kVA Tools logokVATools.io ❯ Breaker Wizard


Breaker Wizard

Technical Documentation and Selection Methodology

1. Introduction

The Breaker Wizard is a decision-support tool intended to help structure the early stages of low-voltage circuit breaker selection. It follows the practical selection framing in IEEE Std 3004.5-2025 (low-voltage circuit breakers), focusing on the “basic selection criteria” (voltage rating, current rating, interrupting rating) and common application/service considerations.

This wizard does not replace a short-circuit study, protective device coordination study, or manufacturer application review. Results are preliminary and must be verified by a qualified engineer against applicable codes, project specifications, and manufacturer documentation.

1.1 Scope

The wizard is aimed at AC low-voltage (typically ≤ 600 V) feeder and main breaker selection tasks where you already have (or can estimate) key system inputs such as load current and available short-circuit current at the equipment terminals. It supports common breaker families (molded-case, insulated-case, and low-voltage power circuit breakers) and provides:

  • Recommended breaker class starting point (MCCB / ICCB / LVPCB) based on application context.
  • Grounding/rating-style compatibility checks (slash-rated vs straight-rated devices).
  • Minimum continuous ampere rating target (including a common 125% factor for continuous loads).
  • Minimum interrupting rating target based on available short-circuit current (symmetrical kA).
  • Environmental/service-condition flags (altitude, ambient temperature, humidity/contamination).
  • Project JSON export/import and browser autosave for repeatable workflows.

2. Low-Voltage Breaker Classifications

2.1 Common device families

Family Typical use cases Selection notes
MCCB (Molded-Case Circuit Breaker) Panelboards, distribution feeders, branch circuits, many switchboard applications Compact, broad availability; verify interrupting rating, trip unit features, and coordination objectives.
ICCB (Insulated-Case Circuit Breaker) Higher current switchboards, applications needing enhanced short-time/adjustability versus many MCCBs A UL 489 sub-type of MCCB with two-step stored energy mechanisms, greater short-time capability, and limited field maintainability. Bridges the gap between standard MCCBs and LVPCBs; confirm short-time withstand and trip unit capability.
LVPCB (Low-Voltage Power Circuit Breaker) Low-voltage switchgear, applications emphasizing maintainability, short-time withstand, and robust coordination Typically used where serviceability and selective coordination are priorities; confirm switchgear design requirements.

2.2 What the wizard outputs here

Step 1 produces a suggested “breaker class” as a starting point. This is a heuristic recommendation based on the selected equipment context and the stated need for selective coordination/short-time features or field maintainability. It is not a definitive product selection.

3. Wizard Workflow Overview

3.1 Progressive modules (Steps 1–6)

  1. Step 1 — Application context: Choose equipment context, maintainability, and coordination needs.
  2. Step 2 — System basics: Enter voltage, system type, frequency, grounding, and rating style.
  3. Step 3 — Load current and duty: Enter load current, continuous duty, device rating type (100% vs non-100%-rated), and special-load flags. Arc energy reduction (≥ 1200 A), GFP (≥ 1000 A solidly grounded > 150 V-to-ground), and NEC 2026 §110.16 arc flash labeling flags are triggered automatically.
  4. Step 4 — Available short-circuit current: Enter available fault current and optional X/R; handle series-rated cases.
  5. Step 5 — Service conditions: Enter altitude, ambient temperature (optional), and humidity/contamination category.
  6. Step 6 — Summary: Consolidated targets and flags for documentation and downstream coordination work.
The step gating is intentionally strict: later modules remain locked until earlier required inputs are provided. This is meant to prevent “false confidence” outputs when core rating inputs are missing.

4. Input Fields and Parameters

4.1 Project

Field Description Where used
Project Title User label used for saved files and reports. Export filename, on-screen header.

4.2 Step 1 — Application context

Field Options Notes
Equipment context Panelboard, Switchboard, MCC, LV switchgear, Other/Unknown Drives the starting-point recommendation (MCCB / ICCB / LVPCB).
Maintainability requirement Field maintainable preferred / Not required / Unknown May bias recommendation toward ICCB/LVPCB depending on context.
Coordination / short-time needs Basic / Selective coordination / Short-time withstand-delay needed Used to infer whether short-time features are likely required.

