kVA Tools logokVATools.io ❯ Cable Caliper


Cable Caliper

Technical Documentation and Calculation Methodology

1. Introduction

The Cable Caliper sizes conductors for fixed low-voltage installations up to 1 kV AC per IEC 60364-5-52:2009+AMD1:2024. The tool uses normative current-carrying capacity values from the standard's Annex B tables and correction factor tables, along with the harmonic derating methodology of Annex E (AMD1:2024).

It covers thermal current-carrying capacity, voltage drop, ambient temperature and soil thermal resistivity correction, grouping effects, triplen harmonic neutral loading, short-circuit withstand verification, and overcurrent protective device (OCPD) coordination.

2. Definitions

2.1 Currents and Ratings

Design Current (Ib)

The current the circuit is rated to carry under normal service conditions, derived from load data (kW/kVA, voltage, power factor) or entered directly. It is the basis for conductor cross-section selection.

Current-Carrying Capacity (Iz,tab)

The maximum continuous current a cable can carry under specified reference conditions without exceeding the insulation temperature limit. The tabulated value is read from the applicable Annex B table for the selected installation method, conductor material, insulation type, and number of loaded conductors. Reference conditions are 30 °C ambient air (cables in air) or 20 °C ground (buried cables), with soil thermal resistivity 2.5 K·m/W for buried methods.

The Cable Caliper carries the full normative Annex B values for all seven installation method columns (A1, A2, B1, B2, C, D1, D2) across four table sets:

  • Table B.52.2 – PVC 70 °C, two loaded conductors, copper and aluminium.
  • Table B.52.3 – XLPE/EPR 90 °C, two loaded conductors, copper and aluminium.
  • Table B.52.4 – PVC 70 °C, three loaded conductors, copper and aluminium.
  • Table B.52.5 – XLPE/EPR 90 °C, three loaded conductors, copper and aluminium.

For methods E (multi-core on perforated tray), F (single-core touching in free air), and G (single-core spaced in free air), the tool carries normative values from Tables B.52.10–B.52.13, with separate two-loaded and three-loaded columns and method-specific entries for F and G (available from 25 mm² upward; smaller sizes fall back to the multi-core method E column).

Corrected Current-Carrying Capacity (Iz,eff)

The effective current-carrying capacity after applying all correction factors:

Iz,eff = Iz,tab × Ca × Cg × Cs × Ch
  • Ca – ambient temperature correction factor (Table B.52.14 for air; Table B.52.15 for ground).
  • Cg – grouping correction factor (Tables B.52.17–B.52.19, method-specific).
  • Cs – soil thermal resistivity correction factor (Table B.52.16, separate rows for D1 and D2).
  • Ch – harmonic neutral current reduction factor (Annex E, Eq. E.52.7).

The calculator enforces Ib ≤ Iz,eff for a valid cable selection.

OCPD Current (In)

The rated current of the overcurrent protective device (circuit-breaker or fuse). IEC 60364-4-43 clause 433.1 requires:

Ib ≤ In ≤ Iz,eff

Condition (a) ensures the device rating covers the design load. Condition (b), combined with the conventional tripping current requirement I₂ ≤ 1.45 × Iz, ensures the cable is not overloaded. For MCBs where I₂ = 1.45 × In by definition, condition (b) reduces to In ≤ Iz,eff. The calculator implements this check and flags any violation.

2.2 Neutral Conductor

Neutral Conductor Cross-Section

IEC 60364-5-52:2009+AMD1:2024 clause 524.2 specifies the minimum neutral cross-section relative to line conductors:

  • Single-phase circuits: neutral ≥ line conductor cross-section.
  • Three-phase, line CSA ≤ 16 mm² Cu or ≤ 25 mm² Al: neutral ≥ line conductor cross-section.
  • Three-phase, larger line CSA: neutral may be reduced, subject to a minimum of 16 mm² Cu or 25 mm² Al and not less than 50 % of line conductor CSA.

Clause 524.3 (AMD1:2024) requires that where triplen harmonic currents are expected in three-phase circuits, line and neutral cross-sections shall be selected per Annex E. Above THDi3n = 15 %, the reduced-neutral column of Table E.52.1 is NA per clause 523.6.3, and the neutral is forced equal to the line conductor.

