kVATools.io ❯ Autotransformer Kit
Autotransformer Kit
Technical Documentation and Calculation Methodology
1. Introduction
The Autotransformer Kit calculates the series winding kVA (Peq), common winding kVA, conductive kVA (Pe), recommended standard unit size, terminal currents, and NEC 450.6 overcurrent protection rating for single-phase and three-phase autotransformers. It applies to fixed-ratio step-up and step-down autotransformer applications at voltages covered by IEEE C57.12.00-2021 (liquid-immersed) and IEEE C57.12.01-2020 (dry-type).
The kit does not cover variable-tap autotransformers (variacs), reduced-voltage motor starter autotransformers, or instrument transformers.
2. Autotransformer Operating Principle
An autotransformer uses a single continuous winding with a tap, rather than separate primary and secondary windings. The source is connected across the full winding; the load is connected between the tap and one end. As a result, the throughput kVA splits into two parts: an electromagnetic component transferred through the magnetic core (Peq), and an electrical or conductive component transferred directly through the shared winding conductor at the tap (Pe). Both physical windings — series and common — are rated for Peq, which determines the physical size and thermal rating of the unit. Pe bypasses the core entirely and imposes no additional winding thermal load; it is reported for systems-level accounting, not for winding sizing.
This distinguishes autotransformers from two-winding isolation transformers, where 100% of the load kVA is transferred electromagnetically. For the same load kVA, an autotransformer requires a smaller physical unit than an equivalent isolation transformer, provided the transformation ratio is low. The advantage diminishes as the ratio increases, and autotransformers with ratios above 2:1 are generally not economical.
A second consequence of the autotransformer construction is the absence of galvanic isolation between source and load. This restricts their use: NEC 450.6 and NEC 210.9 prohibit autotransformers from being used as a source for individual branch circuits where isolation is required (e.g., certain healthcare, IT, and hazardous-location systems). Note: this section was designated 450.4 in editions prior to NFPA 70-2026.
3. Definitions
Load Demand (kVAload)
The total apparent power delivered to the load at the output terminals. This is the throughput kVA used in all autotransformer calculations and corresponds to the nameplate kVA rating quoted by manufacturers. The tool accepts the load demand in five units — kVA, VA, kW, W, or Amps — and converts the entry to kVA internally before proceeding. See Section 4 for conversion details.
Series Winding kVA (Peq, kVAseries)
The electromagnetic (equivalent) kVA transferred through the magnetic core. Also referred to as equivalent two-winding kVA or winding kVA. This value determines the required physical size of the unit and is the basis for IEEE standard size selection.
Common Winding kVA (Peq, kVAcommon)
The kVA rating of the common winding. Both physical windings of an autotransformer are coils of a single two-winding transformer, so by conservation of energy through the core the common winding rating equals the series winding rating: kVAcommon = kVAseries = Peq. This is distinct from the conductive kVA defined below, with which it is sometimes conflated in older literature.
Conductive kVA (Pe, kVAconductive)
The portion of throughput kVA transferred by direct electrical connection at the tap, bypassing the core: kVAconductive = kVAload − kVAseries. This is a systems-level accounting quantity; it does not represent a winding rating and should not be used to size either winding. Pe only equals Peq at a transformation ratio of exactly 2:1, and diverges at all other ratios.
Transformation Ratio (a)
The ratio of the high-voltage terminal voltage to the low-voltage terminal voltage: a = VH / VL. All voltages are line-to-line values. For step-down connections, VH is the source and VL is the output. For step-up connections, VL is the source and VH is the output. The ratio is always expressed as a number ≥ 1.
VH and VL
VH is the higher of the two terminal voltages; VL is the lower. For three-phase systems, both are line-to-line (L-L) voltages regardless of the winding connection. Phase voltages (L-N) are derived internally where needed for winding current calculations.
Series Winding
The portion of the winding that is not common to both input and output circuits. It carries the source terminal current (Isource) and has a terminal voltage of ΔV = VH − VL.