4.3 Step 2 — System voltage and grounding

Field Example values Selection impact
System voltage (V) 120/208, 277/480, 347/600 (line-to-line) Must be compatible with breaker voltage rating and application limits.
System type Single-phase, 3-phase 3-wire, 3-phase 4-wire Used with grounding and rating style checks.
Grounding Solidly grounded, Impedance grounded, Ungrounded, Unknown Important for slash-rated device application checks.
System frequency (Hz) 60 Hz / 50 Hz / Other Non-60 Hz selections generate a flag for trip unit calibration and derating review (§4.12 / §5.3.3). Consult manufacturer for frequencies outside 48–62 Hz.
Rating style Slash-rated, Straight-rated Slash-rated devices are intended for solidly grounded systems only (§5.3.1). Straight-rated devices are applicable on grounded or ungrounded systems; impedance/ungrounded systems require single-pole interrupting capability verification (§4.40).
Grounding and rating-style requirements are manufacturer- and standard-dependent. The wizard flags common misapplication cases (for example, slash-rated on ungrounded/impedance-grounded systems) but cannot confirm suitability without device-specific data.

4.4 Step 3 — Load current and duty

Field Units Selection impact
Load current (Iload) A Baseline for continuous ampere rating target.
Continuous duty Continuous / Non-continuous / Unknown Drives which continuous current formula applies (see §5.3 below).
Device rating Non-100%-rated (most MCCBs/ICCBs) / 100%-rated (all LVPCBs; listed MCCBs/ICCBs) Selects the §5.3.4.1 formula path. Non-100%-rated: trip rating ≥ 1.25 × Iload. 100%-rated: trip rating ≥ Iload. All LVPCBs are 100%-rated in their design enclosures; MCCBs/ICCBs require specific UL 489 listing (§7.1.4.3, frame ≥ 250 A or multi-pole > 250 V).
Special load flag None, Motor/high inrush, Transformer energization, Nonlinear/harmonics Adds informational notes for coordination and thermal considerations.

4.5 Step 4 — Fault current and interrupting rating

Field Units Selection impact
Available short-circuit current at terminals (Isc) kA (symmetrical RMS) Minimum interrupting rating target (Iinterrupt ≥ Isc).
X/R ratio (optional) — When provided, the wizard computes the IEEE 3004.5-2025 Table 24 multiplying factor (MF), calculates the adjusted interrupting requirement (Isc × MF), and rounds up to the next standard rating. If X/R is within the test circuit limit for the device type, MF = 1.00 and no adjustment is needed.
Series-rated system Yes / No If “Yes”, the wizard requires a listed/tested combination reference; it does not calculate series ratings.
Series combination reference Text Manufacturer/listing reference for the exact upstream/downstream combination.

4.6 Step 5 — Service conditions

Field Units Selection impact
Altitude m Flags when > 1830 m (MCCBs/ICCBs) or > 2000 m (LVPCBs); manufacturer derating/correction may be required. See §5.5 for threshold details.
Ambient temperature (optional) °C Flags when > 40 °C to prompt thermal derating review.
Humidity/contamination Normal / High humidity / Corrosive/contaminated Generates environmental cautions for enclosure/material selection and possible derating.

5. Decision Logic and Targets

5.1 Breaker class recommendation (Step 1)

The wizard produces a narrative recommendation for a breaker family based on equipment context and the likelihood that short-time withstand/short-time delay features or field maintainability are required. This recommendation is intended to guide which product families you should consider first (for example, MCCB vs LVPCB), not to pick a specific make/model.

The Step 1 recommendation also feeds the Step 4 X/R logic: if the context leans toward LVPCB (switchgear context, short-time withstand needed, or field maintainability in a switchboard), the wizard applies the LVPCB test circuit X/R limit (6.6 unfused, 4.9 fused) rather than the MCCB/ICCB limits from IEEE 3004.5-2025 Table 18. This matters because a 42 kA MCCB has a test X/R limit of only 4.90, whereas an unfused LVPCB at the same fault level has a limit of 6.6.