2.3 Harmonic Currents

Triplen Harmonic Content and Neutral Loading

Annex E (normative, AMD1:2024) specifies reduction factors for balanced three-phase cables where the neutral carries triplen harmonic currents. The input is THDi3n (total triplen harmonic current content as a percentage of the fundamental). Where THDi3n is not known, the total THDi is used (footnote a).

The reduction factor k is calculated from the following formulae:

  • Equal neutral and line CSA (Eq. E.52.7): k = 1 / √(1 + 4 · THDi²)
  • Neutral CSA = 50 % of line CSA (Eq. E.52.8, valid only where THDi3n ≤ 15 %): khalf = 1 / √(1 + 7 · THDi²)

where THDi is expressed as a fraction (e.g. 20 % → 0.20). Selected values from Table E.52.1:

THDi3n (%) k (equal neutral CSA) k (half neutral CSA)
5 0.99 0.99
10 0.98 0.97
15 0.96 0.93
20 0.93 NA
25 0.89 NA
30 0.86 NA
35 0.82 NA
40 0.78 NA
45 0.74 NA
50 0.71 NA

NA: not applicable per clause 523.6.3. Above THDi3n = 15 %, the neutral must be sized equal to the line conductor (cl. 524.3).

The calculator applies the equal-CSA formula continuously for all THDi inputs. The half-CSA formula is applied internally only where neutral reduction is modelled and THDi3n ≤ 15 %.

3. Calculation Workflow

The algorithm follows the IEC 60364-5-52:2009+AMD1:2024 conductor selection procedure:

  1. Determine the design current Ib from load data:
    • Single-phase: Ib = P / (V × PF) or Ib = S / V.
    • Three-phase: Ib = P / (√3 × V × PF) or Ib = S / (√3 × V).
  2. Select protective device rating In and verify Ib ≤ In.
  3. Select conductor material (Cu/Al), insulation type (PVC 70 °C / XLPE 90 °C), installation method (A1, A2, B1, B2, C, D1, D2, E, F, G), and number of loaded conductors (2 or 3).
  4. Obtain Iz,tab from the normative Annex B table for the selected combination. The Cable Caliper carries all seven method columns of Tables B.52.2–B.52.5 independently (D1 and D2 are not merged) and the multi-core/single-core columns of Tables B.52.10–B.52.13 for methods E, F, and G.
  5. Compute and apply correction factors:
    • Ca from Table B.52.14 (air) or B.52.15 (ground), with linear interpolation.
    • Cs from Table B.52.16. The table provides separate correction factors for cables in ducts (D1) and cables buried direct (D2). At the reference value of 2.5 K·m/W, Cs = 1.00 for both rows. The D2 row yields significantly higher correction factors at low resistivities (e.g. 1.50 at 1.0 K·m/W vs 1.18 for D1) and lower factors at high resistivities (0.90 at 3.0 K·m/W vs 0.96 for D1).
    • Cg from Tables B.52.17–B.52.19. The tool selects the grouping table by installation method: Item 1 (bunched, methods A–C), Item 4 (perforated tray, method E), Item 5 (ladder/cleats, methods F and G), Table B.52.19 (ducts, method D1), or Table B.52.18 (direct buried, method D2).
    • Ch from Annex E Eq. E.52.7: k = 1 / √(1 + 4 · THDi²).
    This yields Iz,eff = Iz,tab × Ca × Cs × Cg × Ch.
  6. Check thermal criterion: Ib ≤ Iz,eff. If not satisfied, increase cross-section and repeat.
  7. Check OCPD coordination: In ≤ Iz,eff per IEC 60364-4-43 clause 433.1. For MCBs where I₂ = 1.45 × In, the conventional tripping requirement I₂ ≤ 1.45 × Iz reduces to In ≤ Iz,eff. If not satisfied, increase cross-section.
  8. Check short-circuit withstand: the minimum cross-section to survive the prospective fault current for the specified clearance time is computed from the IEC 60364-4-43 adiabatic equation S = I√t / k, where k is the material/insulation constant (Cu/PVC: 115, Cu/XLPE: 143, Al/PVC: 76, Al/XLPE: 94). If the selected size is smaller than this minimum, it is increased.
  9. Check voltage drop for the candidate cross-section. If %Vdrop exceeds the user-specified limit, increase cross-section. The calculator selects the smallest standard size satisfying all four criteria simultaneously (thermal, OCPD, short-circuit, voltage drop).
  10. Determine neutral conductor cross-section per clauses 524.2 and 524.3. Where THDi > 15 %, neutral CSA equals line CSA (Annex E Table E.52.1). Otherwise, the neutral may be reduced per clause 524.2 rules.
The calculator treats thermal current-carrying capacity, OCPD coordination, short-circuit withstand, and voltage drop as separate checks, consistent with IEC 60364. A cable that is thermally adequate may still be upsized by the voltage-drop or short-circuit criterion.