Common Winding
The portion of the winding shared between source and load circuits. It carries the difference between the load and source terminal currents (|Iload − Isource|) by Kirchhoff's current law at the tap node, and has a terminal voltage of VL. Common winding current is the load line current minus the series winding contribution, not the full load current.
4. Load Demand Input
The Load Demand field accepts a numeric value paired with a unit selector. The tool converts the entered value to apparent power in kVA before applying any autotransformer formula. The Power Factor field is active only when the unit is W or kW; for all other units it is disabled and ignored.
| Unit | Conversion to kVAload | Power Factor Required |
|---|---|---|
| kVA | kVAload = entered value | No |
| VA | kVAload = VA / 1000 | No |
| kW | kVAload = kW / PF | Yes |
| W | kVAload = (W / 1000) / PF | Yes |
| Amps | kVAload = I × Vload / 1000 (1φ) kVAload = I × √3 × Vload / 1000 (3φ) | No |
When the unit is Amps, the entered current is treated as the load (output) terminal current. Vload is VL for step-down and VH for step-up, consistent with the terminal current convention used throughout the tool (Section 7). Power factor is not required because current in amperes already represents the apparent quantity at the terminal voltage; active and reactive components are not distinguished.
When the unit is kW or W, the Power Factor field accepts values in the range 0.01 to 1.00 (inclusive). The entered active power is divided by the power factor to obtain the apparent power in kVA. All downstream calculations — series kVA, standard size, currents, and OCPD — operate on this derived kVAload value.
The Load (Throughput) kVA output row always displays the resolved kVAload value, regardless of which input unit was used, confirming the conversion before the user reads any sized result.
5. kVA Calculations
5.1 Series Winding kVA (Peq)
The series winding kVA — also referred to as the electromagnetic or equivalent two-winding kVA, Peq — is calculated from the voltage difference and the load kVA:
where ΔV = VH − VL.
This can also be written as:
As the ratio a approaches 1 (small voltage difference), kVAseries approaches zero and the autotransformer advantage is maximum. As a approaches 2, kVAseries approaches 50% of kVAload, and the unit approaches half the size of an isolation transformer for the same load. Above a = 2, the size advantage is generally insufficient to justify the loss of isolation.
5.2 Common Winding kVA (Peq)
Because both physical windings are coils of a single two-winding transformer, by conservation of energy the common winding kVA equals the series winding kVA:
This can be verified directly from the winding voltage and the common winding current (which by Kirchhoff's current law at the tap node equals |Iload − Isource|):
Both windings must therefore be rated for the same Peq. The tool reports kVAcommon as a sizing-level output to confirm this relationship directly for the engineer.
5.3 Conductive kVA (Pe)
The conductive kVA — also called the electrical or transferred kVA — is the portion of throughput transferred by direct electrical connection at the tap, bypassing the magnetic core:
kVAconductive does not represent a winding rating and must not be used to size either winding. It is a systems-level accounting quantity showing the portion of throughput delivered without magnetic coupling; Peq + Pe always equals the throughput (nameplate) kVA. At a transformation ratio of exactly 2:1, Pe equals Peq numerically, but at all other ratios the two diverge.
6. Standard Size Selection
The standard unit size is selected as the next available standard kVA rating at or above kVAseries, not kVAload. The appropriate table is selected based on the Transformer Type input:
| Transformer Type | Governing Standard | Standard kVA Ratings (selected) |
|---|---|---|
| Dry-Type | IEEE C57.12.01-2020 | 0.5, 0.75, 1, 1.5, 2, 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500, 750, 1000, 1500, 2000, 2500 kVA |
| Liquid-Immersed | IEEE C57.12.00-2021 | 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500, 833, 1250, 1667, 2500, 3333, 5000 kVA (1φ); 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3750, 5000, 7500, 10000 kVA (3φ) |
IEEE C57.12.00-2021 classifies autotransformers with an equivalent two-winding (series) kVA of 500 kVA or less as distribution class, even if the nameplate (load) kVA exceeds 500 kVA. Autotransformers with series kVA above the distribution range are classed as power transformers and fall under IEEE C57.12.10.
The tool reports a warning if kVAseries exceeds the tabulated range, indicating that a custom or power-class unit is required.