5.2 Voltage rating styles — slash-rated vs straight-rated

Circuit breakers carry a voltage rating stamped on the nameplate, but the format of that rating tells you something important about how the device was tested and where it can safely be applied. Two formats exist: straight-rated (e.g. 480 V or 600 V) and slash-rated (e.g. 480Y/277 V or 120/240 V).

Why "slash"? The slash (/) in the rating is not a stylistic choice — it carries specific meaning defined in NEC §240.85 and UL 489. A slash-rated device is one that has been tested and proven safe for use on a solidly grounded system where the two numbers represent:

  • The higher value (left of the slash) — the maximum permissible line-to-line voltage.
  • The lower value (right of the slash) — the maximum permissible line-to-ground voltage for any individual pole.

For example, a breaker marked 480Y/277 V may be applied on a 480 V, 3-phase, 4-wire wye system with a solidly grounded neutral, because no individual pole will ever see more than 277 V to ground during a fault. The grounded neutral pins the neutral point to ground potential, bounding the recovery voltage across an opening pole. The breaker is designed and tested for that bounded condition — and only that condition.

Why can a slash-rated breaker not be used on an ungrounded or impedance-grounded system? On a system without a solidly grounded neutral, a line-to-ground fault on one phase can cause the neutral point to shift in voltage. A healthy (unfaulted) phase may then appear at full line-to-line voltage with respect to ground — not line-to-ground voltage. A pole of the slash-rated breaker opening under those conditions faces a recovery voltage it was never tested to handle. Using a slash-rated device on such a system is a misapplication that can result in a failed interruption or catastrophic failure of the breaker.

Straight-rated devices (e.g. 480 V or 600 V with no slash) are tested at full line-to-line voltage across individual poles and are therefore suitable for ungrounded, impedance-grounded, and solidly grounded systems alike — subject to the specific interrupting ratings marked on the device. They are the more conservative and universally applicable choice.

The wizard flags slash-rated devices as NOT OK on ungrounded or impedance-grounded systems, and as Review when grounding is unknown. For impedance-grounded and ungrounded systems, a straight-rated device with verified single-pole interrupting capability must be selected (§4.40, §5.3.2). Confirm with the manufacturer for corner-grounded delta configurations.

The wizard implements this as a conservative screening check:

  • Slash-rated devices are flagged for review when the system is not identified as solidly grounded.
  • Straight-rated devices are treated as broadly applicable, pending manufacturer limits and single-pole rating verification on non-solidly-grounded systems.

5.3 Continuous current target (Step 3)

The wizard applies §5.3.4.1 of IEEE 3004.5-2025, with the formula path selected by the Device Rating field:

Non-100%-rated device (most MCCBs/ICCBs — 80% loading rule):

Itrip,target ≥ 1.25 × Iload
100%-rated device (all LVPCBs; MCCBs/ICCBs listed per UL 489 §7.1.4.3):

Itrip,target ≥ Iload

For non-continuous loads, the target is Itrip,target = Iload regardless of device rating. In all cases, the result is rounded up to the next standard NEC ampere rating from NEC §240.6 / IEEE 3004.5-2025 Table 11. The final selection must also consider conductor size, termination temperature ratings, enclosure ventilation, and ambient temperature effects.

Two automatic flags fire based on the computed standard rating:

  • Arc energy reduction (≥ 1200 A): NEC §240.87 / §5.11 requires a listed arc energy reduction method when the breaker is rated ≥ 1200 A. See §5.7 below.
  • Ground-fault protection (≥ 1000 A, solidly grounded 4-wire, V-to-ground > 150 V): NEC §230.95 / §215.10 / §240.13 may require GFP. See §5.6 below.

5.4 Interrupting rating target and X/R ratio (Step 4)

What is the X/R ratio? In an AC power system, impedance has two components: resistance (R) and inductive reactance (X). The X/R ratio at any point in the system describes how inductive the fault current path is — a higher X/R means the circuit is more inductive and less resistive.