4. User Interface Inputs and IEC Mapping

The table below maps each calculator input to its effect on the calculation and the corresponding IEC 60364-5-52 clause.

Control / Field Main Options / Range Effect on Calculation IEC 60364-5-52 Reference
Design Method "By kW/kVA", "By Current (A)" Determines how Ib is obtained: computed from load data or entered directly. Design current concept in IEC 60364-4-43
System Type Single-phase, Three-phase Sets Ib formula and voltage drop multiplier. Determines the number of loaded conductors (2 for single-phase, 3 for three-phase) for Annex B table selection. Clause 523 (loaded conductors)
System Voltage Common LV levels (e.g. 230/400 V) Used to compute Ib from kW/kVA and in the voltage drop calculation. Does not affect Iz,tab. Clause 525; Annex G Table G.52.1
OCPD Rating In Numeric (A) Verifies Ib ≤ In ≤ Iz,eff. IEC 60364-4-43 clause 433.1
Conductor Material Copper, Aluminium Selects Cu or Al column in Annex B tables and determines conductor resistance for voltage drop. Minimum aluminium size is 10 mm² for power circuits. Annex B; Table 52.2 (minimum sizes)
Insulation Type PVC (70 °C), XLPE/EPR (90 °C) Selects the applicable table set (B.52.2/B.52.4 for PVC or B.52.3/B.52.5 for XLPE) governing permissible conductor temperature and Iz,tab. Also selects the applicable temperature correction column in Tables B.52.14/B.52.15. Annex B tables
Installation Method A1 (single-core in conduit in thermally insulated wall), A2 (multi-core in conduit in thermally insulated wall), B1 (single-core in conduit on wall), B2 (multi-core in conduit on wall), C (clipped direct to wall / unperforated tray), D1 (multi-core in ducts in ground), D2 (cables buried direct in ground), E (multi-core in free air / perforated tray), F (single-core touching in free air / ladder), G (single-core spaced in free air) Selects the applicable Annex B table column. Each method maps directly to its own column in Tables B.52.2–B.52.5 (methods A1–D2) or its own sub-table in Tables B.52.10–B.52.13 (methods E, F, G). The engine does not merge or approximate between methods; D1 and D2 are distinct, and E, F, and G each resolve to their normative column. Annex A (practical-to-reference mapping); Annex B tables
Loaded Phase Conductors 2, 3, or 4 (3P+N) Selects the two-loaded or three-loaded table set from Annex B. A selection of "4" (three phases plus neutral with harmonics) uses the three-loaded-conductor tables, with the neutral heating accounted for by the Annex E harmonic factor Ch. Clause 523; Annex E (four loaded conductors)
Ambient Air Temperature 10–80 °C (entry in °C or °F) Computes Ca for cables in air via Table B.52.14. Separate columns for PVC (11 points, 10–60 °C) and XLPE (15 points, 10–80 °C) with linear interpolation. Reference: 30 °C. The input accepts °C or °F via the inline unit selector; values are converted to °C internally before interpolation. Table B.52.14
Ambient Ground Temperature 10–80 °C (entry in °C or °F) Computes Ca for buried cables via Table B.52.15. Separate columns for PVC and XLPE with linear interpolation. Reference: 20 °C. Applied only for methods D1 and D2. The input accepts °C or °F via the inline unit selector; values are converted to °C internally before interpolation. Table B.52.15
Soil Thermal Resistivity 0.5–3.0 K·m/W Computes Cs for buried cables via Table B.52.16 with linear interpolation. The table provides two separate rows: one for cables in ducts (method D1) and one for cables buried direct (method D2). The D2 row gives substantially higher correction factors at low resistivities and lower factors at high resistivities than the D1 row. Reference: 2.5 K·m/W (Cs = 1.00). Applied only for methods D1 and D2. Table B.52.16
Number of Circuits Grouped 1–20 Determines Cg from method-specific grouping tables with linear interpolation. The engine selects: Table B.52.17 Item 1 (bunched, methods A1/A2/B1/B2/C), Item 4 (perforated tray, method E), Item 5 (ladder/cleats, methods F/G), Table B.52.19 (ducts in ground, method D1), or Table B.52.18 (direct buried, method D2). Cg = 1.0 for a single circuit. Tables B.52.17–B.52.19
THDi (%) 0–200 % Computes Ch per Annex E Eq. E.52.7: k = 1 / √(1 + 4 · THDi²). Enter THDi3n (triplen-only) if known; use total THDi if THDi3n is unknown (footnote a). Above 15 %, neutral CSA is forced equal to line CSA per clause 524.3. Values above approximately 50 % indicate severe harmonic distortion where the Annex E model assumptions are being stretched; such circuits typically warrant power quality investigation and active harmonic mitigation rather than cable derating alone. Annex E (normative); Eq. E.52.7; Table E.52.1; cl. 524.3
Circuit Length Numeric (m or ft) Used in voltage drop calculation. Does not affect Iz,tab but may govern cross-section on long circuits. The input accepts metres or feet via the inline unit selector; values are converted to metres internally before voltage drop is computed. Clause 525
Power Factor (for ΔV) 0–1 Determines the relative contribution of R and X in the voltage drop formula. Low power factor increases voltage drop. Impedance method consistent with clause 525
Voltage Drop Limit Numeric (% or V) Sets the maximum permissible Vdrop. Per clause 525 and Annex G Table G.52.1: 3 % for lighting, 5 % for other uses, measured from the origin of the installation. The input accepts a percentage or an absolute volt value via the inline unit selector; a volt limit is referenced to the nominal system voltage (limit% = limitV × 100 / Vnom) and is converted to a percentage internally before the voltage drop check. Changing the system voltage while the limit is entered in volts will shift the implied percentage. Clause 525; Annex G Table G.52.1
Fault Current Numeric (kA) Prospective fault current at the cable location, used with the fault duration to compute the minimum cross-section via the adiabatic equation. IEC 60364-4-43
Fault Duration Numeric (s or ms) Disconnection time of the protective device at the prospective fault current. Used in the adiabatic equation S = I√t / k. The input accepts seconds or milliseconds via the inline unit selector; values are converted to seconds internally before the adiabatic check. IEC 60364-4-43
k-factor Override Numeric (optional) If entered, overrides the default k constant (Cu/PVC: 115, Cu/XLPE: 143, Al/PVC: 76, Al/XLPE: 94) used in the adiabatic short-circuit equation. This is intended for non-standard insulation systems (e.g. silicone rubber, fire-resistant compounds) or where the designer has a manufacturer-certified k value or has calculated one from first principles per IEC 60364-4-43 Annex A. IEC 60364-4-43 Table 43.1