7. Terminal Current Calculations
7.1 Single-Phase
Terminal currents are calculated using the voltage at the respective terminal. The source terminal voltage depends on the configuration direction:
| Configuration | Vsource | Vload |
|---|---|---|
| Step-Down | VH | VL |
| Step-Up | VL | VH |
Source (primary) current:
Load (secondary) current:
Series winding current:
Common winding current (the magnitude of the circulating difference current at the tap junction):
The absolute value is taken because the current direction through the common winding reverses between step-down and step-up operation. In step-down, Iload > Isource: the series winding delivers Isource to the tap node and the common winding supplies the balance required to make up Iload. In step-up, Isource > Iload and the direction reverses. The magnitude is the same in both cases for a given voltage ratio and load kVA. This is a direct consequence of Kirchhoff's current law at the tap junction.
7.2 Three-Phase
Three-phase terminal line currents are calculated using the three-phase apparent power relationship, with Vsource and Vload assigned per the table in Section 7.1:
Winding currents depend on the connection type, as the relationship between line current and winding current differs between wye and delta:
| Connection | Winding Voltage | Iseries (winding) | Icommon (winding) |
|---|---|---|---|
| Wye (Y) | VLL / √3 | = Isource (line) | = |Iload − Isource| (line) |
| Delta (Δ) | VLL | = Isource / √3 | = |Iload − Isource| / √3 |
| Open Delta | VLL / √3 | = Isource (line) | = |Iload − Isource| (line) |
In a wye connection, each winding phase sees VLL/√3 and the winding current equals the line current. In a delta connection, each winding phase sees the full VLL and the winding current is the line current divided by √3. The open delta case follows the wye convention for winding current calculation purposes, as the individual transformer units in an open delta bank are connected line-to-line. In all three cases the common winding current is the magnitude of the line current difference |Iload − Isource|, by KCL at the tap node.
8. Open Delta Connection
An open delta (V-V) bank consists of two single-phase transformers connected in a delta configuration with one unit absent. It can supply a three-phase load but delivers only 57.74% of the kVA that a closed delta bank of the same individual unit ratings would deliver. This derating factor is derived from the vector relationship of the two active phases:
When Open Delta is selected, the tool applies this derating to the entered load kVA before computing series kVA, currents, and standard size. Both the derated effective kVA and a warning are displayed. The load kVA entered by the user should represent the actual connected load, not the theoretical closed-delta bank rating.
The open delta connection is used where a third transformer unit has failed or where initial installation cost is to be minimised with provision for later addition of the third unit to restore full three-phase capacity.
9. Step-Up Configuration
In a step-up autotransformer, the source is connected to the lower-voltage (VL) terminals and the load is connected to the higher-voltage (VH) terminals. The series kVA formula is unchanged:
The tool internally maintains the convention VH > VL regardless of the selected configuration direction. When Step-Up is selected, the UI labels are adjusted to guide the user to enter the source voltage in the lower-voltage field and the output voltage in the higher-voltage field.
For terminal currents, the source and load voltages are swapped relative to step-down: Isource uses VL (the source terminal) and Iload uses VH (the load terminal). In step-up operation, the source current is therefore higher than the load current — the opposite of step-down. The common winding current magnitude is the same: |Isource − Iload|. See Section 7.1.
10. Overcurrent Protection — NEC 450.6 (NFPA 70-2026)
NEC 450.6 governs overcurrent protection for autotransformers rated 1000 V nominal or less.
10.1 Primary OCPD — NEC 450.6(A)
An individual OCPD must be installed in series with each ungrounded input conductor. The maximum permissible rating depends on the magnitude of the rated input current:
| Isource | Maximum OCPD Rating | Code Reference |
|---|---|---|
| ≥ 9 A | 125% of Isource | NEC 450.6(A)(2) |
| < 9 A | 167% of Isource | NEC 450.6(A) Exception |
The tool selects the next standard OCPD ampere rating at or above IOCPD,calc from the standard sizes listed in NEC 240.6(A):
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 A
NEC 450.6(A) also permits the primary OCPD to be omitted when the autotransformer is supplied from a system that already provides overcurrent protection within the required rating on the supply side. The tool outputs the maximum permissible primary OCPD size; the engineer is responsible for determining whether an existing upstream device satisfies this requirement.
