mixed loads, small motors
D 10–20 × In High-inrush loads, transformers

4.4 Fuses — Classes RK-1, J, L

Fuse curves are reconstructed by log-log interpolation between anchor points of the minimum-melt and total-clearing tables for each class. The operating time is interpolated linearly in log-log space between the bracketing anchors:

log₁₀ t = log₁₀ t₀ + f · ( log₁₀ t₁ − log₁₀ t₀ ),
f = ( log₁₀ m − log₁₀ m₀ ) / ( log₁₀ m₁ − log₁₀ m₀ )

where m is the current expressed as a multiple of the fuse ampere rating. Representative total-clearing anchors for a Class RK-1 dual-element time-delay fuse are shown below; the shape honours the UL 248 requirement that time-delay fuses hold five times rating for at least ten seconds.

Multiple of rating 2× 3× 5× 10× 20×
Total-clear (s) 520 95 18 1.0 0.05

Classes RK-1, J, and L are modelled in the current version; other NEC classes (RK-5, T, CC, G, CF, H) and IEC classes (gG, aM) display a "curve pending" placeholder until anchor data is added.

The fuse anchor tables are generic shapes consistent with class behaviour, not the published curve of any specific manufacturer or catalogue number. Use them for screening and layout, and substitute the manufacturer's curve for final work.

5. Conductor Damage Overlay

The optional conductor overlay draws the cable's short-circuit thermal-withstand curve using the ICEA / IEEE 242 adiabatic relation. For a conductor of cross-section A (mm²) carrying current I, the time to reach the insulation damage limit is:

t(I) = ( k · A / I )²

where k is a material-and-insulation constant. A device protects the conductor when its clearing time at the available fault current lies below this curve.

Conductor Insulation rating k (A·√s / mm²)
Copper 75 °C 115
Copper 90 °C 143
Aluminium 75 °C 76
Aluminium 90 °C 94

6. Coordination Margin Analysis

6.1 Adjacent-Pair Sampling

Device order in the list represents electrical position, from the most upstream device down to the load. For each adjacent pair, the tool samples currents from the plot's lower bound up to the available fault current and evaluates both devices' operating times at every sample. The minimum separation across the overlap and the separation at the fault current are recorded.

Δt(I) = tupstream(I) − tdownstream(I)

6.2 Status Classification

Status Condition
Coordinated No crossing and minimum Δt ≥ margin threshold
Marginal No crossing, but minimum Δt below the threshold
Miscoordination Δt negative somewhere in the overlap — the upstream device is faster (curves cross)

6.3 Conductor Protection Check

When the conductor overlay is enabled, each device's clearing time at the fault current is compared with the conductor withstand time at the same current. A device that clears more slowly than the cable can withstand raises an unprotected-cable warning.

7. Using the Tool

7.1 Workflow

  • Enter the study settings: available fault current (from the Short-Circuit Lab) and the coordination margin threshold.
  • Build the device chain from upstream to downstream with Add device and set each device's type. Every device starts collapsed; click its coloured arrow to fold out the settings beneath the row. The arrow is also the device's curve colour on the plot, and any expanded device is drawn at full weight while the rest dim.
  • Read the overlaid curves, the fault-current reference line, and the margin table; enable the conductor damage curve, beneath the device table, to check cable protection.
  • Resolve any flagged pairs by adjusting pickups and delays, then re-read the verdict.

7.2 Inputs and File Format

Projects auto-save to browser storage and can be exported as a JSON file (suffix _cd.json). The file stores the study settings, the ordered device array with each device's active-type parameters, and the conductor overlay. Import validates the file suffix and the embedded tool identifier before loading.

7.3 Reading the Results

The Coordination Margins panel opens with a plain-language verdict for the study. Below it, the margins table lists each adjacent pair with its separation at the fault current and its status, followed by specific warnings — curve crossings, thin margins, and unprotected cable — each naming the devices involved and suggesting a remedy.

8. Limitations and Best Practices

Generic curves cannot confirm selectivity in the instantaneous region. Where a downstream fault current exceeds the instantaneous pickup of both an upstream and a downstream breaker, only the manufacturer's tested let-through and selectivity tables can establish whether the pair discriminates. Treat a "Marginal" or instantaneous-region result as a prompt to consult those tables, not as a pass or fail.
  • Draw the available fault current from a short-circuit study at the point of application, not a nameplate assumption.
  • Leave upstream instantaneous elements off, or set a short-time delay, where downstream coordination is required — an always-on upstream instantaneous will race downstream devices at high fault current.
  • For emergency and legally required standby systems, NEC 700.32 / 701.32 require selective coordination confirmed against manufacturer data; this tool is a screening aid only.
  • Have final coordination reviewed and stamped by a qualified engineer.

9. Worked Example

A 480 V feeder string with 8 kA available fault current: a 400 A electronic main with its instantaneous element off and a 0.3 s short-time delay, a 100 A thermal-magnetic feeder breaker, and a 20 A Class C branch MCB, protected by 4/0 AWG copper cable with 90 °C insulation.

Device Type Key settings t at 8 kA
Main 400A Electronic (LSIG) Ir = 400 A, ST 0.3 s flat, INST off 0.30 s
Feeder 100A Thermal-mag MCCB INST 10 × In 0.02 s
Branch 20A MCB (Class C) 5–10 × In band 0.01 s
Device pair Separation at fault Status
Main 400A → Feeder 100A 0.28 s Coordinated
Feeder 100A → Branch 20A 0.01 s Marginal

The main clears at 0.30 s against the feeder's 0.02 s — a 0.28 s margin, comfortably coordinated because the main's short-time delay holds it back while the fault current is below its (disabled) instantaneous threshold. The feeder and branch, however, are both in their instantaneous regions at 8 kA and separated by only 0.01 s, which the tool flags as marginal. This is the characteristic difficulty of coordinating a moulded-case breaker with a downstream MCB at high fault current: the instantaneous elements overlap, and generic curves cannot resolve it. The remedy is to check the manufacturer's selectivity table for this specific breaker pair, or to apply a current-limiting or series-rated combination.

The 4/0 AWG copper conductor (90 °C, k = 143) withstands 8 kA for t = (143 × 107 / 8000)² ≈ 3.66 s. Both devices clear in well under this time, so the cable is protected at the stated fault current.

10. References

  1. IEEE Std 242-2001, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (Buff Book)
  2. IEEE Std 141-1993, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants (Red Book)
  3. IEC 60898-1:2015, Electrical accessories — Circuit-breakers for overcurrent protection for household and similar installations — Part 1: Circuit-breakers for a.c. operation
  4. IEC 60947-2:2016, Low-voltage switchgear and controlgear — Part 2: Circuit-breakers
  5. UL 248-1, Low-Voltage Fuses — Part 1: General Requirements
  6. NFPA 70 (National Electrical Code), Articles 240.87, 240.12, 700.32, and 701.32
  7. ICEA P-32-382 / IEEE Std 242, Short-Circuit Withstand of Insulated Conductors