When a short circuit occurs, the fault current does not instantly reach its symmetrical (steady-state) sine wave shape. Because inductance opposes sudden changes in current, there is a large DC component superimposed on the symmetrical AC waveform immediately after fault inception. This DC offset — also called the asymmetrical component — adds to the peak value of the first few current cycles, making the actual peak current significantly higher than the symmetrical rms value that Ohm's Law gives you. The DC component decays over time with a time constant L/R = X/(ωR), directly proportional to the X/R ratio. A high X/R means the offset decays slowly, so the breaker may still face a substantially asymmetrical waveform when it opens.

Why does X/R matter for circuit breaker selection? Circuit breakers are proof-tested at a specific X/R (or power factor) defined by their product standard (Table 18 of IEEE 3004.5-2025). The symmetrical interrupting rating on the nameplate implicitly assumes the system X/R does not exceed that test value. If the system X/R is higher, the breaker faces a more severe asymmetrical peak than it was designed for — its effective interrupting capability is reduced. The multiplying factor (MF) from Table 24 of IEEE 3004.5-2025 quantifies that reduction. You either multiply the calculated fault current by MF to get the true duty requirement, or equivalently de-rate the breaker's interrupting rating by 1/MF.

Practical context: High-voltage utility sources and large transformers typically have high X/R ratios (X/R of 10–20 is common at the secondary terminals of large power transformers). As you move downstream, resistance accumulates in cables and bus, so X/R decreases. For most secondary distribution panels fed through significant cable runs, X/R is often in the 3–8 range. The key insight is that the test X/R limits for MCCBs are surprisingly low — 1.73 for the ≤10 kA range, and only 4.90 for the >20 kA range. A system X/R of 8, common near a transformer secondary, already requires an MF adjustment for any MCCB with a >20 kA rating.

The minimum interrupting rating target is the available short-circuit current at the device terminals, rounded up to the next standard MCCB/ICCB interrupting rating per Table 17 of IEEE 3004.5-2025 (UL 489 Table 8.1). This is the base rating output:

Base interrupting rating target:

Iinterrupt,min ≥ Isc,available → rounded up to nearest standard rating:
5, 7.5, 10, 14, 18, 20, 22, 25, 30, 35, 42, 50, 65, 85, 100, 125, 150, 200 kA (rms sym.)

X/R ratio evaluation and Table 24 MF computation (§4.39): Circuit breakers are tested at specific power factor / X/R values per Table 18. If the system X/R exceeds the test circuit limit, a multiplying factor (MF) from Table 24 must be applied to the calculated fault current. The wizard computes this MF by linear interpolation through Table 24 and outputs an adjusted interrupting requirement:

Adjusted interrupting requirement:

Iinterrupt,adj = Isc,available × MF → rounded up to next standard rating

The test circuit X/R limits depend on both the interrupting rating range and the device type. The wizard selects the correct limit based on the breaker class inferred from Step 1:

Device type Fault range Test PF Test X/R limit
MCCB / ICCB ≤ 10 kA 0.45–0.50 ≈ 1.73–1.98
MCCB / ICCB 10–20 kA 0.25–0.30 ≈ 3.18–3.87
MCCB / ICCB > 20 kA 0.15–0.20 ≈ 4.90–6.59
Unfused LVPCB All ranges 0.15 6.6
Fused LVPCB All ranges 0.20 4.9

A threshold of X/R > 10 (as seen in some older screening tools) is too permissive for MCCBs: a 42 kA MCCB has a test X/R limit of only 4.90, so a system X/R of 8 already requires an MF adjustment. If X/R is within the applicable limit, MF = 1.00 and no adjustment is required. The wizard always shows both the base rating and the MF-adjusted rating for clarity.

5.5 Service condition flags — altitude, temperature, and humidity (Step 5)

Why does altitude affect circuit breaker selection? As altitude increases, atmospheric pressure decreases and air becomes less dense. Air performs two critical jobs inside a circuit breaker: it provides electrical insulation between live parts, and it carries heat away from current-carrying components. Both properties degrade at altitude.