10.2 Primary OCPD — NEC 450.6(A)(3) Next Higher Standard Size
Where Isource ≥ 9 A and 125% of Isource does not correspond to a standard ampere rating in NEC 240.6, the next higher standard rating is permitted per NEC 450.6(A)(3). The tool detects this condition and also displays the next size down as an advisory, since that lower size may be used where conductor ampacity allows. The engineer must verify.
10.3 Shunt Winding Prohibition — NEC 450.6(B)
An OCPD shall not be installed in series with the shunt (common) winding of the autotransformer — that is, the winding section between Points A and B as shown in NEC Figure 450.6(B). The tool displays this as a static advisory in the Overcurrent Protection output panel.
For three-phase systems, Isource is the line current at the source terminal voltage. For single-phase systems, Isource is the single-phase current at Vsource. In both cases Vsource is VH for step-down and VL for step-up.
11. Voltage Input and Three-Phase Convention
All voltage inputs are line-to-line (L-L) values for both single-phase and three-phase systems. This is consistent with the convention used in IEEE C57.12.00-2021 and C57.12.01-2020, where autotransformer voltage ratings are expressed as L-L values regardless of connection.
For three-phase wye-connected autotransformers, the per-phase (L-N) winding voltage is VLL/√3. This value is used internally only for winding current calculation (Section 7.2). It is not a separate user input.
For three-phase delta-connected autotransformers, the winding voltage equals VLL. The series kVA formula uses L-L voltages throughout and produces the correct result independent of connection, because the ratio ΔV/VH is the same whether computed at L-L or L-N.
12. Ratio Warning (a > 2)
When the calculated transformation ratio exceeds 2.0, the calculator displays a warning. At a = 2, the series kVA equals 50% of the load kVA. A two-winding isolation transformer for the same load would need to be rated at 100% of the load kVA. The autotransformer unit is therefore half the size, which may or may not justify the loss of isolation depending on application requirements.
For ratios significantly above 2.0, the series kVA exceeds 50% of load kVA and the physical size advantage over an isolation transformer is small. In such cases, a two-winding transformer is generally preferred because it provides galvanic isolation, which is required in many applications, and is more widely available in the relevant ratings.
13. Worked Examples
13.1 Single-Phase Step-Down, 480 V to 240 V, 50 kVA Load
Inputs: Single-phase, Step-Down, VH = 480 V, VL = 240 V, Load kVA = 50, Dry-type.
Step 1 — Transformation ratio:
Step 2 — Voltage difference:
Step 3 — Series winding kVA (Peq):
Step 4 — Common winding kVA (Peq):
Step 5 — Conductive kVA (Pe):
At a = 2:1, Peq and Pe happen to coincide numerically. Examples 13.2 and 13.4 show the general case where they diverge.
Step 6 — Standard size (dry-type, C57.12.01-2020): Next standard size at or above 25.00 kVA = 25 kVA.
Step 7 — Terminal currents:
Step 8 — Primary OCPD (NEC 450.6(A)):
Isource = 104.17 A ≥ 9 A → 125% applies.
130.21 A does not correspond to a standard size. Next standard size up = 150 A per NEC 450.6(A)(3). Next size down (125 A) is also permitted where conductor ampacity allows — engineer to verify.
13.2 Three-Phase Step-Down Wye, 480 V to 208 V, 100 kVA Load
Inputs: Three-phase, Wye, Step-Down, VH = 480 V, VL = 208 V, Load kVA = 100, Dry-type.
Step 1 — Transformation ratio:
Ratio exceeds 2.0 — ratio warning displayed.
Step 2 — Voltage difference:
Step 3 — Series winding kVA (Peq):
Step 4 — Common winding kVA (Peq):
Step 5 — Conductive kVA (Pe):
At a = 2.308, Peq (56.67) and Pe (43.33) are no longer equal, confirming the general behaviour for ratios other than 2:1.