5. Detailed Methodology

5.1 Determining Design Current

Where load data is entered in kW or kVA, Ib is computed from the nominal voltage and power factor:

Ib,1Φ = P / (V × PF) = S / V
Ib,3Φ = P / (√3 × V × PF) = S / (√3 × V)

Where "By Current" is selected, the entered value is used directly as Ib.

5.2 Selecting the Base Current-Carrying Capacity Iz,tab

The applicable Annex B table is selected based on insulation type (PVC → B.52.2/B.52.4; XLPE → B.52.3/B.52.5), number of loaded conductors (2 → B.52.2/B.52.3; 3 → B.52.4/B.52.5), and installation method (column within the table).

For methods E, F, and G, the engine selects from Tables B.52.10–B.52.13 based on insulation and conductor material. Method E uses the multi-core cable columns (available for all standard sizes from 1.5 mm²). Methods F and G use single-core cable columns which are only populated from 25 mm² upward in the standard; for smaller sizes, the engine falls back to the method E multi-core column.

Iz,tab is read directly for standard cross-sections. The algorithm iterates over the IEC 60228 series (1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630 mm²) until all criteria are satisfied.

5.3 Applying Correction Factors

Ambient Temperature Factor Ca

Ca is obtained from Table B.52.14 (cables in air, reference 30 °C) or Table B.52.15 (cables in ground, reference 20 °C), selected automatically based on whether the installation method starts with "D". Separate columns are provided for PVC 70 °C and XLPE 90 °C insulation. Linear interpolation is applied between tabulated temperature points.