Dielectric (insulation) effect: Less dense air has lower dielectric strength. The same air gap that reliably isolates conductors at sea level provides less insulation at altitude. A breaker operating at high altitude can suffer reduced voltage withstand capability and may flash over at voltages that would be safe at sea level. Voltage derating is required above the standard altitude limits.

Thermal (cooling) effect: Thinner air transfers heat less efficiently by convection. A breaker carrying rated current at high altitude runs hotter because the air cannot remove heat as fast. This can cause thermal trip units to operate prematurely or allow current-carrying parts to overheat. Current derating compensates for this reduced cooling.

Note that ambient temperature naturally decreases with altitude, which partially offsets the thermal effect. However, the dielectric effect is not offset by lower temperature, so voltage derating must be applied regardless.

Why does humidity affect circuit breaker selection? Moisture is the enemy of electrical insulation. High humidity — especially when condensation is possible — creates conducting paths across insulating surfaces inside the breaker. A thin film of water can dramatically reduce the effective surface resistance of an insulator, potentially allowing leakage currents to flow or, in severe cases, causing a tracking fault or flashover at voltage levels the breaker would normally withstand comfortably. The concern is not humidity alone, but condensation — water actually depositing on surfaces — which occurs when a cool breaker is placed in a warm, humid environment or when enclosure temperatures cycle through the dew point.

Corrosive environments add a further mechanism: conductive or chemically aggressive contamination (salt spray, industrial chemicals, conductive dust) deposits on insulating surfaces and accelerates degradation of insulation, contacts, and operating mechanisms. Enclosure selection, space heaters to prevent condensation, and materials treatment (tropical treatment, special coatings) are the primary mitigations.

Environmental inputs do not directly change computed rating targets; instead, they generate explicit flags prompting a derating/correction check during device selection. Key thresholds per §4.18 of IEEE 3004.5-2025:

  • Altitude > 1830 m (6000 ft): MCCBs and ICCBs may require derating for voltage, current, and sometimes interrupting capacity (§4.18). Consult manufacturer.
  • Altitude > 2000 m (6562 ft): LVPCBs require derating per Table 7 (IEEE Std C37.13 correction factors: rated current ×0.99 at 2600 m, ×0.96 at 3900 m; rated voltage ×0.95 and ×0.80 respectively).
  • Ambient > 40 °C: Apply thermal derating per §4.16 — Eq. (1) for LVPCBs (IEEE Std C37.20.1 Appendix B.4.2), Eq. (2) or manufacturer tables for MCCBs with bimetallic trips.
  • Ambient < –5 °C: Below the standard operating range (§4.13, §5.5 — range is –5 °C to +40 °C). Condensation, lubricant thickening, and material brittleness are concerns. Space heaters and special enclosures may be required. Consult manufacturer.

5.6 Ground-fault protection advisory (Step 3 automatic flag)

When the computed minimum continuous rating is ≥ 1000 A and the system is solidly grounded with voltage-to-ground exceeding 150 V (for example, a 480Y/277 V 4-wire system, V-to-ground ≈ 277 V), the wizard automatically generates a ground-fault protection advisory. NEC §230.95, §215.10, and §240.13 require ground-fault protection of equipment (GFP) for these conditions on service entrances and feeders. Key GFP constraints per UL 1053 and the NEC:

  • Nominal current threshold ≤ 1200 A.
  • Time delay ≤ 1 second at 3000 A.
  • Time delay ≤ 2 seconds at 150% of the set threshold.

Verify applicability and settings with the authority having jurisdiction (AHJ). GFP requirements vary by application (see also NEC Article 517 for health care facilities).

5.7 Arc energy reduction flag (Step 3 automatic flag)

When the computed minimum continuous rating reaches ≥ 1200 A, the wizard flags the NEC §240.87 arc energy reduction requirement (IEEE 3004.5-2025 §5.11). Beginning with NEC 2014, all circuit breakers rated ≥ 1200 A must incorporate a listed arc energy reduction method set to operate at a value below the minimum available arcing current. Acceptable methods include:

  • Zone-selective interlocking (ZSI)
  • Differential relaying
  • Energy-reducing maintenance switching (ERMS) with local status indicator
  • Energy-reducing active arc flash mitigation system
  • Instantaneous override (non-adjustable, permanent)
  • Approved equivalent means

Field-test confirmation is required after installation. Temporary adjustment of the instantaneous trip setting to achieve arc energy reduction is not permitted.