Step 6 — Standard size (dry-type, C57.12.01-2020): Next standard size at or above 56.67 kVA = 75 kVA.
Step 7 — Terminal currents (three-phase, wye):
Wye connection: Iseries (winding) = Isource (line) = 120.28 A. The common winding current is the line-current difference by KCL at the tap:
Cross-check: common winding kVA = VLL/√3 × Icommon × 3 = (208/√3) × 157.30 × 3 / 1000 ≈ 56.67 kVA, confirming kVAcommon = kVAseries.
Step 8 — Primary OCPD (NEC 450.6(A)):
Isource = 120.28 A ≥ 9 A → 125% applies.
150.35 A does not correspond to a standard size. Next standard size up = 175 A per NEC 450.6(A)(3). Next size down (150 A) is also permitted where conductor ampacity allows — engineer to verify.
13.3 Three-Phase Open Delta, 480 V to 240 V, 30 kVA Load
Inputs: Three-phase, Open Delta, Step-Down, VH = 480 V, VL = 240 V, Load kVA = 30, Dry-type.
Step 1 — Open delta derating:
Step 2 — Transformation ratio:
Step 3 — Series winding kVA (Peq, on effective load):
Step 4 — Common winding kVA (Peq):
Step 5 — Conductive kVA (Pe):
Step 6 — Standard size (dry-type, C57.12.01-2020): Next standard size at or above 8.66 kVA = 10 kVA.
Step 7 — Terminal currents:
Step 8 — Primary OCPD (NEC 450.6(A)):
Isource = 20.83 A ≥ 9 A → 125% applies.
26.04 A does not correspond to a standard size. Next standard size up = 30 A per NEC 450.6(A)(3). Next size down (25 A) is also permitted where conductor ampacity allows — engineer to verify.
13.4 Single-Phase Step-Up, 120 V to 480 V, 100 kVA Load
Inputs: Single-phase, Step-Up, Vsource = 120 V, Vload = 480 V, Load kVA = 100, Dry-type.
Step 1 — Transformation ratio:
Ratio exceeds 2.0 — ratio warning displayed.
Step 2 — Voltage difference:
Step 3 — Series winding kVA (Peq):
Step 4 — Common winding kVA (Peq):
Step 5 — Conductive kVA (Pe):
At a = 4.000, Peq (75.00) and Pe (25.00) differ by a factor of three. Both physical windings are rated for Peq = 75.00 kVA, regardless of the smaller conductive figure.
Step 6 — Standard size (dry-type, C57.12.01-2020): Next standard size at or above 75.00 kVA = 75 kVA.
Step 7 — Terminal currents (step-up: Vsource = VL = 120 V, Vload = VH = 480 V):
Cross-check: common winding kVA = VL × Icommon / 1000 = 120 × 625.00 / 1000 = 75.00 kVA, confirming kVAcommon = kVAseries.
Note: In step-up operation, Isource > Iload because the source is the low-voltage side. This is the inverse of step-down.
Step 8 — Primary OCPD (NEC 450.6(A)):
Isource = 833.33 A ≥ 9 A → 125% applies.
1041.67 A does not correspond to a standard size. Next standard size up = 1200 A per NEC 450.6(A)(3). Next size down (1000 A) is also permitted where conductor ampacity allows — engineer to verify.
13.5 Single-Phase Step-Down, 480 V to 240 V, 45 kW Load at 0.90 PF
Inputs: Single-phase, Step-Down, VH = 480 V, VL = 240 V, Load Demand = 45 kW, Power Factor = 0.90, Dry-type.
Step 1 — Convert kW to kVA:
All subsequent steps use 50.00 kVA as kVAload. This value is confirmed in the Load (Throughput) kVA output row.
Step 2 — Transformation ratio:
Step 3 — Voltage difference:
Step 4 — Series winding kVA (Peq):
Step 5 — Common winding kVA (Peq):
Step 6 — Conductive kVA (Pe):
Step 7 — Standard size (dry-type, C57.12.01-2020): Next standard size at or above 25.00 kVA = 25 kVA.