Soil Thermal Resistivity Factor Cs

For buried methods only. Cs is obtained from Table B.52.16 with linear interpolation. The table provides two separate rows:

  • Cables in buried ducts (method D1): factors from 1.28 at 0.5 K·m/W to 0.96 at 3.0 K·m/W.
  • Cables buried direct (method D2): factors from 1.88 at 0.5 K·m/W to 0.90 at 3.0 K·m/W.

The D2 row gives substantially higher correction at low resistivities (wet soils) because the direct-buried cable benefits more from good thermal dissipation than a cable confined in a duct. Conversely, at high resistivities (dry soils), the D2 cable suffers a sharper penalty. For non-buried methods, Cs = 1.00.

Grouping Factor Cg

Where multiple loaded circuits share the same installation conditions, current-carrying capacity is reduced by a grouping factor. The tool selects the grouping table by installation method:

  • Methods A1, A2, B1, B2, C: Table B.52.17 Item 1 (bunched in air / on surface / enclosed).
  • Method E: Table B.52.17 Item 4 (single layer on perforated tray).
  • Methods F, G: Table B.52.17 Item 5 (single layer on ladder/cleats).
  • Method D1: Table B.52.19 Part A (multi-core in single-way ducts, touching).
  • Method D2: Table B.52.18 (direct buried cables, touching).

Linear interpolation is applied between tabulated circuit counts. For counts above the maximum tabulated value, the last tabulated factor is reduced by a further 5 %. For a single circuit, Cg = 1.00.

Harmonic Factor Ch and Neutral Sizing

For three-phase four- or five-core cables with triplen harmonic content, Ch is computed from Annex E Eq. E.52.7:

k = 1 / √(1 + 4 · THDi²)

where THDi is expressed as a fraction. Ch = k is applied for all non-zero THDi. Above THDi3n = 15 %, the neutral cross-section is forced equal to the line conductor per clause 524.3 (Table E.52.1 half-CSA column NA per 523.6.3).

5.4 OCPD Coordination

The calculator verifies the IEC 60364-4-43 clause 433.1 coordination condition:

Ib ≤ In ≤ Iz,eff

For MCBs, the conventional tripping current I₂ equals 1.45 × In by the device standard. The IEC requirement I₂ ≤ 1.45 × Iz therefore reduces to In ≤ Iz,eff. The sizing loop selects the smallest cable satisfying this alongside the thermal, short-circuit, and voltage drop criteria.

5.5 Short-Circuit Withstand

The minimum conductor cross-section to withstand the prospective fault current is computed from the IEC 60364-4-43 adiabatic equation:

Smin = Isc × √t / k

where Isc is the prospective fault current (A), t is the disconnection time (s), and k is the material/insulation constant. Default k values: Cu/PVC = 115, Cu/XLPE = 143, Al/PVC = 76, Al/XLPE = 94 A·s½/mm². An optional k-factor override is available for non-standard insulation systems.

5.6 Voltage Drop Calculation

An impedance-based R–X method is used:

%Vdrop,1Φ = 2 × I × (R cos φ + X sin φ) × L Vnom × 100

%Vdrop,3Φ = √3 × I × (R cos φ + X sin φ) × L Vnom × 100

Conductor resistance R is calculated from material resistivity at 20 °C (1.72×10−8 Ω·m for copper, 2.82×10−8 Ω·m for aluminium), divided by cross-sectional area, and corrected to operating temperature (90 °C for XLPE, 70 °C for PVC) using the temperature coefficient (0.00393/°C Cu, 0.00403/°C Al).

Cable reactance X is size-dependent, using representative values of 0.065–0.095 Ω/km for multi-core LV cables (higher for smaller cross-sections). These are engineering approximations; for critical applications, manufacturer-specific reactance data should be used.

5.7 Linear Interpolation

IEC tables provide discrete values for standard cross-sections, temperatures, and installation conditions. Linear interpolation between bounding table entries is applied to temperature correction factors, grouping factors, and soil resistivity correction factors where the input falls between tabulated points. Ampacity values are looked up directly for standard IEC 60228 cross-sections without interpolation. The Cable Caliper does contain interpolation infrastructure for ampacity tables as a safeguard, but during normal conductor selection it only queries standard sizes and the interpolation path is not exercised.