5.7a Arc flash hazard labeling (NEC 2026 §110.16)

NEC 2026 §110.16 significantly expands the scope of required arc flash hazard labeling. Prior editions required field-applied warning labels only on service and feeder equipment rated 1,000 A or larger. The 2026 edition removes the current-rating threshold entirely: labels are now required on all non-dwelling service and feeder equipment, including switchboards, switchgear, panelboards, motor control centres, meter sockets, and similar equipment, regardless of ampere rating.

Required label content per NEC 2026 §110.16:

  • Nominal voltage of the equipment
  • Arc-flash boundary distance
  • Incident energy level or PPE category
  • Date of the arc flash assessment

The wizard generates a §110.16 labeling note for all non-panelboard contexts (switchgear, switchboards, MCCs) and for panelboards in non-dwelling occupancies. The note is informational — the label data must come from a site-specific arc flash hazard analysis per IEEE Std 1584-2018, which the Arc Flash Calculator supports. Ensure the labeling requirement is coordinated with the arc flash study scope before equipment procurement.

5.8 DC system advisory (Step 2)

When "DC" is selected as the system type, the wizard flags that its rating logic (continuous current factor, X/R multiplying factor, AC voltage/grounding checks) applies to AC systems only. DC application requires a separate evaluation path per §4.41 of IEEE 3004.5-2025:

  • Verify the DC voltage rating marked on the device; DC interrupting ratings differ from AC.
  • Apply a √2 (≈ 1.41) correction factor in the instantaneous trip region of the TCC — the magnetic trip mechanism responds to peak current, so the DC current required to operate it is √2 times the equivalent AC rms value shown on the TCC abscissa.
  • Verify the circuit L/R time constant: ≤ 3 ms for circuit breakers with interrupting ratings below 10 000 A; ≤ 8 ms for ratings ≥ 10 000 A.
  • Confirm the trip unit is suitable for DC — electronic trip units designed for AC may not function correctly on DC circuits.

5.9 System frequency advisory (Step 2)

Why does frequency affect circuit breaker selection? Frequency influences circuit breaker performance through three distinct mechanisms: thermal trip calibration, iron-core losses, and current sensor accuracy.

Thermal trip calibration: Bimetallic overload elements respond to the heat produced by current. Some MCCBs use an iron-core transformer to couple load current into the bimetal — the heating in that core depends on frequency, so a trip unit calibrated at 60 Hz will respond at a different threshold at 50 Hz. Transformer-heated bimetal MCCBs therefore require special recalibration for 50 Hz operation. Directly heated bimetal elements (where load current flows directly through the bimetal strip) are resistive heaters and are generally insensitive to frequency up to about 120 Hz.

Eddy current and skin effect: Above 120 Hz, eddy current losses in iron-core components (sensors, flux-shifting mechanisms, current transformers) increase substantially — eddy current loss is proportional to frequency squared (Peddy ∝ f²). Skin effect simultaneously concentrates current at the surface of conductors and bimetal strips, raising their effective resistance. Both effects cause components to run hotter than expected and can alter trip characteristics or shorten service life.

Electronic trip unit sensor accuracy: Many modern electronic trip units use air-core (Rogowski coil) sensors. A Rogowski coil produces an output proportional to the rate of change of current (di/dt) rather than to the current itself. At high frequencies or with significant harmonic content, the di/dt signal grows large and can exceed the input range of the analog-to-digital converter, causing nuisance trips or measurement errors. Consult the manufacturer's data for the trip unit's specified operating frequency range and harmonic tolerance.