Step 8 — Terminal currents:
Note: terminal currents are identical to Example 13.1 (50 kVA entered directly), confirming that the kW/PF conversion produces the correct apparent power basis for all calculations.
Step 9 — Primary OCPD (NEC 450.6(A)):
Isource = 104.17 A ≥ 9 A → 125% applies.
130.21 A does not correspond to a standard size. Next standard size up = 150 A per NEC 450.6(A)(3). Next size down (125 A) is also permitted where conductor ampacity allows — engineer to verify.
13.6 Three-Phase Wye, 230 kV to 115 kV, 300 MVA Power Transformer
This example illustrates the Kit's behaviour on a power-class three-phase autotransformer and is useful as a cross-check against per-phase hand calculations. The case analyses a 300 MVA three-phase wye bank at 230/115 kV line-to-line. Each phase of the bank carries 100 MVA at phase voltage (VLL/√3), a configuration commonly used in transmission-level interconnections.
Inputs: Three-phase, Wye, Step-Down, VH = 230,000 V, VL = 115,000 V, Load kVA = 300,000, Liquid-Immersed.
Step 1 — Transformation ratio:
Step 2 — Voltage difference:
Step 3 — Series winding kVA (Peq):
This is the three-phase bank total. Per phase: 150,000 / 3 = 50,000 kVA.
Step 4 — Common winding kVA (Peq):
Step 5 — Conductive kVA (Pe):
Step 6 — Standard size: 300,000 kVA throughput and 150,000 kVA series kVA exceed the C57.12.00 distribution table; the tool flags this as a power-class unit outside the tabulated range, consistent with IEEE C57.12.10 scope.
Step 7 — Terminal currents (three-phase, wye):
At this 2:1 ratio, Iseries = Icommon because the load line current splits equally between the transformed component (through the series winding) and the conductive component (through the common winding). Cross-check: common winding kVA per phase = (VLL/√3) × Icommon = (115,000/√3) × 753.07 / 1000 = 50,000 kVA, confirming kVAcommon = kVAseries on a per-phase basis.
14. Limitations and Assumptions
- Load demand may be entered in kVA, VA, kW, W, or Amps. When entered in kW or W, the power factor field is used to derive the apparent power; the entered power factor applies uniformly to the full load and does not account for mixed or varying load power factors on the same circuit. For Amps entry, the current is treated as apparent (no power factor applied); active and reactive components are not separated.
- Calculations assume sinusoidal, balanced, steady-state conditions. No harmonic derating is applied.
- Temperature rise, impedance, efficiency, and voltage regulation of the autotransformer unit are not calculated. These parameters are unit-specific and must be obtained from the manufacturer's datasheet or confirmed against IEEE C57.12.00-2021 or C57.12.01-2020 test requirements.
- The standard size output identifies the minimum standard unit size that covers the series kVA requirement. Selection of a larger standard size may be appropriate depending on load growth, service factor, or application-specific derating requirements.
- NEC 450.6 OCPD calculations apply to systems 1000 V nominal or less. For systems above 1000 V, refer to NEC 450.3 and the applicable medium-voltage protection standards.
- The open delta derating of 1/√3 (57.74%) applies to a balanced three-phase load. Unbalanced loads on open delta banks produce unequal unit loading and require separate analysis.
- Altitude and ambient temperature derating per IEEE C57.12.00-2021 and C57.12.01-2020 are not applied. Standard ratings assume ≤ 30 °C average ambient, ≤ 40 °C maximum ambient, and ≤ 1000 m altitude.
15. References
- IEEE Std C57.12.00-2021, IEEE Standard for General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers
- IEEE Std C57.12.01-2020, IEEE Standard for General Requirements for Dry-Type Distribution and Power Transformers
- IEEE Std C57.12.10-2010, IEEE Standard Requirements for Liquid-Immersed Power Transformers
- IEEE Std C57.12.90-2015, IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers
- IEEE Std C57.12.91-2011, IEEE Standard Test Code for Dry-Type Distribution and Power Transformers
- NFPA 70-2026, National Electrical Code (NEC)