6. Worked Examples

6.1 Example 1 – Three-Phase Cable in Air

Objective: Size a three-phase copper cable in air to supply a 30 kW motor at 400 V, 50 Hz, PF = 0.85, length 40 m, with a voltage-drop limit of 5 %.

Step 1 – Design Current:

Ib = P / (√3 × V × PF) = 30,000 / (√3 × 400 × 0.85) ≈ 51 A

Step 2 – User Selections:

  • System type: Three-phase.
  • Conductor: Copper, XLPE/EPR (90 °C).
  • Cable: Multi-core, 3 loaded conductors.
  • Installation: Clipped direct to wall (reference method C).
  • Ambient air temperature: 40 °C.
  • Grouping: Single circuit (Cg = 1.0).
  • THDi: 0 % (Ch = 1.0).

Step 3 – Base Ampacity from Table B.52.5 Column 6 (method C, XLPE, 3-loaded, Cu):

For 10 mm²: Iz,tab = 71 A.

Step 4 – Temperature Correction:

At 40 °C, Table B.52.14 gives Ca = 0.91 for XLPE. Iz,eff = 71 × 0.91 = 64.6 A. Since 64.6 ≥ 51 A, 10 mm² is thermally adequate.

Step 5 – OCPD Coordination:

If In = 63 A (standard MCB rating), verify In ≤ Iz,eff: 63 ≤ 64.6 A — satisfied.

Step 6 – Voltage Drop:

Using R and X for 10 mm² Cu at 90 °C over 40 m, the three-phase voltage drop is evaluated. If the result is within 5 %, the cable is accepted.

Result: 10 mm² Cu XLPE, method C. The results panel shows the thermal margin, voltage drop percentage, and that all four criteria (thermal, OCPD, short-circuit, voltage drop) are satisfied.

6.2 Example 2 – Harmonic-Rich Four-Core Cable in Ground

Objective: Size a four-core cable supplying a three-phase IT load at 400 V with significant third harmonic content and multiple circuits in a trench.

Given:

  • Three-phase balanced load, P = 40 kW, PF = 0.9.
  • Nominal voltage: 400 V, 50 Hz.
  • Third harmonic content: THDi = 35 %.
  • Four-core cable (3P+N) in ducts in the ground (method D1).
  • Ground temperature: 30 °C, soil thermal resistivity: 2.5 K·m/W.
  • 3 circuits grouped in the same trench.
  • Circuit length: 80 m, voltage-drop limit: 5 %.

Step 1 – Design Current:

Ib = 40,000 / (√3 × 400 × 0.9) ≈ 64 A

Step 2 – Correction Factors:

  • Ca: Table B.52.15, XLPE at 30 °C ground = 0.93.
  • Cs: Table B.52.16, D1 row at 2.5 K·m/W = 1.00.
  • Cg: Table B.52.19, D1 ducts touching, 3 circuits = 0.75.
  • Ch: Annex E Eq. E.52.7, THDi = 0.35: k = 1 / √(1 + 4 × 0.1225) = 1 / √1.49 = 0.819.

Total factor: 0.93 × 1.00 × 0.75 × 0.819 = 0.571.

Step 3 – Size Selection from Table B.52.5 Column 7 (D1, XLPE, 3-loaded, Cu):

The tool iterates over standard sizes. For 50 mm²: Iz,tab = 135 A, Iz,eff = 135 × 0.571 = 77.1 A ≥ 64 A — thermally adequate.

Step 4 – Neutral Sizing:

THDi = 35 % > 15 %: neutral CSA forced equal to line CSA (50 mm²) per clause 524.3.

Step 5 – OCPD and Voltage Drop:

OCPD coordination and voltage drop for 80 m are checked. If voltage drop requires a larger size, the calculator upsizes accordingly.

Result: The selected cross-section is significantly larger than a non-harmonic, ungrouped circuit of the same current, due to the combined effects of grouping (Cg = 0.75) and harmonic derating (Ch = 0.82). The results panel shows all applied factors and which criterion governed.

7. References

7.1 Standards

  1. IEC 60364-5-52:2009+AMD1:2024 – Low-voltage electrical installations – Part 5-52: Selection and erection of electrical equipment – Wiring systems.
  2. IEC 60364-4-43:2023 – Low-voltage electrical installations – Part 4-43: Protection for safety – Protection against overcurrent.
  3. IEC 60228:2004 – Conductors of insulated cables.
  4. IEC 60287 series – Electric cables – Calculation of the current rating.