When a frequency other than 60 Hz is selected, the wizard generates a flag referencing §4.12 and §5.3.3. Practical considerations:

  • Transformer-heated bimetal MCCBs are calibrated for 60 Hz and require special recalibration for 50 Hz. Directly heated bimetal MCCBs can generally be applied up to 120 Hz without derating.
  • At frequencies above 120 Hz, eddy currents and skin effect increase heating in iron-core sensors and thermal elements; derating or special calibration is required.
  • Electronic trip units with Rogowski coil sensors produce output proportional to di/dt — verify the trip unit's specified operating frequency range and harmonic tolerance with the manufacturer.
  • Circuit breakers applied outside 48–62 Hz must be specifically approved by the manufacturer for the intended frequency.

6. Application and Rating Considerations (IEEE 3004.5 topics)

6.1 Voltage rating and system grounding

  • Confirm the breaker’s AC voltage rating matches the system’s maximum line-to-line voltage and the intended pole application.
  • Confirm line-to-ground voltage limits for slash-rated devices, and ensure system grounding matches the intended application.
  • For corner-grounded delta, ungrounded, or impedance-grounded systems, verify device application restrictions carefully.

6.2 Frequency, temperature, and enclosure effects

  • Verify the breaker's frequency rating (typically 50/60 Hz) is compatible with the supply. Non-standard frequencies require manufacturer consultation (§4.12 / §5.3.3). See §5.9 above.
  • Standard operating ambient range is –5 °C to +40 °C for MCCBs, ICCBs, and LVPCBs (§4.13). Operation outside this range requires special provisions.
  • Consider enclosure heat rise; the standard assumes internal temperature may be up to 15 °C above external ambient. Apply manufacturer thermal derating per §4.16 where required.
  • Enclosure selection and ventilation can materially affect breaker temperature rise and usable ampacity. Minimum enclosure sizes are specified by the manufacturer and affect whether the device is 80% or 100% rated.

6.3 Conductors, terminations, and nonlinear loads

  • Confirm conductor size, insulation, and termination temperature ratings align with the breaker’s lugs/terminations.
  • Nonlinear loads can increase RMS current and thermal stress; review neutral loading and harmonic heating impacts.
  • High inrush loads (motors/transformers) require review of instantaneous pickup and coordination.

6.4 Short-time withstand and selective coordination

Where selective coordination is required (for example, essential systems or critical process loads), evaluate time-current curves for:

  • Long-time pickup and delay (overload region)
  • Short-time pickup and delay (if available/used)
  • Instantaneous pickup (if enabled)
  • Ground-fault pickup and delay (if equipped)

The wizard does not compute coordination (see §1 note); it prompts you to select a breaker family likely to support the required adjustments.

6.5 Series ratings — what they are and how they differ from slash-rated

What is a series-rated system? A series-rated system is one where a load-side circuit breaker (the branch or feeder breaker) has an interrupting rating lower than the available short-circuit current at its point of connection. Under normal rules, this would be a code violation — every protective device must be rated to interrupt the maximum fault current it could face. A series rating is the tested exception to that rule.

In a series arrangement, the upstream device (the main breaker or upstream MCCB) has a full interrupting rating at the available fault level. When a fault occurs on the load side, both devices operate together to interrupt the fault current. The upstream device limits the let-through current — either by operating very fast (current-limiting) or by tripping and interrupting — to a level that the downstream device, despite its lower individual rating, can safely handle. The combination is assigned the higher series interrupting rating only after the manufacturer has proven, through actual short-circuit testing, that the downstream device survives the fault sequence without damage.

How does a fault clear in a series-rated system? When the available fault current exceeds the downstream breaker's standalone rating but is within the series rating:

  • Both the upstream and downstream devices operate and attempt to trip.
  • The upstream device (with the higher rating) may interrupt the fault, or both devices may share the interruption — the exact sequence depends on the tested combination.
  • In most cases, both breakers trip, de-energizing the entire upstream bus section — not just the faulted feeder. This loss of selectivity is the principal disadvantage of series ratings.
  • After the fault, both devices must be inspected before reenergizing, and the downstream device must be replaced if it has been subjected to current above its standalone rating.

Key restrictions on series-rated systems (NEC §240.86, §110.22):

  • Series ratings must be UL-recognized for the specific combination — they cannot be calculated or assumed from similar-looking products of different manufacturers.
  • Motor loads contributing to fault current are restricted: the sum of motor full-load currents connected between the upstream and downstream devices must not exceed 1% of the downstream breaker's standalone interrupting rating. Motor contribution bypasses the series protection mechanism and can cause the downstream device to face current it cannot handle.
  • Equipment containing series-rated breakers must be permanently field-marked "Caution — Series Rated System" with the series rating clearly identified.
  • The equipment bus bracing must still be rated for the full available fault current, regardless of whether the breakers are series-rated.

Series-rated vs slash-rated — not the same thing. These two terms are sometimes confused by practitioners, but they describe completely different concepts:

Aspect Slash-rated (e.g. 480Y/277 V) Series-rated
What it refers to The voltage rating format of a single breaker The interrupting rating of a tested combination of two breakers in series
What the rating exploits The grounded neutral, which limits the voltage-to-ground on each individual pole The upstream device's ability to limit let-through current to protect the downstream device
Normal-current operation Only the one breaker is in the circuit; the rating describes its voltage limits Both breakers are in the circuit; downstream breaker handles normal overload and fault protection
Fault above the individual rating The breaker may fail — it was not tested for that voltage-to-ground condition Both breakers trip; the upstream device protects the downstream device
Selectivity during fault Not relevant — single device Lost above the downstream breaker's standalone rating; upstream device trips too
System grounding requirement Solidly grounded neutral required No grounding requirement — independent of system grounding
Proof required Device-level UL 489 testing Combination-level short-circuit testing; UL recognition of the specific pair

The wizard requires a manufacturer/listing reference whenever "Series-rated" is selected. The series rating applies only to the exact tested combination — substituting a different model, even from the same manufacturer, invalidates the listed rating. Cascade arrangements (calculated rather than tested) are no longer an acceptable method and are not supported.

7. Outputs

Each step provides an inline output module beneath the inputs. Step 6 consolidates the key targets:

  • Suggested breaker class: MCCB / ICCB / LVPCB starting point with rationale.
  • Voltage/grounding compatibility: OK / Review / NOT OK screening result for slash-rated vs grounding, plus DC and frequency advisories if applicable.
  • Minimum continuous rating target: Ampere target from the selected §5.3.4.1 formula path (100%-rated or non-100%-rated), rounded to the next NEC standard rating. Includes arc energy reduction flag (≥ 1200 A), GFP advisory (≥ 1000 A, solidly grounded 4-wire > 150 V-to-ground), and NEC 2026 §110.16 arc flash hazard labeling note where triggered.
  • Minimum interrupting rating target (base): kA target from IEEE 3004.5-2025 Table 17, rounded up from available fault current.
  • Adjusted interrupting rating (Table 24 MF): When X/R is provided, the MF-adjusted requirement and the resulting standard rating. Shown as “X kA (base) → Y kA (MF = Z)” in the summary when an adjustment applies.
  • X/R evaluation: Confirms whether system X/R is within the test circuit limit for the applicable device type/rating range, and shows the computed MF.
  • Environmental flags: Altitude, ambient temperature (high and low), and humidity/contamination cautions.

8. References

  1. IEEE Std 3004.5-2025, IEEE Recommended Practice for the Application of Low-Voltage Circuit Breakers in Industrial and Commercial Power Systems
  2. NFPA 70-2026, National Electrical Code (NEC) — Articles 110 (§110.16 arc flash labeling), 210, 215, 230 (§230.95 GFP), 240 (§240.6, §240.13, §240.85, §240.86, §240.87), and applicable installation requirements
  3. UL 489, Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
  4. UL 1066, Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures
  5. IEC 60947-2, Low-voltage switchgear and controlgear – Circuit-breakers
  6. IEEE Std 3002.3, IEEE Recommended Practice for Calculating AC Short-Circuit Currents in Industrial and Commercial Power Systems
  7. IEEE Std C37.13, IEEE Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures
  8. IEEE Std C37.20.1, IEEE Standard for Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear